YCIV_0210

72
GUÍA TÉCNICA YCIV0600SE-YCIV1500SE & YCIV0590HE-YCIV1380HE Revision 4 Form 201.26 EG 04 (ES 02/10) PLANTAS ENFRIADORAS DE LÍQUIDO REFRIGERADAS POR AIRE Y COMPRESOR DE TORNILLO TIPO B (513 - 1355 KW) RENDIMIENTO ESTÁNDARD SE Y ALTO RENDIMIENTO HE Symphony R134a

Transcript of YCIV_0210

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 1/72

 

GUÍA TÉCNICA

YCIV0600SE-YCIV1500SE & YCIV0590HE-YCIV1380HE

Revision 4 Form 201.26 EG 04 (ES 02/10)

PLANTAS ENFRIADORAS DE LÍQUIDO REFRIGERADAS PORAIRE Y COMPRESOR DE TORNILLO

TIPO B(513 - 1355 KW)

RENDIMIENTO ESTÁNDARD SE Y ALTO RENDIMIENTO HE

Symphony 

R134a

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 2/72

 

2

Form No. 201.26 EG 04 (ES 02/10)

TABLA DE CONTENIDOS

Características . . . . . . . . . . . . . . . . . . . . . . 3

Historia de la Planta con Variador de Velocidad (VSD) 5

Datos Nominales . . . . . . . . . . . . . . . . . . . . . 6

Especificación . . . . . . . . . . . . . . . . . . . . . . 7

Prueba a Final de Línea y Plan de Calidad . . . . . . . 10

Accesorios y Opciones . . . . . . . . . . . . . . . . . 10

Diagrama de Flujo del Refrigerante . . . . . . . . . . . 13

Siatuación de los Componentes . . . . . . . . . . . . 14

Lógica de Control de la Planta . . . . . . . . . . . . . 15

Datos de Aplicación . . . . . . . . . . . . . . . . . . . 16

Espacio Libre Necesario . . . . . . . . . . . . . . . . . 18

Conexiones Eléctricas . . . . . . . . . . . . . . . . . . 21

Datos de Selección de una Planta . . . . . . . . . . . 23

Gráfico de Pérdida de Carga . . . . . . . . . . . . . . 24

Límites de Utilización . . . . . . . . . . . . . . . . . . 25

Modelos de Rendimiento Estándar (SE) conVentiladores Estándar - Capacidades Frigorí ficas . . . 26

Modelos De Rendimiento Estándar (SE RS) ConVentiladores Ultra Silencioso - CapacidadesFrigorí ficas . . . . . . . . . . . . . . . . . . . . . . . . 28

Modelos de Rendimiento Estándar (SE LS) conVentiladores de Dos Velocidades - CapacidadesFrigorí ficas . . . . . . . . . . . . . . . . . . . . . . . . 30

Modelos de Rendimiento Estándar (SE LS) conVentiladores de Dos Velocidades (Velocidad AltaInhibida) - Capacidades Frigorí ficas . . . . . . . . . . 32

Modelos de Alto Rendimiento (HE) con VentiladoresEstándar - Capacidades Frigorí ficas . . . . . . . . . . 34

Modelos De Rendimiento Estándar (HE RS) ConVentiladores Ultra Silencioso - CapacidadesFrigorí ficas . . . . . . . . . . . . . . . . . . . . . . . . 36

Modelos de Alto Rendimiento (HE LS) con Ventiladoresde Dos Velocidades - Capacidades Frigorí ficas . . . . 38

Modelos de Alto Rendimiento (HE LS) con Ventiladoresde Dos Velocidades (Velocidad Alta Inhibida) -Capacidades Frigorí ficas . . . . . . . . . . . . . . . . 40

Modelos Estándar/Alto Rendimiento(SE & SERS/HE & HERS) - Datos Acústicos . . . . . . 42

Modelos Estándar/Alto Rendimiento(SELS/HELS) - Datos Acústicos . . . . . . . . . . . . . 43

Modelos de Rendimiento Estándar(SE) - Datos Físicos . . . . . . . . . . . . . . . . . . . 44

Modelos de Alto Rendimiento

(HE) - Datos Físicos . . . . . . . . . . . . . . . . . . . 45Modelos De Rendimiento Estándar(SE) - Características Eléctricas . . . . . . . . . . . . 46

Modelos de Alto Rendimiento(HE) - Características Eléctricas . . . . . . . . . . . . 46

Características Eléctricas(Rendimiento Estándar - 2 Circuitos) . . . . . . . . . . 47

Características Eléctricas(Rendimiento Estándar - 3 Circuitos) . . . . . . . . . . 48

Características Eléctricas(Alto Rendimiento - 2 Circuitos). . . . . . . . . . . . . 49

Características Eléctricas(Alto Rendimiento - 3 Circuitos). . . . . . . . . . . . . 50

YCIV0590HE, 0600SE y 0650SE - Dimensiones . . . . 51

YCIV0630HE, 0720SE y 0770SE - Dimensiones . . . . 52

YCIV0700HE, 0760HE y 0840SE - Dimensiones . . . . 53

YCIV0800HE Y 0920SE - Dimensiones . . . . . . . . . 54

YCIV0830HE, 0930he y 1000SE - Dimensiones. . . . . 55

YCIV1050HE - Dimensiones . . . . . . . . . . . . . . . 56

YCIV1070SE - Dimensiones . . . . . . . . . . . . . . . 57

YCIV1120HE - Dimensiones . . . . . . . . . . . . . . . 58

YCIV1180SE - Dimensiones . . . . . . . . . . . . . . . 59

YCIV12200HE y 1340SE - Dimensiones . . . . . . . . . 60

YCIV1380HE y 1500SE - Dimensiones . . . . . . . . . 61

Entrada Cables Eléctricos . . . . . . . . . . . . . . . . 62

Pérdida de Carga Lado Agua conDesrecalentador Opcional . . . . . . . . . . . . . . . . 63

Conexiones Hidráulicas en Desrecalentador Opcional .60

Especificaciones Guía Del Consultor . . . . . . . . . . 64

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 3/72

 

3

Form No. 201.26 EG 04 (ES 02/10)

CARACTERÍSTICAS

YCIV es una planta enfriadora de líquido refrigerada poraire, completamente autónoma, con compresores de tornilloaccionados por un “inverter”, diseñada para ser instaladasobre el tejado de un edificio o a nivel del suelo.

Hay dos niveles de rendimiento operativo:

YCIV Estándar

YCIV de Alto Rendimiento

El control de capacidad optimizado aumenta el rendimientooperativo de la planta enfriadora.

Cada uno de los niveles de rendimiento dispone de tresopciones acústicas:

Nivel Sonoro Estándar (modelos SE o HE) -Generalmente aplicable al funcionamiento diurno encentros de ciudades, etc.

Nivel Sonoro Reducido (RS) - Para el funcionamientodiurno donde el ruido de fondo es menor.

Nivel Sonoro Bajo (LS) - Para el funcionamiento nocturnoy diurno cerca de zonas residenciales.

Gastos de Explotación Bajos durante Todo el Año

La incorporación de tecnología de velocidad variable delcompresor, economizadores de tanque de expansión, válvulasde expansión electrónica y control de capacidad optimizado,da como resultado unos Coeficientes de RendimientoEnergético extraordinariamente elevados tanto a plena carga(Rendimiento clase A) como con cargas parciales, así comounos gastos de explotación bajos durante todo el año. Puedeincluso lograrse una mayor reducción de dichos gastos conel alto factor de potencia de 0,95 que se mantiene en toda la

gama de funcionamiento de la planta enfriadora.Se utiliza un Control Lógico Difuso (Fuzzy Logic Control)para tomar las decisiones de aumentar o reducir la velocidadde los compresores de acuerdo con el error o desvíorespecto al Punto de Consigna y a la velocidad de cambiode la temperatura del líquido frío. Esto mejora aún más elrendimiento energético, al garantizar que los compresores nofuncionen de forma innecesaria para enfriar excesivamenteel sistema.

Especí ficamente Diseñados para un Funcionamientocon Bajo Nivel Sonoro

En la actualidad, la mayoría de las ciudades tienen una legislación

rigurosa en cuanto al control de ruido y muchas aplicaciones,como por ejemplo médicas, educativas, hoteles y teatros, sonextremadamente sensibles al ruido. En tales casos, una plantaenfriadora no sólo debe satisfacer los niveles acústicos duranteel día, cuando los niveles de ruido de fondo a menudo “camuflan”el ruido de la planta enfriadora, sino también durante la nochecuando los niveles permitidos son más estrictos y los niveles deruido de fondo disminuyen.

La planta enfriadora YCIV LS ha sido específicamentediseñada para un funcionamiento de bajo nivel sonoro,con el fin de satisfacer los requisitos de emplazamientosdistintos, situando los componentes que emiten ruido juntosen un mismo lugar y encerrándolos en un compartimientoinsonorizado. Incorpora ventiladores de dos velocidadesque funcionan automáticamente a una velocidad lenta ysilenciosa cuando la temperatura ambiente disminuye por latarde y por la noche.

1.

2.

1.

2.

3.

Mayor Fiabilidad y Bajo Coste de Mantenimiento

El corazón de la planta enfriadora YCIV es el compresorsemihermético de tornillo MTS de YORK. Las siguientescaracterísticas de diseño proporcionan una mayor fiabilidady un bajo coste de mantenimiento:

Todos los motores de los compresores llevan un variadorde velocidad (VSD) exclusivo para equilibrar la velocidaddel motor con la demanda de frío; no hay válvula decorredera, muelle recuperador, ni solenoide de control.

Así pues, este compresor de doble tornillo tiene un50% menos de piezas móviles que los compresores detornillo convencionales.

