Esquema Unilineal piscicultura
-
Upload
champarret-sosa -
Category
Documents
-
view
352 -
download
16
description
Transcript of Esquema Unilineal piscicultura
FECHA :
CROQUIS DE UBICACION INSCRIPCION S.E.C.
NÁ:
R.L. : DANIEL E. CORREA WALKER
RUT : 76.908.610-2
RUT : 8.749.046-7
COMUNA :
PGC SMOLT CHILE S.A.
CALBUCO
SECTOR :
PISCICULTURA
ESCALA : S/I FECHA : MAYO 2008
ACEPTACION INTERESADO INSTALADOR
PROYECTO : R. NIETO
DE ESQUEMA UNILINEAL GENERAL
PROYECTO INSTALACION ELECTRICA
LAMINA : 13 DE 16
MAURICIO GONZALEZ MU¤OZ
INGENIERO EN ELECTRICIDAD
MARTIN SKORUPPA 162 - PTO. MONTT
RUT : 14.150.770 - 2 SEC CLASE "A"
Ducto = c.p.e.s. 63 mm Ø
Cond. = Multiflex 4x107mm2 Largo = 54 Mts.ALIMENTADOR TRIFASICO SUBT.
Cond. = Multiflex 3x5,26 mm2
Ducto = c.p.e.e. 32 mm Ø
ALIMENTADOR TRIFASICO EMBUTIDOLargo = 13 Mts.
2
+ 1x21,2mm2
+ 2x5,26 mm2 + 2x8,37 mm2
ALIMENTADOR TRIFASICO A LA VISTA
Ducto = c.p.e.s. 63 mm Ø
Cond. = Multiflex 3x13,3 mm2 Largo = 15 Mts.
Ducto = c.p.e.s. 110 mm Ø
ALIMENTADOR TRIF.ASICO SUBT.
Cond. = Multiflex 3x33,6mm2 + 2x21,2mm2
Largo = 66 M.
+ 1x42mm2Cond. = Multiflex 3x67,3mm2
ALIMENTADOR TRIFASICO SUBT.Largo = 345 M.
Ducto = c.p.e.s. 110 mm Ø
Multiflex 2x8.37 mm2
21
Neutro
T.P.
Largo = 20 Mts.ALIMENTADOR TRIFAS.SUBT.
Cond. = Multiflex 3x13.27 mm2
Ducto = c.p.e.s. 1x50 mm Ø
VER DETALLE
MALLA DE TIERRA
T. P.
T.P.
Neutro
3 Fases
c.p.e.e. 50 mm ØTHHN 1 x 67 mm2
POTENCIA =12,0 KW.
T.G.Aux.2
Cond. = Multiflex 4x42,4mm2
ALIMENTADOR TRIFASICO SUBT.Largo = 80 Mts.
Ducto = c.p.e.s. 75 mm Ø
4 BARRAS DE COBRE 2.000 A.
Armarios 2000 x 800 x 600 mm.
Largo = 28 Mts.Cond. = Multiflex 3x8,37mm2
Ducto = c.p.e.s. 50 mm Ø
ALIMENTADOR TRIFASICO SUBT.
+ 2x5,26mm2
AR
Largo = 40 Mts.ALIMENTADOR TRIFASICO SUBT.
Cond. = Multiflex 4x13,3 mm2 + 1x8,37mm2
Ducto = c.p.e.s. 50 mm Ø+ 1x33,6mm2+ 1x42mm2
Cond. = Multiflex 4x85mm2
ALIMENTADOR TRIFASICO SUBT.Largo = 64 Mts.
Ducto = c.p.e.s. 110 mm ØDucto = c.p.e.s.110 mm Ø+ 1x42 mm2
Cond. = Multiflex 4x 85 mm2
ALIMENTADOR TRIFASICO SUBT.Largo = 75 Mts.
Ducto = Por Zocalo
Cond. = Multiflex 4x42,4mm2
ALIMENTADOR TRIFASICO EMBUTIDOLargo = 10 Mts. Largo = 95 Mts.
Cond. = Multiflex 4x13,3 mm2
Ducto = c.p.e.s. 63 mm Ø
ALIMENTADOR TRIF.ASICO SUBT.
+ 1x8,3mm2Ducto = c.p.e.s. 75 mm Ø
Largo = 120 Mts.
30 KW.
+ 2x21,2mm2
ALIMENTADOR TRIFASICO SUBT.
Cond. = Multiflex 3x33,6mm2
3 x 1250 A.3 x 1250 A.
EMERGENCIA
Cond. = Multiflex 18x85mm2Largo = 12 Mts.
Ducto = c.p.e.s. 3x110 mm Ø
GENERADOR
700 KVA.TRIFASICO
T. P.GE
ALIMENTADOR TRIFASICO SUBTERRANEO
GETRIFASICO700 KVA.
GENERADORT. P.
Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 18x85mm2Largo = 12 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO
EMERGENCIA
Estructura Proyectada
EXISTENTENº 633890
Estructura SAESA
THHN 2 x 33 mm2c.p.e.e. 50 mm Ø
T. P. T. S.
MALLA DE TIERRA
VER DETALLE
THHN 1 x 33 mm2c.p.e.e. 50 mm Ø
T. P.
MALLA DE TIERRA
VER DETALLE
Tipo BCámara
2 Desc. Fusibles
Transformador 5 KVA
XS 25KV. - 1 A.
c.p.e.e. 50 mm ØTHHN 2 x 33 mm2
T.G.
