Esquema Unilineal piscicultura

Post on 15-Dec-2015

352 views 16 download

description

esquema unilineal electrico piscicultura tipo

Transcript of Esquema Unilineal piscicultura

FECHA :

CROQUIS DE UBICACION INSCRIPCION S.E.C.

NÁ:

R.L. : DANIEL E. CORREA WALKER

RUT : 76.908.610-2

RUT : 8.749.046-7

COMUNA :

PGC SMOLT CHILE S.A.

CALBUCO

SECTOR :

PISCICULTURA

ESCALA : S/I FECHA : MAYO 2008

ACEPTACION INTERESADO INSTALADOR

PROYECTO : R. NIETO

DE ESQUEMA UNILINEAL GENERAL

PROYECTO INSTALACION ELECTRICA

LAMINA : 13 DE 16

MAURICIO GONZALEZ MU¤OZ

INGENIERO EN ELECTRICIDAD

MARTIN SKORUPPA 162 - PTO. MONTT

RUT : 14.150.770 - 2 SEC CLASE "A"

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 4x107mm2 Largo = 54 Mts.ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x5,26 mm2

Ducto = c.p.e.e. 32 mm Ø

ALIMENTADOR TRIFASICO EMBUTIDOLargo = 13 Mts.

2

+ 1x21,2mm2

+ 2x5,26 mm2 + 2x8,37 mm2

ALIMENTADOR TRIFASICO A LA VISTA

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 3x13,3 mm2 Largo = 15 Mts.

Ducto = c.p.e.s. 110 mm Ø

ALIMENTADOR TRIF.ASICO SUBT.

Cond. = Multiflex 3x33,6mm2 + 2x21,2mm2

Largo = 66 M.

+ 1x42mm2Cond. = Multiflex 3x67,3mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 345 M.

Ducto = c.p.e.s. 110 mm Ø

Multiflex 2x8.37 mm2

21

Neutro

T.P.

Largo = 20 Mts.ALIMENTADOR TRIFAS.SUBT.

Cond. = Multiflex 3x13.27 mm2

Ducto = c.p.e.s. 1x50 mm Ø

VER DETALLE

MALLA DE TIERRA

T. P.

T.P.

Neutro

3 Fases

c.p.e.e. 50 mm ØTHHN 1 x 67 mm2

POTENCIA =12,0 KW.

T.G.Aux.2

Cond. = Multiflex 4x42,4mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 80 Mts.

Ducto = c.p.e.s. 75 mm Ø

4 BARRAS DE COBRE 2.000 A.

Armarios 2000 x 800 x 600 mm.

Largo = 28 Mts.Cond. = Multiflex 3x8,37mm2

Ducto = c.p.e.s. 50 mm Ø

ALIMENTADOR TRIFASICO SUBT.

+ 2x5,26mm2

AR

Largo = 40 Mts.ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 4x13,3 mm2 + 1x8,37mm2

Ducto = c.p.e.s. 50 mm Ø+ 1x33,6mm2+ 1x42mm2

Cond. = Multiflex 4x85mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 64 Mts.

Ducto = c.p.e.s. 110 mm ØDucto = c.p.e.s.110 mm Ø+ 1x42 mm2

Cond. = Multiflex 4x 85 mm2

ALIMENTADOR TRIFASICO SUBT.Largo = 75 Mts.

Ducto = Por Zocalo

Cond. = Multiflex 4x42,4mm2

ALIMENTADOR TRIFASICO EMBUTIDOLargo = 10 Mts. Largo = 95 Mts.

Cond. = Multiflex 4x13,3 mm2

Ducto = c.p.e.s. 63 mm Ø

ALIMENTADOR TRIF.ASICO SUBT.

+ 1x8,3mm2Ducto = c.p.e.s. 75 mm Ø

Largo = 120 Mts.

30 KW.

+ 2x21,2mm2

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x33,6mm2

3 x 1250 A.3 x 1250 A.

EMERGENCIA

Cond. = Multiflex 18x85mm2Largo = 12 Mts.

Ducto = c.p.e.s. 3x110 mm Ø

GENERADOR

700 KVA.TRIFASICO

T. P.GE

ALIMENTADOR TRIFASICO SUBTERRANEO

GETRIFASICO700 KVA.

GENERADORT. P.

Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 18x85mm2Largo = 12 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO

EMERGENCIA

Estructura Proyectada

EXISTENTENº 633890

Estructura SAESA

THHN 2 x 33 mm2c.p.e.e. 50 mm Ø

T. P. T. S.

MALLA DE TIERRA

VER DETALLE

THHN 1 x 33 mm2c.p.e.e. 50 mm Ø

T. P.

MALLA DE TIERRA

VER DETALLE

Tipo BCámara

2 Desc. Fusibles

Transformador 5 KVA

XS 25KV. - 1 A.

c.p.e.e. 50 mm ØTHHN 2 x 33 mm2

T.G.