Los controles de YCIV monitorizan el tiempo defuncionamiento y número de arranques del compresor yconmutan automáticamente los compresores principal ysecundario para equilibrar las horas de funcionamiento.

Las características de arranque suave del variador develocidad (VSD) eliminan toda tensión de arranque delcompresor, ya que la intensidad de arranque nuncasupera la intensidad a plena carga.

Otra ventaja de un bajo consumo de corriente al arranque esque los generadores de emergencia son más pequeños quelos que se necesitan para las plantas enfriadoras de tornilloconvencionales.

Control de Capacidad Suave y Sin Etapas

El control de capacidad es suave y sin etapas, proporcionandoun mínimo control de la capacidad del 10% en plantasenfriadoras con dos compresores y del 75% en modelos contres compresores.

La Planta Seguirá Funcionando

Se han incluido controles de limitación de la capacidad para

asegurarse de que si se sobrepasan las condiciones defuncionamiento máximas, tales como: consumo del motor,presión de aspiración o de descarga, temperatura excesivadel “inverter”, la planta seguirá funcionando para mantenerun rendimiento dentro de los límites de seguridad.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 4/72

 

4

Form No. 201.26 EG 04 (ES 02/10)

Pantalla de 80 Caracteres en Lenguaje Sencillo

El centro de control dispone de una pantalla de 80 caracteresen lenguaje sencillo, que indica las temperaturas del sistema,presiones, consumo de los motores, horas de funcionamientoy número de arranques de los compresores, frecuencia de lavariación de velocidad, hora de los arranques/paros, festivos,etc. Se proporciona una información completa para facilitar elregistro cronológico de datos, programas de mantenimientoy gestión energética.

Interfaz con Sistemas de Comunicaciones OpcionalesBacnet, Lonmark y Modbus

Conexión Eléctrica de Un Solo Punto

Por motivos de seguridad y para simplificar la instalación, laplanta YCIV se suministra de serie con un magnetotérmicobloqueable de un solo punto de conexión.

Amplia Gama de Temperaturas Ambientes

La planta enfriadora YCIV ha sido diseñada para funcionar atemperaturas ambientes de -18ºC hasta +52ºC.

Amplia Gama de Temp. de Salida del LíquidoLa planta enfriadora YCIV ha sido diseñada para proporcionartemperaturas de salida del líquido de -9ºC hasta +15ºC.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 5/72

 

5

Form No. 201.26 EG 04 (ES 02/10)

HISTORIA DE LA PLANTA CON VARIADOR DEVELOCIDAD (VSD)

1979: YORK presenta el VSD, refrigerado por agua,para aplicaciones de enfriamiento de proceso.Hasta 400 C.V.

1985: Montaje del primer VSD, refrigerado por

aire, en piso, en la industria para plantasenfriadoras centrífugas para aplicaciones deaire acondicionado. Hasta 500 C.V.

1995: Montaje del primer VSD en plantas enfriadorascentrífugas para aplicaciones de aire

acondicionado. Hasta 500 C.V.

2000: Montaje de VSD compacto en plantasenfriadoras centrífugas para aplicaciones deaire acondicionado. Hasta 1000 C.V.

2004: YORK presenta la primera planta enfriadorarefrigerada por aire, con compresor de tornillo yvariador de velocidad (VSD), del mundo.

2005: YORK recibe el Premio de Protección Climáticapor la tecnología de VSD, otorgado por laOrganización de Protección del Medio Ambientede los Estados Unidos de Norteamérica.

2006: YORK presenta la primera planta enfriadorarefrigerada por aire, con compresor de tornilloy variador de velocidad (VSD) de bajo nivelsonoro, del mundo.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 6/72

 

6

Form No. 201.26 EG 04 (ES 02/10)

DATOS NOMINALES

Opción YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV

Acústica 0600 0650 0720 0770 0840 0920 1000 1070 1180 1340 1500

Capacidad frigorífica kW* 546 593 648 695 758 832 906 960 1066 1207 1355Coef. Rendimiento Energ. (EER)* 2.90 2.87 2.91 2.88 2.96 2.96 2.96 2.93 2.94 2.96 2.96Clase de Rendimiento B C B C B B B B B B BESEER ** 4.00 3.95 3.99 3.95 3.99 4.03 4.08 4.01 4.03 4.05 4.13Presión Acústica a 10 metros dB(A) 69.4 70.4 71.6 70.3 73.3 72.1 72.1 73.9 75.9 76.1 76.4Capacidad frigorífica kW* 539 579 641 679 748 822 896 940 1045 1193 1340Coef. Rendimiento Energ. (EER)* 2.77 2.71 2.74 2.7 2.77 2.77 2.78 2.76 2.76 2.8 2.78

Clase de Rendimiento C C C C C C C C C C CESEER** 3.93 3.88 3.91 3.88 3.90 3.96 3.99 3.92 3.95 3.98 4.01Presión Acústica a 10 metros dB(A) 67.4 66.4 67.6 66.3 69.3 68.1 68.1 69.9 71.9 72.1 72.4Capacidad frigorífica kW* 539 579 641 679 748 822 896 940 1045 1193 1340Coef. Rendimiento Energ. (EER)* 2.78 2.72 2.75 2.70 2.77 2.78 2.79 2.77 2.77 2.78 2.79Clase de Rendimiento C C C C C C C C C C CESEER** 3.97 3.91 3.95 3.91 3.93 4.00 4.03 3.96 3.98 4.01 4.05

Veloc. Normal Ventil. 65.3 61.5 62.4 61.4 63.4 63.2 63 63.4 63.9 65.6 65.8Veloc. Baja Ventil. 58.5 58.5 59.3 58.3 60.3 61.2 61.2 60.1 60.7 63.6 63.5

Capacidad frigorífica kW* 523 547 607 638 702 779 857 892 987 1129 1283Coef. Rendimiento Energ. (EER)* 2.55 2.45 2.47 2.42 2.52 2.51 2.51 2.49 2.49 2.51 2.51Clase de Rendimiento D E E E D D D E E D DESEER** 3.95 3.85 3.91 3.84 3.87 3.92 3.96 3.91 3.92 3.97 4.01Presión Acústica a 10 metros dB(A) 62.4 58.2 60.1 59.3 61.3 61.2 61.2 60.1 60.7 63.6 63.5

Opción YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV

Acústica 0590 0630 0700 0760 0800 0830 0930 1050 1120 1220 1380

Capacidad frigorífica kW* 540 583 631 682 726 756 837 948 1010 1099 1244Coef. Rendimiento Energ. (EER)* 3.12 3.13 3.08 3.05 3.1 3.13 3.05 3.09 3.11 3.1 3.09Clase de Rendimiento A A B B A A B B A A B

ESEER ** 4.05 4.04 4.00 4.01 4.00 4.02 4.05 4.08 4.08 4.08 4.13Presión Acústica a 10 metros dB(A) 67.4 69.3 69.3 71.3 69.2 73 72 71.6 72.3 73.5 74.0Capacidad frigorífica kW* 531 575 625 675 720 749 828 938 1000 1088 1230Coef. Rendimiento Energ. (EER)* 2.98 2.99 2.91 2.87 2.92 2.98 2.88 2.92 2.93 2.91 2.92Clase de Rendimiento B B B C B B C B B B B

ESEER** 3.98 3.97 3.94 3.94 3.94 3.97 3.98 3.98 3.99 3.98 4.05Presión Acústica a 10 metros dB(A) 64.4 65.3 65.8 67.3 66 69 67.5 68.6 68.6 70.8 70.4Capacidad frigorífica kW* 531 575 625 675 720 749 828 938 1000 1088 1230

Coef. Rendimiento Energ. (EER)* 2.99 3.00 2.92 2.88 2.93 2.99 2.89 2.93 2.94 2.92 2.93Clase de Rendimiento B B B C B B C B B B B

ESEER** 4.01 4.00 3.98 3.97 3.98 4.00 4.02 4.02 4.03 4.02 4.08Veloc. Normal Ventil. 63 63.8 61.8 61.8 61.7 62.7 62.4 63.2 63.5 64.1 64.5Veloc. Baja Ventil. 56.8 57.5 58.6 58.9 58.8 59.8 59.8 59.3 59.7 60.8 61.0

Capacidad frigorífica kW* 513 559 604 648 696 734 800 903 965 1044 1189Coef. Rendimiento Energ. (EER)* 2.76 2.76 2.68 2.59 2.66 2.72 2.61 2.64 2.64 2.64 2.65Clase de Rendimiento C C D D D C D D D D DESEER** 4.00 3.98 3.96 3.93 3.95 3.99 3.97 3.98 3.99 4.00 4.03Presión Acústica a 10 metros dB(A) 61.4 62.3 58.1 59.3 59.2 61.2 61.2 59.3 59.7 60.8 61.1

* A 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.** ESEER = Coef. Europeo de Rendimiento Energético. ESEER = 0.03A + 0.33B + 0.41C + 0.23DA = El EER es el 100% de la capacidad a 35°C de temp. ambiente. B = El EER es el 75% de la capacidad a 30°C de temp. ambiente.

C = El EER es el 50% de la capacidad a 25°C de temp. ambiente. D = El EER es el 25% de la capacidad a 20°C de temp. ambiente.