VER DETALLE
MALLA DE TIERRA
T. S.T. P.
Largo = 32 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO
Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 22x85mm2
RED TRIFASICA MEDIA TENSION SAESA
Al Desnudo 33.6 mm2Largo = 304 Mts.
L = 15 mtsDucto = c.a.g. 4" Conductor = XAT 3x42,4 mm2
3 Desc. Tipo CuchillasXS 25KV.
14400 / 220 V - Aislación 25 KV
Largo = Mts.Al Desnudo 33.6 mm2
FUTURO
XS 25KV. - 30 A.
Compacto de Medida
XS 25KV. 3 Desc. Tipo Cuchillas
Al Desnudo 33.6 mm2Largo = 96 Mts.
Automático
Conductor = XAT 3x42,4 mm2 3 t.p.r.s. 75 mm.
L=216 MTS.
23000 / 400 - 231 V.SUB ESTACION - 900 KVA.
VACANTE
+ 1x8,37mm2
Largo = 90 Mts.Largo = 38 Mts.
40 kVAR60 A
ALIMENTADOR TRIFASICO SUBT.
Cond. = Multiflex 5x5,26 mm2
Ducto = c.p.e.s. 40 mm Ø+ 1x67,4mm2 + 1x5,26mm2
Cond. = Multiflex 4x8.37 mm2 Largo = 45 Mts.ALIMENTADOR TRIFASICO SUBT.
Ducto = c.p.e.s.1x50 mm Ø
Cond. = Multiflex 4x8.37 mm2 + 2x5,26mm2
Ducto = c.p.e.s.1x50 mm Ø
ALIMENTADOR TRIFASICO SUBT.Largo = 55 Mts.
20 kVAR20 kVAR10 kVAR 20 kVAR30 A15 A 30 A 30 A
R
Cond. = Multiflex 6x127mm2 + 2x33mm2
ALIMENTADOR TRIFASICO
Ducto = Zócalo Tablero
Largo = 6 Mts.
ALIMENTADOR TRIFASICO SUBT.
Ducto = c.p.e.s.110 mm Ø
Cond. = Multiflex 4x107mm2 + 1x67,4mm2
Repartidor Tetrapolar 600 A.
10 kVAR15 A
Cond. = Multiflex 4x13,3 mm2
Ducto = c.p.e.s. 50 mm Ø
ALIMENTADOR TRIFASICO SUBT.Largo = 21 Mts.
40 kVAR40 kVAR 40 kVAR40 kVAR60 A 60 A60 A 60 A
40 kVAR40 kVAR45 A45 A
Largo = 16 Mts.ALIMENTADOR TRIFASICO
Cond. = Multiflex 3x42.43mm2 y 2x13mm2
GE
M
SIMBOLOGIA
Reconectador Automático
Cond. = Multiflex 22x85mm2Ducto = c.p.e.s. 3x110 mm Ø
ALIMENTADOR TRIFASICO SUBTERRANEOLargo = 6 Mts.
MS
Modulo de Control
65 kA65 kA
Largo = 16 Mts.Cond. = Multiflex 3x3.31 mm2
ALIMENTADOR CONTROL
MS
Modulo de Control y Sincronismo
y Sincronismo
T.G.Aux.de F.y A.
1
2
1
CASA CUIDADOR
5 KW./220V. AC.
Ducto = c.p.e.s. 75 mm Ø
Largo = 240 Mts.
ALIMENTADOR TRIFASICO SUBT.
Cond. = Multiflex 3x42mm2 + 1x13,3mm2
Ducto = c.p.e.s. 40 mm Ø
Largo = 120 M.
ALIMENTADOR TRIFASICO SUBT.
Cond. = Multiflex 2x13,3mm2
T. S.T. P.
THHN 1 x 21,2 mm2c.p.e.v. 25 mm Ø
T. P.
TIERRA DE PROTECCION
Ducto = c.p.e.s. 40 mm Ø
Largo = 10 M.
ALIMENTADOR TRIFASICO SUBT.
Cond. = Multiflex 3x13,3mm2 + 1x8,37mm2
Largo = 6 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO
Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 22x85mm2
PS
Reconectador
27 KV. - 600 A
PUNTA TIQUE
CHAYAHUE
Largo = 20 Mts.Cond. = Multiflex 3x13,3 mm2
Ducto = c.p.e.s. 63 mm Ø
ALIMENTADOR TRIFASICO A LA VISTA
+ 2x8,37 mm2
CAJA METALICA 800x600x250 mm. IP 55
CHASIS CUBRE ELEMENTOS 800x600 mm.
Largo = 54 Mts.ALIMENTADOR TRIFASICO SUBT.
Ducto = c.p.e.s. 63 mm Ø
Cond. = Multiflex 4x67,4mm2 + 1x33,6mm2
Largo = 38 Mts.ALIMENTADOR TRIFASICO SUBT.
Ducto = e.p.c.g. 200x100 mm
Cond. = Multiflex 4x67,4mm2 + 1x42,4mm2
Largo = 180 Mts.ALIMENTADOR TRIFASICO SUBT.
Ducto = c.p.e.s. 63 mm Ø
Cond. = Multiflex 4x13,3mm2 + 1x5,26mm2
8 KW. 3 KW.