Esquema Unilineal piscicultura

1
FECHA : CROQUIS DE UBICACION INSCRIPCION S.E.C. 1 R.L. : DANIEL E. CORREA WALKER RUT : 76.908.610-2 RUT : 8.749.046-7 COMUNA : PGC SMOLT CHILE S.A. CALBUCO SECTOR : PISCICULTURA ESCALA : S/I FECHA : MAYO 2008 ACEPTACION INTERESADO INSTALADOR PROYECTO : R. NIETO DE ESQUEMA UNILINEAL GENERAL PROYECTO INSTALACION ELECTRICA LAMINA : 13 DE 16 0$85,&,2 *21=$/(= 08f2= INGENIERO EN ELECTRICIDAD MARTIN SKORUPPA 162 - PTO. MONTT RUT : 14.150.770 - 2 SEC CLASE "A" 'XFWR FSHV PP Cond. = Multiflex 4x107mm2 Largo = 54 Mts. ALIMENTADOR TRIFASICO SUBT. Cond. = Multiflex 3x5,26 mm2 'XFWR FSHH PP ALIMENTADOR TRIFASICO EMBUTIDO Largo = 13 Mts. 2 + 1x21,2mm2 + 2x5,26 mm2 + 2x8,37 mm2 ALIMENTADOR TRIFASICO A LA VISTA 'XFWR FSHV PP Cond. = Multiflex 3x13,3 mm2 Largo = 15 Mts. 'XFWR FSHV PP ALIMENTADOR TRIF.ASICO SUBT. Cond. = Multiflex 3x33,6mm2 + 2x21,2mm2 Largo = 66 M. + 1x42mm2 Cond. = Multiflex 3x67,3mm2 ALIMENTADOR TRIFASICO SUBT. Largo = 345 M. 'XFWR FSHV PP Multiflex 2x8.37 mm2 2 1 Neutro T.P. Largo = 20 Mts. ALIMENTADOR TRIFAS.SUBT. Cond. = Multiflex 3x13.27 mm2 'XFWR FSHV [ PP VER DETALLE MALLA DE TIERRA T. P. T.P. Neutro 3 Fases FSHH PP THHN 1 x 67 mm2 POTENCIA =12,0 KW. T.G.Aux.2 Cond. = Multiflex 4x42,4mm2 ALIMENTADOR TRIFASICO SUBT. Largo = 80 Mts. 'XFWR FSHV PP 4 BARRAS DE COBRE 2.000 A. Armarios 2000 x 800 x 600 mm. Largo = 28 Mts. Cond. = Multiflex 3x8,37mm2 'XFWR FSHV PP ALIMENTADOR TRIFASICO SUBT. + 2x5,26mm2 AR Largo = 40 Mts. ALIMENTADOR TRIFASICO SUBT. Cond. = Multiflex 4x13,3 mm2 + 1x8,37mm2 'XFWR FSHV PP + 1x33,6mm2 + 1x42mm2 Cond. = Multiflex 4x85mm2 ALIMENTADOR TRIFASICO SUBT. Largo = 64 Mts. 'XFWR FSHV PP 'XFWR FSHV PP + 1x42 mm2 Cond. = Multiflex 4x 85 mm2 ALIMENTADOR TRIFASICO SUBT. Largo = 75 Mts. Ducto = Por Zocalo Cond. = Multiflex 4x42,4mm2 ALIMENTADOR TRIFASICO EMBUTIDO Largo = 10 Mts. Largo = 95 Mts. Cond. = Multiflex 4x13,3 mm2 'XFWR FSHV PP ALIMENTADOR TRIF.ASICO SUBT. + 1x8,3mm2 'XFWR FSHV PP Largo = 120 Mts. 30 KW. + 2x21,2mm2 ALIMENTADOR TRIFASICO SUBT. Cond. = Multiflex 3x33,6mm2 3 x 1250 A. 3 x 1250 A. EMERGENCIA Cond. = Multiflex 18x85mm2 Largo = 12 Mts. 'XFWR FSHV [ PP GENERADOR 700 KVA. TRIFASICO T. P. GE ALIMENTADOR TRIFASICO SUBTERRANEO GE TRIFASICO 700 KVA. GENERADOR T. P. 'XFWR FSHV [ PP Cond. = Multiflex 18x85mm2 Largo = 12 Mts. ALIMENTADOR TRIFASICO SUBTERRANEO EMERGENCIA Estructura Proyectada EXISTENTE 1 Estructura SAESA THHN 2 x 33 mm2 FSHH PP T. P. T. S. MALLA DE TIERRA VER DETALLE THHN 1 x 33 mm2 FSHH PP T. P. MALLA DE TIERRA VER DETALLE Tipo B &iPDUD 2 Desc. Fusibles Transformador 5 KVA XS 25KV. - 1 A. FSHH PP THHN 2 x 33 mm2 T.G. VER DETALLE MALLA DE TIERRA T. S. T. P. Largo = 32 Mts. ALIMENTADOR TRIFASICO SUBTERRANEO 'XFWR FSHV [ PP Cond. = Multiflex 22x85mm2 RED TRIFASICA