Modelos de Rendimiento Estándar

(SE)

Modelos SE LS con

Alta Velocidad de los

Ventiladores

Inhibida

Presión Acústica a 10 metros dB(A)

Modelos con

Ventiladores de 2

Velocidades

(SE LS)

Modelos de Nivel

Sonoro Reducido(SE RS)

Modelos de Nivel

Sonoro Estándar

(SE)

Modelos de Alto Rendimiento (HE)

Modelos SE LS con

Alta Velocidad de los

Ventiladores

Inhibida

Presión Acústica a 10 metros dB(A)

Modelos con

Ventiladores de 2Velocidades

(HE LS)

Modelos de Nivel

Sonoro Estándar

(HE)

Modelos de Nivel

Sonoro Reducido

(HE RS)

 

Opción YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV

Acústica 0600 0650 0720 0770 0840 0920 1000 1070 1180 1340 1500

Capacidad frigorífica kW* 546 593 648 695 758 832 906 960 1066 1207 1355Coef. Rendimiento Energ. (EER)* 2.90 2.87 2.91 2.88 2.96 2.96 2.96 2.93 2.94 2.96 2.96Clase de Rendimiento B C B C B B B B B B BESEER ** 4.00 3.95 3.99 3.95 3.99 4.03 4.08 4.01 4.03 4.05 4.13Presión Acústica a 10 metros dB(A) 69.4 70.4 71.6 70.3 73.3 72.1 72.1 73.9 75.9 76.1 76.4Capacidad frigorífica kW* 539 579 641 679 748 822 896 940 1045 1193 1340Coef. Rendimiento Energ. (EER)* 2.77 2.71 2.74 2.7 2.77 2.77 2.78 2.76 2.76 2.8 2.78

Clase de Rendimiento C C C C C C C C C C CESEER** 3.93 3.88 3.91 3.88 3.90 3.96 3.99 3.92 3.95 3.98 4.01Presión Acústica a 10 metros dB(A) 67.4 66.4 67.6 66.3 69.3 68.1 68.1 69.9 71.9 72.1 72.4Capacidad frigorífica kW* 539 579 641 679 748 822 896 940 1045 1193 1340Coef. Rendimiento Energ. (EER)* 2.78 2.72 2.75 2.70 2.77 2.78 2.79 2.77 2.77 2.78 2.79Clase de Rendimiento C C C C C C C C C C CESEER** 3.97 3.91 3.95 3.91 3.93 4.00 4.03 3.96 3.98 4.01 4.05

Veloc. Normal Ventil. 65.3 61.5 62.4 61.4 63.4 63.2 63 63.4 63.9 65.6 65.8Veloc. Baja Ventil. 58.5 58.5 59.3 58.3 60.3 61.2 61.2 60.1 60.7 63.6 63.5

Capacidad frigorífica kW* 523 547 607 638 702 779 857 892 987 1129 1283Coef. Rendimiento Energ. (EER)* 2.55 2.45 2.47 2.42 2.52 2.51 2.51 2.49 2.49 2.51 2.51Clase de Rendimiento D E E E D D D E E D DESEER** 3.95 3.85 3.91 3.84 3.87 3.92 3.96 3.91 3.92 3.97 4.01Presión Acústica a 10 metros dB(A) 62.4 58.2 60.1 59.3 61.3 61.2 61.2 60.1 60.7 63.6 63.5

Opción YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV YCIV

Acústica 0590 0630 0700 0760 0800 0830 0930 1050 1120 1220 1380

Capacidad frigorífica kW* 540 583 631 682 726 756 837 948 1010 1099 1244Coef. Rendimiento Energ. (EER)* 3.12 3.13 3.08 3.05 3.1 3.13 3.05 3.09 3.11 3.1 3.09Clase de Rendimiento A A B B A A B B A A B

ESEER ** 4.05 4.04 4.00 4.01 4.00 4.02 4.05 4.08 4.08 4.08 4.13Presión Acústica a 10 metros dB(A) 67.4 69.3 69.3 71.3 69.2 73 72 71.6 72.3 73.5 74.0Capacidad frigorífica kW* 531 575 625 675 720 749 828 938 1000 1088 1230Coef. Rendimiento Energ. (EER)* 2.98 2.99 2.91 2.87 2.92 2.98 2.88 2.92 2.93 2.91 2.92Clase de Rendimiento B B B C B B C B B B B

ESEER** 3.98 3.97 3.94 3.94 3.94 3.97 3.98 3.98 3.99 3.98 4.05Presión Acústica a 10 metros dB(A) 64.4 65.3 65.8 67.3 66 69 67.5 68.6 68.6 70.8 70.4Capacidad frigorífica kW* 531 575 625 675 720 749 828 938 1000 1088 1230

Coef. Rendimiento Energ. (EER)* 2.99 3.00 2.92 2.88 2.93 2.99 2.89 2.93 2.94 2.92 2.93Clase de Rendimiento B B B C B B C B B B B

ESEER** 4.01 4.00 3.98 3.97 3.98 4.00 4.02 4.02 4.03 4.02 4.08Veloc. Normal Ventil. 63 63.8 61.8 61.8 61.7 62.7 62.4 63.2 63.5 64.1 64.5Veloc. Baja Ventil. 56.8 57.5 58.6 58.9 58.8 59.8 59.8 59.3 59.7 60.8 61.0

Capacidad frigorífica kW* 513 559 604 648 696 734 800 903 965 1044 1189Coef. Rendimiento Energ. (EER)* 2.76 2.76 2.68 2.59 2.66 2.72 2.61 2.64 2.64 2.64 2.65Clase de Rendimiento C C D D D C D D D D DESEER** 4.00 3.98 3.96 3.93 3.95 3.99 3.97 3.98 3.99 4.00 4.03Presión Acústica a 10 metros dB(A) 61.4 62.3 58.1 59.3 59.2 61.2 61.2 59.3 59.7 60.8 61.1

* A 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.** ESEER = Coef. Europeo de Rendimiento Energético. ESEER = 0.03A + 0.33B + 0.41C + 0.23DA = El EER es el 100% de la capacidad a 35°C de temp. ambiente. B = El EER es el 75% de la capacidad a 30°C de temp. ambiente.

C = El EER es el 50% de la capacidad a 25°C de temp. ambiente. D = El EER es el 25% de la capacidad a 20°C de temp. ambiente.

Modelos de Rendimiento Estándar

(SE)

Modelos SE LS con

Alta Velocidad de los

Ventiladores

Inhibida

Presión Acústica a 10 metros dB(A)

Modelos con

Ventiladores de 2

Velocidades

(SE LS)

Modelos de Nivel

Sonoro Reducido(SE RS)

Modelos de Nivel

Sonoro Estándar

(SE)

Modelos de Alto Rendimiento (HE)

Modelos SE LS con

Alta Velocidad de los

Ventiladores

Inhibida

Presión Acústica a 10 metros dB(A)

Modelos con

Ventiladores de 2Velocidades

(HE LS)

Modelos de Nivel

Sonoro Estándar

(HE)

Modelos de Nivel

Sonoro Reducido

(HE RS)

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 7/72

 

7

Form No. 201.26 EG 04 (ES 02/10)

ESPECIFICACIÓN

YCIV air-cooled chillers are completely assembled with allinterconnecting refrigerant piping and internal wiring, readyfor field installation. The unit is pressure tested, evacuated,and fully factory charged with refrigerant R134a and oil ineach of the independent refrigerant circuits. After assembly,an operational test is performed with water flowing throughthe evaporator to ensure that each refrigerant circuit operatescorrectly.

La estructura del equipo es de acero grueso galvanizado ylleva una capa de pintura en polvo, esmaltada al horno (colorChampagne (RAL 7006)), Anotación 9.8YR4.36/1.2 delSistema Munsell)), la cual, cuando es sometida a los ensayossegún la norma ASTMB117, de 1.000 horas de duración yuna prueba de niebla salina al 5%, ofrece un valor mínimo“6” según ASTM 1654.

Las plantas enfriadoras YCIV están diseñadas de conformidadcon EN ISO 9001 y están construidas por una empresaacreditada por la norma EN ISO 9002.

Las plantas enfriadoras cumplen con las siguientes Directivaseuropeas:

Directiva sobre Maquinaria 2006/42/CEE

Directiva sobre Compatibilidad Electromagnética2004/108/CEE

Directiva sobre Recipientes a Presión 97/23/CEE

Norma de Seguridad sobre Refrigeración MecánicaEN378-2 (2008)

O, de otro modo, cumplen con los requisitos pertinentes delas siguientes Normas y Normativas:

Norma 15 de ANSI/ASHRAE, Normativa de Seguridad

sobre Refrigeración Mecánica.Norma 70 de ANSI/NFPA, Normativa sobre InstalacionesEléctricas.

Normativa ASME sobre Calderas y Recipientes aPresión, Apartado VIII, División 1.

Norma ARI 550/590-98, Plantas Enfriadoras de Aguacon Ciclo de Compresión de Vapor.

ASHRAE 90.1, Norma sobre Energía para Edificios,excepto Edificios Residenciales de Poca Altura.

ARI 370, Clasificación Acústica de Grandes Equipos de

Refrigeración y de Aire Acondicionado en Exteriores.

Además, las plantas enfriadoras se ajustan a los requisitosde los Laboratorios de Aseguradoras (UnderwritersLaboratories) sobre la construcción de plantas enfriadoras yfacilitan la Calificación U.L./cU.L.

Gases Invernadero Fluorados

Este equipo contiene gases invernadero fluorados cubiertospor el Protocolo de Kyoto.

El factor de efecto invernadero del refrigerante (R134a) quese utiliza en este equipo es 1300.

La cantidad de refrigerante figura en la tabla de Datos Físicos,en el Capítulo 9 de este documento.

Los gases invernadero fluorados que hay en este equipo nopueden ser expulsados a la atmósfera.

Este equipo sólo debe ser revisado por técnicoscualificados.

Compresores Semiherméticos York de Doble Tornillo

Un Variador de Velocidad (VSD) de funcionamiento continuoy controlado por microprocesador proporcionará un controlde la capacidad suave, sin válvulas, del 100% al 10% dela capacidad de la planta enfriadora en equipos con doscompresores y del 100% al 7,5% en equipos con trescompresores. Además, la eliminación de la válvula correderay componentes de descarga respectivos ha dado como

resultado una reducción del 50% de piezas móviles en loscompresores.