VER DETALLE

MALLA DE TIERRA

T. S.T. P.

Largo = 32 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO

Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 22x85mm2

RED TRIFASICA MEDIA TENSION SAESA

Al Desnudo 33.6 mm2Largo = 304 Mts.

L = 15 mtsDucto = c.a.g. 4" Conductor = XAT 3x42,4 mm2

3 Desc. Tipo CuchillasXS 25KV.

14400 / 220 V - Aislación 25 KV

Largo = Mts.Al Desnudo 33.6 mm2

FUTURO

XS 25KV. - 30 A.

Compacto de Medida

XS 25KV. 3 Desc. Tipo Cuchillas

Al Desnudo 33.6 mm2Largo = 96 Mts.

Automático

Conductor = XAT 3x42,4 mm2 3 t.p.r.s. 75 mm.

L=216 MTS.

23000 / 400 - 231 V.SUB ESTACION - 900 KVA.

VACANTE

+ 1x8,37mm2

Largo = 90 Mts.Largo = 38 Mts.

40 kVAR60 A

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 5x5,26 mm2

Ducto = c.p.e.s. 40 mm Ø+ 1x67,4mm2 + 1x5,26mm2

Cond. = Multiflex 4x8.37 mm2 Largo = 45 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s.1x50 mm Ø

Cond. = Multiflex 4x8.37 mm2 + 2x5,26mm2

Ducto = c.p.e.s.1x50 mm Ø

ALIMENTADOR TRIFASICO SUBT.Largo = 55 Mts.

20 kVAR20 kVAR10 kVAR 20 kVAR30 A15 A 30 A 30 A

R

Cond. = Multiflex 6x127mm2 + 2x33mm2

ALIMENTADOR TRIFASICO

Ducto = Zócalo Tablero

Largo = 6 Mts.

ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s.110 mm Ø

Cond. = Multiflex 4x107mm2 + 1x67,4mm2

Repartidor Tetrapolar 600 A.

10 kVAR15 A

Cond. = Multiflex 4x13,3 mm2

Ducto = c.p.e.s. 50 mm Ø

ALIMENTADOR TRIFASICO SUBT.Largo = 21 Mts.

40 kVAR40 kVAR 40 kVAR40 kVAR60 A 60 A60 A 60 A

40 kVAR40 kVAR45 A45 A

Largo = 16 Mts.ALIMENTADOR TRIFASICO

Cond. = Multiflex 3x42.43mm2 y 2x13mm2

GE

M

SIMBOLOGIA

Reconectador Automático

Cond. = Multiflex 22x85mm2Ducto = c.p.e.s. 3x110 mm Ø

ALIMENTADOR TRIFASICO SUBTERRANEOLargo = 6 Mts.

MS

Modulo de Control

65 kA65 kA

Largo = 16 Mts.Cond. = Multiflex 3x3.31 mm2

ALIMENTADOR CONTROL

MS

Modulo de Control y Sincronismo

y Sincronismo

T.G.Aux.de F.y A.

1

2

1

CASA CUIDADOR

5 KW./220V. AC.

Ducto = c.p.e.s. 75 mm Ø

Largo = 240 Mts.

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x42mm2 + 1x13,3mm2

Ducto = c.p.e.s. 40 mm Ø

Largo = 120 M.

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 2x13,3mm2

T. S.T. P.

THHN 1 x 21,2 mm2c.p.e.v. 25 mm Ø

T. P.

TIERRA DE PROTECCION

Ducto = c.p.e.s. 40 mm Ø

Largo = 10 M.

ALIMENTADOR TRIFASICO SUBT.

Cond. = Multiflex 3x13,3mm2 + 1x8,37mm2

Largo = 6 Mts.ALIMENTADOR TRIFASICO SUBTERRANEO

Ducto = c.p.e.s. 3x110 mm ØCond. = Multiflex 22x85mm2

PS

Reconectador

27 KV. - 600 A

PUNTA TIQUE

CHAYAHUE

Largo = 20 Mts.Cond. = Multiflex 3x13,3 mm2

Ducto = c.p.e.s. 63 mm Ø

ALIMENTADOR TRIFASICO A LA VISTA

+ 2x8,37 mm2

CAJA METALICA 800x600x250 mm. IP 55

CHASIS CUBRE ELEMENTOS 800x600 mm.

Largo = 54 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 4x67,4mm2 + 1x33,6mm2

Largo = 38 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = e.p.c.g. 200x100 mm

Cond. = Multiflex 4x67,4mm2 + 1x42,4mm2

Largo = 180 Mts.ALIMENTADOR TRIFASICO SUBT.

Ducto = c.p.e.s. 63 mm Ø

Cond. = Multiflex 4x13,3mm2 + 1x5,26mm2

8 KW. 3 KW.