MEDIA TENSION SAESA Al Desnudo 33.6 mm2 Largo = 304 Mts. L = 15 mts Ducto = c.a.g. 4" Conductor = XAT 3x42,4 mm2 3 Desc. Tipo Cuchillas XS 25KV. 9 $LVODFLyQ .9 Largo = Mts. Al Desnudo 33.6 mm2 FUTURO XS 25KV. - 30 A. Compacto de Medida XS 25KV. 3 Desc. Tipo Cuchillas Al Desnudo 33.6 mm2 Largo = 96 Mts. $XWRPiWLFR Conductor = XAT 3x42,4 mm2 3 t.p.r.s. 75 mm. L=216 MTS. 23000 / 400 - 231 V. SUB ESTACION - 900 KVA. VACANTE + 1x8,37mm2 Largo = 90 Mts. Largo = 38 Mts. 40 kVAR 60 A ALIMENTADOR TRIFASICO SUBT. Cond. = Multiflex 5x5,26 mm2 'XFWR FSHV PP + 1x67,4mm2 + 1x5,26mm2 Cond. = Multiflex 4x8.37 mm2 Largo = 45 Mts. ALIMENTADOR TRIFASICO SUBT. 'XFWR FSHV[ PP Cond. = Multiflex 4x8.37 mm2 + 2x5,26mm2 'XFWR FSHV[ PP ALIMENTADOR TRIFASICO SUBT. Largo = 55 Mts. 20 kVAR 20 kVAR 10 kVAR 20 kVAR 30 A 15 A 30 A 30 A R Cond. = Multiflex 6x127mm2 + 2x33mm2 ALIMENTADOR TRIFASICO 'XFWR =yFDOR 7DEOHUR Largo = 6 Mts. ALIMENTADOR TRIFASICO SUBT. 'XFWR FSHV PP Cond. = Multiflex 4x107mm2 + 1x67,4mm2 Repartidor Tetrapolar 600 A. 10 kVAR 15 A Cond. = Multiflex 4x13,3 mm2 'XFWR FSHV PP ALIMENTADOR TRIFASICO SUBT. Largo = 21 Mts. 40 kVAR 40 kVAR 40 kVAR 40 kVAR 60 A 60 A 60 A 60 A 40 kVAR 40 kVAR 45 A 45 A Largo = 16 Mts. ALIMENTADOR TRIFASICO Cond. = Multiflex 3x42.43mm2 y 2x13mm2 GE M SIMBOLOGIA 5HFRQHFWDGRU $XWRPiWLFR Cond. = Multiflex 22x85mm2 'XFWR FSHV [ PP ALIMENTADOR TRIFASICO SUBTERRANEO Largo = 6 Mts. MS Modulo de Control 65 kA 65 kA Largo = 16 Mts. Cond. = Multiflex 3x3.31 mm2 ALIMENTADOR CONTROL MS Modulo de Control y Sincronismo y Sincronismo T.G.Aux.de F.y A. 1 2 1 CASA CUIDADOR 5 KW./220V. AC. 'XFWR FSHV PP Largo = 240 Mts. ALIMENTADOR TRIFASICO SUBT. Cond. = Multiflex 3x42mm2 + 1x13,3mm2 'XFWR FSHV PP Largo = 120 M. ALIMENTADOR TRIFASICO SUBT. Cond. = Multiflex 2x13,3mm2 T. S. T. P. THHN 1 x 21,2 mm2 FSHY PP T. P. TIERRA DE PROTECCION 'XFWR FSHV PP Largo = 10 M. ALIMENTADOR TRIFASICO SUBT. Cond. = Multiflex 3x13,3mm2 + 1x8,37mm2 Largo = 6 Mts. ALIMENTADOR TRIFASICO SUBTERRANEO 'XFWR FSHV [ PP Cond. = Multiflex 22x85mm2 PS Reconectador 27 KV. - 600 A PUNTA TIQUE CHAYAHUE Largo = 20 Mts. Cond. = Multiflex 3x13,3 mm2 'XFWR FSHV PP ALIMENTADOR TRIFASICO A LA VISTA + 2x8,37 mm2 CAJA METALICA 800x600x250 mm. IP 55 CHASIS CUBRE ELEMENTOS 800x600 mm. Largo = 54 Mts. ALIMENTADOR TRIFASICO SUBT. 'XFWR FSHV PP Cond. = Multiflex 4x67,4mm2 + 1x33,6mm2 Largo = 38 Mts. ALIMENTADOR TRIFASICO SUBT. Ducto = e.p.c.g. 200x100 mm Cond. = Multiflex 4x67,4mm2 + 1x42,4mm2 Largo = 180 Mts. ALIMENTADOR TRIFASICO SUBT. 'XFWR FSHV PP Cond. = Multiflex 4x13,3mm2 + 1x5,26mm2 8 KW. 3 KW.

description

esquema unilineal electrico piscicultura tipo

Transcript of Esquema Unilineal piscicultura

Page 1: Esquema Unilineal piscicultura

FECHA :

CROQUIS DE UBICACION INSCRIPCION S.E.C.