Los compresores son del tipo de accionamiento directo,semiherméticos, de doble tornillo rotativo, incluyendo:silenciador, resistencia calefactora “durante periodos deparo” que se activa en función de la temperatura, cajade bornes con un grado de protección IP55, válvula deservicio de cierre de la descarga y carcasa de fundiciónmecanizada con precisión.

Motor del compresor hermético accesible, de altorendimiento, fiable y refrigerado por el propio gas deaspiración, flujo de gas de aspiración a través de filtro de

malla, con protección interna de sobrecarga y externade sobreintensidad en las tres fases.

Filtro de gas de aspiración y filtro de aceite registrablede 0,5 micras, situados dentro de la carcasa delcompresor.

Carcasa de fundición del compresor, mecanizada conprecisión a fin de proporcionar un espacio libre óptimoy un rendimiento excelente. Todo el compresor, desdela aspiración hasta la descarga, tiene una presión detrabajo de diseño de 24 bar.

Potencia y Electricidad

YORK cuenta con una experiencia de más de 25 años enel diseño de variadores de velocidad, específicamente paraplantas enfriadoras. El resultado es un grupo enfriador,refrigerado por aire y extremadamente fiable, que ofreceun rendimiento líder en la industria en condiciones defuncionamiento reales, carga/descarga del compresor sinválvulas, control de capacidad excelente, alto factor depotencia y arranque suave.

Todos los controles y dispositivos de arranque de losmotores que son necesarios para el funcionamiento delequipo saldrán de fábrica cableados y probados.

El Panel de Control/Potencia VSD comprende las

conexiones principales de potencia, los contactores delVSD y de los motores de los ventiladores, protectoresde sobreintensidad y cableado de fábrica. El diseñoestándar incluye un grado de protección IP55, armariometálico acabado con pintura en polvo, con puertasarticuladas y pestillo, junta de estanqueidad y puntales

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 8/72

 

8

Form No. 201.26 EG 04 (ES 02/10)

contra el viento para una mayor seguridad durante lasoperaciones de reparación o mantenimiento.

La sección del panel de potencia del VSD incluye unasalida exclusiva para el “inverter” de cada uno de loscompresores.

Los “inverters” de los variadores de velocidad (VSD) estánrefrigerados por un circuito de propilenglicol. Una bombade glicol hace circular glicol a través del disipador decalor del VSD para enfriar los componentes de potencia.

A continuación, el glicol pasa por varias hileras inferioresde la batería condensadora para disipar el calor.

El panel incluye una puerta de acceso a la pantalla decontrol, de forma que se pueda acceder a la pantalla ya los dispositivos de control sin necesidad de abrir laspuertas del armario principal.

Los modelos con dos y tres compresores disponen,de serie, de una conexión eléctrica de un solo punto.Además, todos los modelos se suministran con untransformador de control, montado y cableado enfábrica, que suministrará todo el voltaje de controldel equipo desde la alimentación de red del mismo.

El transformador utiliza tensión de red en el lado delprimario y proporciona 115 V/1 fase en el secundario.

El panel de potencia va equipado con un magnetotérmicomontado en fábrica, en el punto de entrada de laconexión de un solo punto, que proporciona el mediode desconexión de la potencia y de protección contracortocircuitos. Una palanca de accionamiento bloqueablese extiende por la puerta del panel de potencia, de formaque se pueda desconectar la potencia sin necesidad deabrir ninguna de las puertas del panel.

Los motores de los compresores están accionados porun variador de velocidad. Así pues, el consumo delmotor nunca sobrepasa la intensidad nominal a plenacarga, proporcionando arranques suaves sin puntasde sobreintensidad. Esto elimina el calentamiento yesfuerzo de los motores que normalmente se producecon arrancadores convencionales. Además, al eliminarla acumulación de calor durante el arranque, el tiempode inactividad que se necesita entre arranques se reducea un máximo de dos minutos.

Muchas empresas de servicios cobran un precio adicionalsi el factor de potencia es inferior a 0,95. Dichos ajustes/ penalizaciones por factor de potencia pueden afectartanto a las tarifas habituales como a los gastos dedemanda. Todos los modelos YCIV tienen un factor de

potencia a plena carga del 95% y mantienen este nivelen toda la gama de funcionamiento. Las especificacionesdeben siempre exigir que sea el Contratista Instalador elresponsable de los costes adicionales del suministro einstalación de condensadores de corrección del factorde potencia, si no vienen montados y cableados defábrica.

Todos los cables de potencia vistos se canalizan a travésde tubo portacables

Circuitos Frigorí ficos

Se suministra un circuito frigorífico independiente porcompresor. Todos los circuitos llevan tubo de cobre formado

en una máquina de doblar controlada por ordenador, con elfin de reducir el número de juntas soldadas, dando comoresultado un sistema fiable a prueba de fugas.

Los componentes de la línea de líquido comprenden:válvula de cierre manual con boca de carga, filtrosecador de gran absorción con elemento extraíble,

mirilla con indicador de humedad y válvula de expansiónelectrónica.

Las líneas de descarga llevan una válvula de servicio decierre manual del compresor (Ver el apartado Opcionesy Accesorios sobre la válvula de la línea de aspiración).

En cada circuito frigorífico va un tanque de expansiónpara aumentar el rendimiento del sistema. La presión detrabajo de diseño es de 31 bar.

Separadores de aceite externos aislados sin piezasmóviles, con una presión de trabajo de diseño 24 bar.

La presión diferencial del circuito frigorífico proporcionaun flujo de aceite a través de un filtro intercambiable de0,5 micras, tipo cartucho, interno al compresor.

Las líneas de aspiración, los separadores de aceite ylos tanques de expansión van recubiertos de materialaislante de célula cerrada.

Evaporador

El equipo lleva un evaporador multitubular de expansióndirecta y alto rendimiento. Cada uno de los circuitos

frigoríficos consta de 2 pasos, con líquido frío fluyendo por lacarcasa con deflectores.

La presión de trabajo de diseño del evaporador es de 10,3bar en el lado de la carcasa y de 16 bar en el lado de lostubos (lado del refrigerante).

Construido y marcado conforme a la Directiva sobreRecipientes a Presión y sometido a una prueba depresión de acuerdo con la Normativa de Seguridad sobreRefrigerantes EN 378 o Normativa sobre Recipientes aPresión ASME, Apartado VII, División (1). El lado aguaqueda exento según el párrafo U-1, c, (6).

Los defl

ectores de agua están fabricados con acerogalvanizado para resistir a la corrosión.

Se suministran cabezales desmontables para poderacceder a los tubos de cobre sin costura, interiormenteranurados.

Se incluyen conexiones de purga y vaciado de agua.

El evaporador va equipado con una resistenciacalefactora controlada termostáticamente paraproporcionar protección hasta -29ºC de temperaturaambiente y aislada con espuma flexible de célula cerradade 19 mm de espesor.

Los colectores de agua disponen de ranuras Victaulic deserie y opcionalmente pueden suministrarse con bridas.

Condensador

Los modelos Estándar (SN) y de Nivel Sonoro Reducido(RS) incorporan condensadores con ventiladores de unasola velocidad. Los modelos de Nivel Sonoro Bajo (LS) llevanventiladores de dos velocidades.

Los ventiladores están dinámica y estáticamenteequilibrados, con accionamiento directo y álabes deun material compuesto con refuerzo de fibra de vidrio,resistente a la corrosión, de sección totalmente perfilada,

proporcionando así una descarga de aire vertical através de orificios alargados para un mejor rendimientoy bajo nivel de ruido.

Se suministran protecciones de tela metálica gruesarecubierta de PVC.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 9/72

 

9

Form No. 201.26 EG 04 (ES 02/10)

Los motores de los ventiladores son de alto rendimiento,accionamiento directo, 6 polos en los modelos Estándar(SN), 8 polos en los modelos de Nivel Sonoro Reducido(RS) y Nivel de Sonoro Bajo (LS), trifásicos, clase “F”,con protector de sobreintensidad, del tipo totalmentecerrado y cojinetes de bolas con doble sellado ylubricación permanente.

Las baterías condensadoras de tubos de aletas estánfabricadas a base de tubos de cobre sin costura, interiormenteranurados, alto coeficiente de condensación, resistentes

a la corrosión, dispuestos al tresbolillo y mecánicamenteexpansionados en aletas de una aleación de aluminioresistente a la corrosión, con collarín de máxima altura.

El enfriamiento de aceite se realiza canalizándolodesde el separador, pasando a través de varias hilerassuperiores de la batería condensadora y devolviéndoloal compresor.

La presión de trabajo de diseño es de 24 bar.

Controles por Microprocesador

El sistema de control por microprocesador proporciona uncontrol automático del funcionamiento de la planta enfriadora,

incluyendo el arranque/paro y carga/descarga de loscompresores, temporizadores de antirreciclaje, ventiladoresde los condensadores, bomba del evaporador, resistenciacalefactora del evaporador, contactos de las alarmas delequipo y contactos de la señal de funcionamiento.

La planta enfriadora se reama automáticamente y vuelveal funcionamiento normal después de un fallo eléctrico.

El programa operativo del equipo se guarda en la memoriapermanente. Los puntos de consigna programados enobra se guardan durante cinco años en la memoria RTC(Reloj de Tiempo Real), soportada por una pila de litio.

Se suministran contactos de alarmas para alertasremotas relativas a cualquier fallo de seguridad delequipo o del sistema.

Pantalla y Teclado

Pantalla de cristal líquido de 80 caracteres que puede leersetanto con luz solar directa como por la noche mediante laretroiluminación por LED. Con cada planta enfriadora sesuministra un teclado con pantalla.

La pantalla y el teclado son accesibles a través de una puertade acceso, sin necesidad de abrir las puertas del armarioprincipal de control/eléctrico.

La pantalla facilita puntos de consigna, estado, característicaseléctricas, temperaturas, presiones, bloqueos de seguridad ydiagnósticos del equipo, sin usar una pantalla codificada.

El teclado sellado incluirá un interruptor de Marcha/Paro delequipo.

Puntos de consigna programables:idioma de lectura;

temperatura de salida del líquido frío:

punto de consigna, campo de control;

control local o remoto;

unidades de medida;

compresor principal/secundario;

gama de reajuste máximo del punto de consigna delagua fría.

Datos de Lectura:

temperaturas de retorno y de salida del líquido frío;

temperatura ambiente;

identificación del compresor principal;

reloj y programación;

variable fuera de límites;

indicación de entrada remota;

reajuste del punto de consigna del líquido frío;

historial de las diez últimas paradas por anomalía;

presiones y temperaturas de aspiración y descarga delos compresores y del aceite;

recalentamiento de la aspiración y de la descarga;

porcentaje respecto a plena carga;

horas de funcionamiento, arranques y estado deltemporizador de antirreciclaje;

Mensajes de estado de anulación manual, desconexióndel equipo, funcionamiento del compresor, permiso defuncionamiento, parada controlada a distancia, sin cargafrigorífica, parada diaria/de festivos, temporizador deantirreciclaje.

Durante condiciones extremas o inusuales (p.ej. bateríascondensadoras bloqueadas, temperatura ambiente superioral máximo previsto, etc.), el sistema de control de la plantaenfriadora evitará que se produzca una parada de seguridadvariando los mandos de la planta y la producción de carga

de frío con el fin de permanecer en-línea y evitar que sealcancen los límites de seguridad. Esto permite la máximacapacidad de refrigeración posible hasta que se elimina lacondición inusual y evita paradas costosas.

El sistema hace un seguimiento de los siguientes parámetrosy mantiene la máxima producción de frío posible sin parar elequipo:

consumo del motor;

presión de aspiración;

presión de descarga

Se suministran seguridades del sistema para que loscompresores individuales realicen paradas con rearmeautomático (se precisa un rearme manual después del tercerdisparo en 90 minutos). Las seguridades comprenden:

alta presión o temperatura de descarga;

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 10/72

 

10

Form No. 201.26 EG 04 (ES 02/10)

baja presión de aspiración;

alto / bajo consumo del motor;

elevada temperatura del motor;

presostato de alta;

alta / baja presión diferencial de aceite;

elevada temperatura de aceite;

bajo recalentamiento en la aspiración;

anomalía crítica de algún sensor;

alto o bajo consumo de corriente;

pérdida de fase/alimentación monofásica;

sobrecarga del devanado del motor;

baja tensión.

Se suministran seguridades del sistema para que la plantaenfriadora realice una parada con rearme automático en lascondiciones siguientes:

alta o baja temperatura ambiente;

baja temperatura de salida del líquido frío;

bajo voltaje (caída de tensión);

funcionamiento del interruptor de flujo.

PRUEBA A FINAL DE LÍNEA Y PLAN DECALIDAD

Prueba de fugas

Después de montar el equipo, los circuitos frigoríficos son

sometidos, individualmente, a una prueba de estanqueidadcon nitrógeno.

Prueba de resistencia

Se hace el vacío en el circuito y se carga con una mezclade helio. Los lados de alta y baja presión de los circuitosfrigoríficos se prueban por separado a sus presiones detrabajo de diseño para asegurarse de que se mantienela presión. Se usa un detector de fugas electrónico paracomprobar todas las juntas de los circuitos frigoríficos y versi hay indicios de algún escape.

Prueba de funcionamiento

La planta enfriadora se conecta a un circuito hidráulico ya una fuente de alimentación eléctrica y se hace funcionarcada circuito frigorífico durante un mínimo de 10 minutospara comprobar que todo funciona satisfactoriamente. Si seproduce una parada de seguridad, se soluciona el problemay se vuelve a probar el sistema.

Al finalizar la prueba, se vacía el evaporador y se realiza unaprueba final de estanqueidad (usando un detector de fugas).Luego se inspecciona el equipo y se prepara para el envío.

ACCESORIOS Y OPCIONES

Opciones Acústicas

Existen tres opciones acústicas para adaptarse a los distintosemplazamientos donde se instalan las plantas enfriadorasrefrigeradas por aire:

La opción de nivel sonoro Estándar (SE y HE) disponede ventiladores que funcionan a velocidad normal y sincubierta del compresor.

Esta opción se usa normalmente en zonas no sensibles alruido, como por ejemplo, zonas industriales o lugares conmucho ruido de tráfico rodado, etc.

La opción de nivel sonoro reducido (RS) dispone deventiladores que funcionan a velocidad normal y concubierta del compresor no insonorizada.

Esta opción se usa normalmente para el funcionamientodiurno donde el ruido de fondo es inferior al del tráfico normalde la ciudad, etc.

La opción de nivel sonoro bajo (LS) dispone deventiladores de 2 velocidades y cubierta insonorizantedel compresor.

En condiciones de alta temperatura ambiente, los ventiladoresfuncionan a velocidad normal y conforme desciende latemperatura ambiente, la velocidad de los mismos se reduceautomáticamente a velocidad lenta. Si se necesita un nivelsonoro muy bajo en cualquier condición de temperaturaambiente, se puede inhibir la velocidad normal de losventiladores.

Normalmente esta opción es para lugares próximos azonas residenciales, hoteles, hospitales, etc., donde losventiladores funcionan a velocidad normal durante el día,cuando los niveles acústicos son apreciables, y a velocidadlenta durante la tarde y noche cuando los niveles de ruido defondo son inferiores

Opción de Eficiencia Energética

La opción de control de capacidad optimizada aumentael Coeficiente de Rendimiento Energético en cualquiercondición de funcionamiento.

Protección Batería Condensadora

Los materiales constructivos de la batería condensadoraestándar comprenden aletas de aluminio, tubos de cobrey soportes galvanizados de los tubos para una buenaresistencia general contra la corrosión.

No obstante, estos materiales no son apropiados paratodos los ambientes. El diseñador de la instalación puedeadoptar los pasos necesarios para inhibir la corrosión delas baterías en ambientes rigurosos y mejorar la vida útil delequipo eligiendo entre estas opciones de fábrica en basea los parámetros del proyecto y a los factores ambientales

respectivos:BATERÍAS CONDENSADORAS DE ALETAS CONPRE-RECUBRIMIENTO - Las baterías condensadorasrefrigeradas por aire están construidas a base de aletasde aluminio recubiertas de pintura epóxida. Esto puedeproporcionar una resistencia a la corrosión comparable abaterías de aletas de cobre en lugares típicos costeros.

Ya sean estas o las baterías con post-recubrimiento (acontinuación), se recomiendan para equipos que se instalenen lugares costeros o donde la niebla salina pueda afectaral equipo.

BATERÍAS CONDENSADORAS CON POST-RECUBRIMIENTO EN BAÑO EPÓXIDO - El equipoestá construido con baterías condensadoras de aletascuradas en baño epóxido.

Esta es otra posibilidad para aplicaciones en zonas costerasy otras de tipo corrosivo (a excepción de álcalis, oxidantes y

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 11/72

 

11

Form No. 201.26 EG 04 (ES 02/10)

bromos húmedos fuertes, cloro y flúor en concentracionessuperiores a 100 ppm).

BATERÍAS CONDENSADORAS DE ALETAS DE COBRE- Equipo construido a base de baterías condensadorasde tubos de cobre con aletas de cobre.

Éstas no son recomendables para equipos que puedan estarexpuestos a lluvia ácida.

Opción Recuperación de Calor

Desrecalentadores montados en fábrica en las líneas dedescarga de los compresores de los circuitos 1 y 2, paraproporcionar agua caliente durante el funcionamiento enrefrigeración.

Paneles Protectores del Equipo

Paneles Metálicos (todo el equipo) - Protecciones detela metálica gruesa soldada y recubierta de cloruro depolivinilo (PVC) negro estable a los rayos UV, montadasen el exterior del equipo (montaje de fábrica).

Protegen los laterales de las baterías condensadoras y evitanel acceso no autorizado a los componentes refrigerantes

(compresores, tuberías, evaporador, etc.) y no obstanteproporcionan aire gratuito. Esto puede reducir los costesde instalación al eliminar la necesidad de un vallado caroindependiente.

Opciones del Evaporador

Para facilitar la instalación, las conexiones hidráulicas delevaporador pueden estar a la derecha o a la izquierda,vistas desde el lado del panel de control. De serie sesuministran conexiones de mano izquierda.

Aislamiento de 38 mm - Se facilita aislamiento de dobleespesor (montaje de fábrica).

Kit de junta con bridas Victaulic PN10 (10 bar) que sesuministra suelto para su instalación en obra. Incluyebrida y contrabrida, así como toda la tornillería y juntasnecesarias.

Interruptor de flujo - Resistente al vapor, presión detrabajo de diseño 10,3 bar, de -28,9ºC a 121,1ºC conconexión de 1” BSP para montaje vertical en tuberíahorizontal. Con cada equipo debe suministrarse esteinterruptor de flujo, o equivalente, (montaje en obra).

Presostato diferencial montado en obra para proteger alevaporador contra pérdidas de caudal de líquido

Interfaz con Sistema de Automatización de Edificios(BAS)

Las posibles entradas de BAS son:

Temperatura de Salida del Líquido Frío

Cada entrada BAS puede aceptar un rearme a través de unaseñal de 0 a 10 V.c.c., o de 2 a 10 V.c.c. o de 0 a 20 mA c.c.o de 4 a 20 mA c.c.