NÁ:

R.L. : DANIEL E. CORREA WALKER

RUT : 76.908.610-2

RUT : 8.749.046-7

COMUNA :

PGC SMOLT CHILE S.A.

CALBUCO

SECTOR :

PISCICULTURA

ESCALA : S/I FECHA : MAYO 2008

ACEPTACION INTERESADO INSTALADOR

PROYECTO : R. NIETO

DE ESQUEMA UNILINEAL GENERAL

PROYECTO INSTALACION ELECTRICA

LAMINA : 13 DE 16

MAURICIO GONZALEZ MU¤OZ

INGENIERO EN ELECTRICIDAD

MARTIN SKORUPPA 162 - PTO. MONTT

RUT : 14.150.770 - 2 SEC CLASE "A"

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 4x107mm2 Largo = 54 Mts.ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x5,26 mm2

Ducto = c.p.e.e. 32 mm Ø

ALIMENTADOR TRIFASICO EMBUTIDOLargo = 13 Mts.

2

+ 1x21,2mm2

+ 2x5,26 mm2 + 2x8,37 mm2

ALIMENTADOR TRIFASICO A LA VISTA

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 3x13,3 mm2 Largo = 15 Mts.

Ducto = c.p.e.s. 110 mm Ø

ALIMENTADOR TRIF.ASICO SUBT.

Cond. = Multiflex 3x33,6mm2 + 2x21,2mm2

Largo = 66 M.

+ 1x42mm2Cond. = Multiflex 3x67,3mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 345 M.

Ducto = c.p.e.s. 110 mm Ø

Multiflex 2x8.37 mm2

21

Neutro

T.P.

Largo = 20 Mts.ALIMENTADOR TRIFAS.SUBT.

Cond. = Multiflex 3x13.27 mm2

Ducto = c.p.e.s. 1x50 mm Ø

VER DETALLE

MALLA DE TIERRA

T. P.

T.P.

Neutro

3 Fases

c.p.e.e. 50 mm ØTHHN 1 x 67 mm2

POTENCIA =12,0 KW.

T.G.Aux.2

Cond. = Multiflex 4x42,4mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 80 Mts.

Ducto = c.p.e.s. 75 mm Ø

4 BARRAS DE COBRE 2.000 A.

Armarios 2000 x 800 x 600 mm.

Largo = 28 Mts.Cond. = Multiflex 3x8,37mm2

Ducto = c.p.e.s. 50 mm Ø

ALIMENTADOR TRIFASICO SUBT.

+ 2x5,26mm2

AR

Largo = 40 Mts.ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 4x13,3 mm2 + 1x8,37mm2

Ducto = c.p.e.s. 50 mm Ø+ 1x33,6mm2+ 1x42mm2

Cond. = Multiflex 4x85mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 64 Mts.

Ducto = c.p.e.s. 110 mm ØDucto = c.p.e.s.110 mm Ø+ 1x42 mm2

Cond. = Multiflex 4x 85 mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 75 Mts.

Ducto = Por Zocalo

Cond. = Multiflex 4x42,4mm2

ALIMENTADOR TRIFASICO EMBUTIDOLargo = 10 Mts. Largo = 95 Mts.

Cond. = Multiflex 4x13,3 mm2

Ducto = c.p.e.s. 63 mm Ø

ALIMENTADOR TRIF.ASICO SUBT.

+ 1x8,3mm2Ducto = c.p.e.s. 75 mm Ø

Largo = 120 Mts.

30 KW.

+ 2x21,2mm2

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x33,6mm2

3 x 1250 A.3 x 1250 A.

EMERGENCIA

Cond. = Multiflex 18x85mm2Largo = 12 Mts.

Ducto = c.p.e.s. 3x110 mm Ø

GENERADOR

700 KVA.TRIFASICO

T. P.GE

ALIMENTADOR TRIFASICO SUBTERRANEO

GETRIFASICO700 KVA.

GENERADORT. P.

Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 18x85mm2Largo = 12 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO

EMERGENCIA

Estructura Proyectada

EXISTENTENº 633890

Estructura SAESA

THHN 2 x 33 mm2c.p.e.e. 50 mm Ø

T. P. T. S.

MALLA DE TIERRA

VER DETALLE

THHN 1 x 33 mm2c.p.e.e. 50 mm Ø

T. P.

MALLA DE TIERRA

VER DETALLE

Tipo BCámara

2 Desc. Fusibles

Transformador 5 KVA

XS 25KV. - 1 A.

c.p.e.e. 50 mm ØTHHN 2 x 33 mm2

T.G.

VER DETALLE

MALLA DE TIERRA

T. S.T. P.

Largo = 32 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO

Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 22x85mm2

RED TRIFASICA MEDIA TENSION SAESA

Al Desnudo 33.6 mm2Largo = 304 Mts.

L = 15 mtsDucto = c.a.g. 4" Conductor = XAT 3x42,4 mm2

3 Desc. Tipo CuchillasXS 25KV.

14400 / 220 V - Aislación 25 KV

Largo = Mts.Al Desnudo 33.6 mm2

FUTURO

XS 25KV. - 30 A.

Compacto de Medida

XS 25KV. 3 Desc. Tipo Cuchillas

Al Desnudo 33.6 mm2Largo = 96 Mts.

Automático

Conductor = XAT 3x42,4 mm2 3 t.p.r.s. 75 mm.

L=216 MTS.

23000 / 400 - 231 V.SUB ESTACION - 900 KVA.

VACANTE

+ 1x8,37mm2

Largo = 90 Mts.Largo = 38 Mts.

40 kVAR60 A

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 5x5,26 mm2

Ducto = c.p.e.s. 40 mm Ø+ 1x67,4mm2 + 1x5,26mm2

Cond. = Multiflex 4x8.37 mm2 Largo = 45 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s.1x50 mm Ø

Cond. = Multiflex 4x8.37 mm2 + 2x5,26mm2

Ducto = c.p.e.s.1x50 mm Ø

ALIMENTADOR TRIFASICO SUBT.Largo = 55 Mts.

20 kVAR20 kVAR10 kVAR 20 kVAR30 A15 A 30 A 30 A

R

Cond. = Multiflex 6x127mm2 + 2x33mm2

ALIMENTADOR TRIFASICO

Ducto = Zócalo Tablero

Largo = 6 Mts.

ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s.110 mm Ø

Cond. = Multiflex 4x107mm2 + 1x67,4mm2

Repartidor Tetrapolar 600 A.

10 kVAR15 A

Cond. = Multiflex 4x13,3 mm2

Ducto = c.p.e.s. 50 mm Ø

ALIMENTADOR TRIFASICO SUBT.Largo = 21 Mts.

40 kVAR40 kVAR 40 kVAR40 kVAR60 A 60 A60 A 60 A

40 kVAR40 kVAR45 A45 A

Largo = 16 Mts.ALIMENTADOR TRIFASICO

Cond. = Multiflex 3x42.43mm2 y 2x13mm2

GE

M

SIMBOLOGIA

Reconectador Automático

Cond. = Multiflex 22x85mm2Ducto = c.p.e.s. 3x110 mm Ø

ALIMENTADOR TRIFASICO SUBTERRANEOLargo = 6 Mts.

MS

Modulo de Control

65 kA65 kA

Largo = 16 Mts.Cond. = Multiflex 3x3.31 mm2

ALIMENTADOR CONTROL

MS

Modulo de Control y Sincronismo

y Sincronismo

T.G.Aux.de F.y A.

1

2

1

CASA CUIDADOR

5 KW./220V. AC.

Ducto = c.p.e.s. 75 mm Ø

Largo = 240 Mts.

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x42mm2 + 1x13,3mm2

Ducto = c.p.e.s. 40 mm Ø

Largo = 120 M.

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 2x13,3mm2

T. S.T. P.

THHN 1 x 21,2 mm2c.p.e.v. 25 mm Ø

T. P.

TIERRA DE PROTECCION

Ducto = c.p.e.s. 40 mm Ø

Largo = 10 M.

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x13,3mm2 + 1x8,37mm2

Largo = 6 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO

Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 22x85mm2

PS

Reconectador

27 KV. - 600 A

PUNTA TIQUE

CHAYAHUE

Largo = 20 Mts.Cond. = Multiflex 3x13,3 mm2

Ducto = c.p.e.s. 63 mm Ø

ALIMENTADOR TRIFASICO A LA VISTA

+ 2x8,37 mm2

CAJA METALICA 800x600x250 mm. IP 55

CHASIS CUBRE ELEMENTOS 800x600 mm.

Largo = 54 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 4x67,4mm2 + 1x33,6mm2

Largo = 38 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = e.p.c.g. 200x100 mm

Cond. = Multiflex 4x67,4mm2 + 1x42,4mm2

Largo = 180 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 4x13,3mm2 + 1x5,26mm2

8 KW. 3 KW.