Montaje Antivibratorio

Los soportes antivibratorios de neopreno ofrecen unmuy buen rendimiento en la mayoría de casos, con uncoste mínimo (montaje en obra).

Soportes antivibratorios de muelle regulables de 1”.Soportes de muelle y tipo jaula, para montar debajo delas viguetas de la base del equipo. La flexión nominalde 1” puede variar ligeramente según el caso (montajeen obra).

Las instalaciones sobre tejado deben llevar soportesantivibratorios tipo muelle.

Soportes Antivibratorios de Muelle de 2” contra Seísmos.Los soportes antivibratorios de muelle semiempotradosSpring-Flex incorporan una robusta carcasa de acerosoldada, con topes limitadores verticales y horizontales.Las carcasas están diseñadas para soportar una fuerzaacelerada mínima de 1,0 gr en todas direcciones, hasta51 mm. Si bien son regulables, la flexión puede variarligeramente según el caso (montaje en obra).

Válvulas de Seguridad Dobles

Dos válvulas de seguridad en paralelo, una de las cuales esoperativa para ayudar en la sustitución de una de las válvulasdurante los trabajos de mantenimiento

Salmuera a Baja Temperatura

Modificaciones de control para funcionar con una temperaturade salida del líquido de -9ºC.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 12/72

 

12

Form No. 201.26 EG 04 (ES 02/10)

DIAGRAMA DE FLUJO DEL REFRIGERANTE

AceiteLíquido a baja presiónVapor a Baja Presión Recalentado

Vapor a Alta Presión Recalentado

Vapor a Media Presión

Líquido a Alta Presión Subenfriado

Compresor Separadorde Aceite

Evaporador

Tanque deExpansión

Entradade líquido

Salida delíquido frío

Solenoide Economizador

Batería Enfriadora de Aceite

Batería Condensadora

Válvula de alimentación

con motor paso a paso

Válvula de desagüe

con motor paso a paso

El refrigerante líquido a baja presión entra en los tubos delevaporador y es evaporado y recalentado por la energía

térmica que absorbe del agua fría que pasa por la carcasa delevaporador. El vapor a baja presión entra en el compresor,donde aumentan la presión y el recalentamiento. El vapor aalta presión pasa a través del separador de aceite, dondese elimina el aceite del refrigerante y se recircula hacia elcompresor a través del enfriador de aceite. El vapor a altapresión, sin aceite, es alimentado a la batería condensadorarefrigerada por aire, donde se elimina el calor al aire, que esforzado por los ventiladores a atravesar la superficie de labatería. El líquido refrigerante totalmente condensado entraen la válvula de alimentación del motor paso a paso queregula el caudal de líquido para mantener un nivel constanteen el Tanque de Expansión. La válvula de vaciado del motorpaso a paso funciona como una Válvula de Expansión

Electrónica y regula el caudal de refrigerante que va hacia elevaporador en base al recalentamiento de la aspiración delcompresor. La Válvula Solenoide del Economizador regulala alimentación de vapor a media presión que va a la bocadel economizador del compresor. Cuando la válvula estáabierta, el vapor refrigerante se vaporiza instantáneamenteen el tanque de expansión para proporcionar subenfriamientoadicional al líquido que hay en el tanque. Entonces, el líquidosubenfriado es alimentado al evaporador, aumentandoasí tanto el subenfriamiento como el recalentamiento ymejorando, por tanto, la capacidad frigorífica.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 13/72

 

13

Form No. 201.26 EG 04 (ES 02/10)

SIATUACIÓN DE LOS COMPONENTES

Equipo Estándar

Equipo de Bajo Nivel Sonor

Compresor

Evaporador

Válvula Solenoide

del Economizador

Economizador de Expansión

Batería Condensadora

Ventilador del Condensador

Válvula de Serviciode Descarga

Válvula de

desagüe con

motor pasoa paso

Válvula dealimentación

con motor paso a paso

VálvulaSolenoide

de la Línea

de Líquido

Filtro Secador

Separador de Aceite

Válvula de

Seguridad

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 14/72

 

14

Form No. 201.26 EG 04 (ES 02/10)

LÓGICA DE CONTROL DE LA PLANTA

Control Optimizado por Coef. Europeo de RendimientoEnergético Estacional (ESEER)

Un Control Anticipatorio Inteligente determina cuántoscompresores deben arrancar para satisfacer la cargafrigorífica actual. La lógica “inteligente” puede reducir elfuncionamiento de ciclos cortos y el tiempo de carga enun arranque de agua caliente y poner en marcha todos loscompresores simultáneamente.

Para lograr un mayor rendimiento, es deseable quefuncionen cuantos compresores sea posible. La lógica decontrol anticipatorio inteligente mantendrá en línea el mayornúmero de compresores posible y reducirá la velocidad enun intento por optimizar el uso de toda la superficie tubulardel evaporador.

Últimofuncionamiento,

inferior a 5 minutos

NoTiempo de

inactividad, inferior a5 minutos

No Velocidad de cambio de latemp. del líquido frío.

Desviación de la temp.respecto al límite superior

del punto de consigna

Sí Sí Sí  

Reducir el númerode compresores que

tiene que arrancar

Reducir el númerode compresores que

tiene que arrancar

Reducir el número decompresores que tiene que

arrancar

Continuar

Ajustar el número de compresoresa arrancar = número de

compresores en el equipo

Frecuencia Mínima de Arranque del Variador de Velocidad(VSD)

La frecuencia mínima de arranque del VSD se basa en latemperatura ambiente y determina la frecuencia máximahasta la cual ascienden los compresores en el arranque(rampa de arranque). A temperaturas ambientes máselevadas, se necesitan mayores velocidades de los motorespara que haya una refrigeración adecuada de los mismos; ya temperaturas ambientes menores, se necesitan mayores

velocidades de los motores para crear una presión diferencialde aceite al arranque.

Frecuencia Mínima de Funcionamiento del Variador deVelocidad (VSD)

La frecuencia mínima de funcionamiento del VSD delcompresor se basa en la temperatura ambiente y determina lafrecuencia a la cual se permite que funcionen los compresoresconforme se descarga el sistema. A temperaturas ambientesmás elevadas, se necesitan mayores velocidades de losmotores para refrigerar los motores de los compresores.

El gráfico ilustra la variación de las frecuencias Mínimas de

Arranque y de Funcionamiento del VSD.

100

95

90

85

80

75

70

6560

55

50

45

4040 42 44 46 48 50 52

100

95

90

85

80

75

70

6560

55

50

45

4040 42 44 46 48 50 52

Temperatura Ambiente °C

   F  r  e  c  u  e  n  c   i  a   M   í  n   i  m  a   (   H  z   )

   d  e   l   V  a  r   i  a   d  o  r   d  e   V  e   l  o  c   i   d  a   d

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 15/72

 

15

Form No. 201.26 EG 04 (ES 02/10)

Control Anticipatorio Inteligente de Carga/Descarga yArranque de Compresores Adicionales

Límite Sup.

Pto. Cons.+CR

Punto de Consigna

Límite InferiorPto. Cons. -CR     C    a

    m    p    o     d    e     C    o    n     t    r    o     l     (     C     R     )

Durante los primeros 30 segundos después de que uncompresor alcanza la frecuencia de arranque, se inhibe lacarga/descarga. Al cabo de 30 segundos, la lógica de controlmira la temperatura de salida del líquido, la compara conel punto de consigna más el campo de control y toma ladecisión de cargar o descargar. Conforme se necesita másrefrigeración, el microprocesador de la placa de control de laplanta enfriadora aumenta la velocidad del compresor a razónde 1 Hz cada 2 segundos, hasta alcanzar el nivel de cargacorrespondiente. La carga seguirá mientras la temperatura

de salida del líquido sea superior al punto de consigna másel campo de control.

Si no se alcanza la temperatura del líquido frío, y está porencima del punto de consigna más el campo de control, elmicroprocesador pondrá en marcha un compresor más, ytodos los compresores se acelerarán hasta la frecuencia dearranque.

Si la capacidad frigorífica supera la demanda, elmicroprocesador de la placa de control reducirá la velocidaddel compresor a razón de 0,1 a 1 Hz cada 2 segundos, hastaque la temperatura de salida del líquido aumente hastasituarse dentro del campo de control.

Control Lógico Difuso (Fuzzy Logic Control)

El control lógico difuso (Fuzzy Logic Control) toma decisionespara aumentar o reducir la capacidad de acuerdo con el erroro desvío respecto al Punto de Consigna y a la velocidad decambio de la temperatura del líquido frío.

En la mayoría de situaciones, cuando la temperatura dellíquido frío es superior al punto de consigna más el campode control, el microprocesador de la placa de control seguiráaumentando la velocidad de los compresores para aumentarla capacidad de la planta enfriadora, hasta que la temperaturadisminuya y se sitúe dentro de la banda del Límite Superiordel Punto de Consigna. Conforme descienda la temperatura

y se acerque al Límite Superior del Punto de Consigna(Punto de Consigna + campo de control), la lógica “fuzzy”del microprocesador empezará a considerar la velocidadde cambio antes de seguir cargando. Si la velocidad decambio disminuye demasiado aprisa y hay posibilidad desobreenfriamiento por inercia, el microprocesador de la placade control de la planta enfriadora puede decidir no seguiraumentando la velocidad. La siguiente tabla ilustra la Carga/ Descarga con Fuzzy Logic frente a Error.

Desvio respecto al Pto. Cons.

Error Error* Error

Negativo Cero PositivoVelocidad de Cambio

de la Temp. Descendente DESCARGAR DESCARGAR MANTENER

Velocidad Cero DESCARGAR MANTENER MANTENER

Velocidad de Cambio

de la Temp. AscendenteM ANT ENER CARGAR CARGAR

* Error Cero es cuando la temp. del líquido está en el Punto de Consigna.

Velocidad de Cambio

de la Temp. del Líquido

DATOS DE APLICACIÓN

Emplazamiento del Equipo

Para lograr un rendimiento óptimo y un funcionamiento sinproblemas, es fundamental que el lugar donde se vaya ainstalar equipo sea satisfactorio en cuanto a emplazamiento yespacio necesario para el modelo en cuestión. Es importanteasegurarse de que se mantiene un espacio mínimo de accesopara los trabajos de limpieza y mantenimiento.

Instalación en ExterioresLos equipos pueden instalarse a nivel del suelo, sobre unabase nivelada apropiada que sea capaz de soportar el pesodel equipo sin problemas, o bien sobre tejado. En amboscasos se necesita una aportación de aire adecuada. Hay queevitar lugares en los que la emisión acústica y la descarga deaire procedentes del equipo puedan resultar molestas.

El lugar elegido para instalar el equipo debe estar expuesto alsol lo menos posible y lejos de salidas de humos de calderasu otras fuentes de sustancias químicas suspendidas en elaire que pudieran atacar las baterías condensadoras y laspiezas de acero del equipo.

Si el equipo está situado en una zona accesible a personasno autorizadas, deben adoptarse las medidas oportunas paraevitar el acceso colocando una valla protectora. Ello ayudaráa prevenir la posibilidad de actos vandálicos, daños fortuitoso que sufra posibles daños por la retirada no autorizada delas protecciones, o de que se puedan abrir los paneles deforma que queden al descubierto elementos giratorios o dealto voltaje.

En lugares a nivel del suelo, el equipo debe instalarsesobre una bancada de hormigón adecuada, que estéplana y nivelada y que se prolongue de modo que soportecompletamente los dos perfiles laterales de la bancada delequipo. Se recomienda que sea una losa de hormigón deuna sola pieza, con zapatas que se extiendan en el terrenopor debajo del límite de heladas. Para evitar la transmisiónde ruido y vibraciones, el equipo no debe anclarse a loscimientos del edificio.

En instalaciones sobre tejado, elegir un lugar cuya resistenciaestructural sea adecuada para soportar con seguridad elpeso total del equipo en funcionamiento y del personal demantenimiento. El equipo puede montarse sobre una losa dehormigón, similar a la que se necesita para instalaciones enplanta baja, o bien sobre perfiles de acero suficientementeresistentes. Los perfiles deben estar espaciados en losmismos centros que los perfiles laterales y delanteros de labase del equipo.

Esto permitirá el montaje de soportes antivibratorios, si fuesennecesarios. En instalaciones sobre tejado se recomiendael uso de soportes antivibratorios. Todos los conductos osilenciadores que se monten en el equipo deben tener unaresistencia de presión estática total -con el caudal de airedel equipo al máximo- que no supere la capacidad de losventiladores instalados en el equipo.

Instalación en Interiores

El equipo puede instalarse en una sala de máquinascerrada, siempre y cuando el suelo esté nivelado y tenga laresistencia adecuada para soportar el peso total del equipo en

funcionamiento. Es imprescindible que haya un espacio libreadecuado para la ventilación del equipo. El aire de descargade la parte superior del equipo debe canalizarse hacia elexterior para evitar que haya recirculación de aire dentro dela sala de máquinas. Si se utilizan conductos comunes paralos ventiladores, deben instalarse compuertas antirretorno ala salida de cada ventilador.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 16/72

 

16

Form No. 201.26 EG 04 (ES 02/10)

Los conductos de descarga deben estar debidamentedimensionados, de forma que la pérdida de presión estáticatotal (junto con cualquier otra pérdida de presión estática deentrada) sea inferior a la presión estática disponible para eltipo de ventilador que haya instalado.

El conducto de aire de descarga normalmente expulsa el aireal exterior del edificio a través de una rejilla. La salida debeposicionarse de forma que se evite que el aire vuelva a entrarde nuevo directamente a través de las tomas de aire de lasbaterías condensadoras, ya que dicha recirculación afectará

al rendimiento del equipo.

Funcionamiento en Condiciones de Baja TemperaturaAmbiente

Si se precisan capacidades frigoríficas bajas, en condicionesde baja temperatura ambiente (-4ºC e inferior), la presióndel refrigerante descenderá. Para evitar problemas defuncionamiento, debe utilizarse la alternativa de ventiladoresde dos velocidades.

En condiciones ambientales de -10ºC o inferior, debeutilizarse la alternativa de los Paneles de Rejilla de lasBaterías Condensadoras, si el cliente no ha facilitado una

protección adecuada contra el viento.Conexión de Conductos

El objetivo de las siguientes recomendaciones relativas aconductos es garantizar el funcionamiento satisfactorio delequipo. El incumplimiento de dichas recomendaciones podríacausar daños al equipo, o una pérdida de rendimiento, asícomo la invalidación de la garantía. Cuando los conductosdeban montarse en la descarga de los ventiladores, serecomienda que los conductos tengan la misma sección quela salida de los ventiladores y tengan un tramo recto mínimode 1 metro con el fin de conseguir recuperar presión estáticade los ventiladores.

Ductwork should be suspended with flexible hangers toprevent noise and vibration being transmitted to the structure.A flexible joint is also recommended between the ductattached to the fan and the next section for the same reason.Flexible connectors should not be allowed to concertina.

45

45

8 Agujeros, 9 mm paraTornillos M8 en

Ø 970 mm.

Brida superior Protección

150 mm

   9  0  0   m  m

   5  0   m  m

Los conductos deben ir suspendidos con tirantes flexiblespara evitar transmitir ruidos y vibraciones a la estructura. Por

la misma razón también se recomienda montar una juntaflexible entre el conducto que va unido al ventilador y el tramosiguiente. No debe permitirse que las conexiones flexibles seaplasten y formen pliegues (como un acordeón).

El equipo no está diseñado para soportar cargas estructurales.No debe permitirse que una cantidad significativa de pesodescanse sobre las brida de salida de los ventiladores, enlos conjuntos de bandejas-soporte, ni sobre los módulos delas baterías condensadoras. El equipo puede soportar comomáximo el peso de conductos ligeros de 1 metro de largo.

En lugares expuestos a vientos de costado, todos losconductos deben ir soportados para evitar cargas lateralessobre el equipo. Si los conductos de dos o más ventiladoresdeben convertirse en un conducto común, hay que montarcompuertas antirretorno en el conducto de cada ventilador.Ello evitará la recirculación de aire cuando sólo funcione unode los ventiladores.

Los equipos se suministran con protecciones en el ladode salida por motivos de seguridad y para evitar dañar losálabes de los ventiladores. Si dichas protecciones se retiranpara instalar conductos, deben adoptarse precaucionesalternativas adecuadas para evitar que los álabes giratorios

de los ventiladores puedan causar daños o poner en peligrola integridad física de las personas.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 17/72

 

17

Form No. 201.26 EG 04 (ES 02/10)

Espacio Libre Necesario

Es preciso que haya un espacio libre alrededor del equipopara que el aire que necesitan las baterías condensadorasrefrigeradas por aire pueda circular libremente y para evitarque el aire caliente de descarga vuelva a las baterías. Sino se respetan los espacios libres indicados, la restriccióno recirculación del volumen de aire provocará una pérdidade rendimiento del equipo, un aumento del consumoenergético y puede incluso causar anomalías. También debecontemplarse la posibilidad de que se produzcan corrientes

de aire descendentes provocadas por edificios colindantes,lo cual puede dar lugar a una recirculación o a un caudal deaire irregular en el equipo.

En lugares expuestos a fuertes vientos laterales, como porejemplo en tejados de edificios, se recomienda el uso de unacubierta sólida o tipo rejilla para evitar que las turbulenciasde viento afecten al caudal de aire del equipo.

ESPACIO LIBRE NECESARIO

PAREDES MACIZAS

SE 0600-0920 1000-1500

HE 0590-0800 0830-1380

Dimensión A mm 1500 1700Dimensión B mm 2700 3000

REJILLAS EN PAREDES B & D

Dimensión A mm 800 800Dimensión B mm 2700 3000

Notas

Las paredes no deben superar la altura de la planta en más de un lado.Las rejillas deben ser como mínimo el 50% de la zona libre.Las dimensiones A puede que tengan que aumentarse para permitir instalar las tuberías y el acceso para mantenimiento a su alrededor.

Modelos

1200

1000

A BPARED A

PARED B

PARED C

PARED D

A

1200

1000

PARED A

A AB

PARED B

PARED C

PARED D

1200

Cuando los equipos se instalan en un espacio cerrado,la altura de las paredes no debe superar la del equipo enmás de un lado. Si las paredes son de rejilla, hay que teneren cuenta las mismas necesidades de pérdida de presiónestática que para los conductos y silenciadores mencionadosanteriormente. En zonas en las que pueda acumularse nieve,debe elevarse el equipo para garantizar que éste dispongade un caudal de aire suficiente.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 18/72

 

18

Form No. 201.26 EG 04 (ES 02/10)

Soportes Antivibratorios

Con cada equipo pueden suministrase (sueltos) juegosopcionales de soportes antivibratorios.

Tuberías de Líquido Frío

Las siguientes recomendaciones tienen por objeto garantizarel funcionamiento satisfactorio de/de los equipo(s). Elincumplimiento de dichas recomendaciones podría causardaños al equipo, o una pérdida de rendimiento, así como la

invalidación de la garantía.Debe instalarse un interruptor de flujo en las tuberías delcliente, a la salida del evaporador, conectándolo al panel decontrol mediante cable blindado, con el fin de evitar dañar elevaporador porque el equipo funcione sin un caudal adecuadode líquido. Debe haber un tramo recto de tubería de al menos5 diámetros de tubo a ambos lados del interruptor de flujo. Eldetector de caudal que se utilice debe tener los contactos deoro para funcionar a baja tensión/intensidad.

Como alternativa puede utilizarse un presostato diferencialen un orificio calibrado, preferiblemente del tipo límite alto/ bajo.

La(s) bomba(s) de líquido frío instalada(s) en la red detuberías debe descargar directamente en la sección delevaporador del sistema del equipo. La(s) bomba(s) puede(n)estar controlada(s) por los mandos de la planta enfriadora odesde una posición externa al equipo. Tanto las tuberías comola valvulería deben estar soportadas de forma independientepara evitar transmitir cargas al evaporador.

En este sentido, se recomienda el uso de conexionesflexibles con el fin de reducir al mínimo la transmisión devibraciones al edificio. Si el equipo va montado sobre soportesantivibratorios, deben usarse dichas conexiones flexibles,ya que es previsible que el equipo se mueva durante elfuncionamiento normal del mismo.

Las tuberías y la valvulería próximas al evaporador debenser fácilmente desmontables para facilitar las operacionesde limpieza antes de poner el equipo en funcionamiento, asícomo para facilitar la inspección visual de las conexiones delintercambiador.

El evaporador debe estar protegido por un filtro,preferiblemente de malla 40, montado tan cerca como seaposible de la conexión de entrada de líquido e ir provisto deválvulas de cierre. El evaporador no debe estar expuesto avelocidades excesivas de limpieza o a residuos liberadosdurante la misma.

Se recomienda instalar un by-pass y válvulas del tamañoadecuado para permitir la limpieza de las tuberías. El by-passpuede utilizarse durante las operaciones de mantenimientopara aislar el intercambiador de calor, sin que ello afecte lacirculación de líquido a otros equipos.

En la entrada y salida de cada evaporador deben instalarseconexiones para los termómetros y los manómetros. Elequipo se suministra sin termómetros ni manómetros.

Deben preverse conexiones de desagüe y purga en todoslos puntos altos y bajos de las tuberías, para permitir vaciarla instalación y para purgar el aire que pudiera haber en lastuberías.

Las tuberías de líquido de los circuitos que estén expuestas aheladas, debido a las bajas temperaturas ambientes, debenprotegerse utilizando material aislante, una resistenciaeléctrica plana o bien una solución de glicol adecuada.También puede(n) utilizarse la(s) bomba(s) de líquido para

asegurarse de que el líquido circula cuando la temperaturaambiente se acerca al punto de congelación.

También debe ponerse material aislante alrededor de lasconexiones del evaporador. Se recomienda colocar unaresistencia eléctrica plana se 21 W por metro debajo delaislamiento. Dicha resistencia debe ser alimentada de formaindependiente y estar controlada por un termostato deambiente, regulado para activarse a unos 2,2ºC por encimade la temperatura de congelación del líquido frío.

El evaporador está protegido por mantas calefactorascolocadas debajo del aislamiento y que están alimentadasa través del mismo circuito que alimenta el panel de controldel equipo. Durante la época de frío, cuando existe el riesgode heladas, la alimentación eléctrica de la planta enfriadoradebe dejarse conectada para asegurar el funcionamiento delsistema de protección contra heladas, salvo que se hayanvaciado los circuitos hidráulicos

Disposición de las Tuberías

El esquema que hay a continuación muestra la disposiciónsugerida de las tuberías para instalaciones de un solo equipo.Para instalaciones con varios equipos, la disposición de las

tuberías de cada uno de ellos debe ser tal como indica elesquema siguiente.

-Llave de Cierre - Normalmente Abierta

-Llave de Cierre - Normalmente Cerrada

-Válvula Reguladora de Caudal

-Caudalímetro

-Filtro

-Toma de Presión

-Interruptor de Flujo

-Conexión con brida

-Tuberías

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 19/72

 

19

Form No. 201.26 EG 04 (ES 02/10)

Conexiones del Evaporador

Las conexiones estándar de líquido frío de todos losevaporadores son del tipo Ranuras Victaulic.

Bridas Opcionales

Pueden montarse dos tipos de bridas, dependiendo de lasnecesidades del cliente o de los requisitos de la Normativasobre Recipientes a Presión: Bridas tipo AcoplamientoVictaulic, normalmente suministradas sueltas, o Bridas paraSoldar, que pueden suministrarse sueltas o ya montadas. Lasdimensiones, tanto de las bridas tipo Acoplamiento Victauliccomo las de Soldar, se ajustan a la norma ISO 7005 - NP10.

Acoplamiento

Tratamiento del Agua

Las prestaciones del equipo que se facilitan en ladocumentación técnica (Guía de Diseño) están basadas

en un coeficiente de ensuciamiento de 0,018 m²/h ºC/kW.La suciedad, las incrustaciones, la grasa y ciertos tiposde tratamiento de agua, afectará de forma adversa lassuperficies del intercambiador y por tanto el rendimientodel equipo. Las materias extrañas que pueda haber en el/ los circuito(s) hidráulico(s) pueden provocar un aumentode la pérdida de carga en el intercambiador, reduciendo elcaudal y provocando posibles daños a los tubos del propiointercambiador.

No se recomienda utilizar agua aireada, salobre o salada enlos circuitos hidráulicos. York recomienda consultar con unespecialista en tratamiento de aguas para determinar si lacomposición del agua que se pretende utilizar afectará a los

materiales de acero al carbono y de cobre del evaporador.El pH del agua que fluye a través del evaporador debemantenerse entre unos valores de 7 y 8,5.

Tuberías de las Válvulas de Seguridad de Refrigerante

El evaporador está protegido contra los aumentos excesivosde la presión interna del refrigerante mediante válvulas deseguridad. Se monta una válvula de seguridad en cada unade las mangueras principales de interconexión que conectanel evaporador con los compresores.

Se coloca un trozo de tubo de descarga en cada válvula,orientado de forma que cuando ésta se active, el gas y ellíquido a alta presión que se libere no constituya un peligro

ni cause daños personales. En instalaciones de interior, ladescarga de las válvulas de seguridad debe llevarse hasta elexterior del edificio.

Los tubos que vayan conectados a las válvulas de seguridaddeben tener un diámetro suficiente como para no causarresistencia al funcionamiento de las válvulas. A menos que lanormativa local especifique lo contrario, el diámetro interiordepende de la longitud del tubo que se necesita y que vienedado por la siguiente fórmula:

D5 = 1.447 x L

En que:

D = diámetro mínimo interior del tubo en centímetrosL = longitud del tubo en metros

Si los tubos de descarga de presión son comunes a másde una válvula, su sección debe ser como mínimo el totalque necesita cada válvula. No deben mezclarse tipos deválvulas que vayan en un mismo tubo común. Se debentomar precauciones para asegurarse de que las salidas delas válvulas de seguridad/tubos de descarga (de presión) noestén nunca obstruidas.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 20/72

 

20

Form No. 201.26 EG 04 (ES 02/10)

captar ruidos eléctricos. Usar el pasacables del panel decontrol para evitar los cables de potencia.

Los contactos libres de tensión conectados en el paneldeben ser adecuados para 115 V.c.a., 10 mA (se recomiendacontactos de oro). Si los contactos libres de tensión formanparte de un relé o contactor, debe suprimirse la bobina deeste dispositivo mediante un supresor estándar R/C. Debenadoptarse estas precauciones para evitar ruidos eléctricoque podrían provocar alguna anomalía o daños al equipo y asus dispositivos de control.

CONEXIONES ELÉCTRICAS

No se deben montar controles adicionales (relés, etc.) en elpanel de control. Los cables de potencia y control que novayan conectados al panel de control, no deben pasar através del mismo. Si no se respetan estas precauciones, secorre el riesgo de electrocución. Además, el ruido eléctricopodría provocar alguna anomalía o daños al equipo y a susdispositivos de control.

Una vez realizadas las conexiones eléctricas, no conectar

la alimentación eléctrica principal del equipo. Algunoscomponentes internos tienen corriente cuando se conecta laalimentación eléctrica y esto sólo debe realizarlo personal“autorizado” que esté familiarizado con el arranque,funcionamiento y solución de problemas de este tipo deequipos.

Cableado de Potencia

Todo el cableado eléctrico debe ser realizado de acuerdocon la normativa local. Pasar los cables debidamentedimensionados hasta los pasacables que hay situados enel equipo. Según las normas CE o U.L., es responsabilidaddel usuario instalar dispositivos protectores contra

sobreintensidades entre los conductores de alimentación ylos terminales de entrada que lleva el equipo.

Para evitar que se formen corrientes parásitas en el panelde potencia, los cables que forman la alimentación trifásicadeben entrar a través del mismo pasacables. Todas lasfuentes de suministro del equipo deben tomarse de un puntocomún de desconexión (no suministrado por York).

Los equipos sólo precisan una alimentación eléctrica trifásicay conexión a tierra. Conectar las alimentaciones trifásicas ala regleta de conexiones o al magnetotérmico opcional quehay en el panel, usando los bornes que se detallan en elApartado de Características Técnicas.

Conectar un hilo de tierra desde el borne de tierra del panelde la planta enfriadora a tierra de la línea de alimentacióneléctrica

Transformador de Alimentación del Circuito de Controlde 115 V.c.a.

Con la planta enfriadora se suministra de serie untransformador de 3 hilos de alto voltaje a 115 V.c.a. Dichotransformador va montado en un armario y reduce laalimentación de alto voltaje a 115 V.c.a. que utilizan losControles, el Variador de Velocidad (VSD), el Controlador dela Válvula de Alimentación & Desagüe, válvulas, solenoides,resistencias calefactoras, etc.

El alto voltaje para el primario del transformador se toma dela entrada a la planta enfriadora. El transformador va provistode fusible(s).

Eliminando el alto voltaje a la planta enfriadora tambiéneliminará la tensión de alimentación de 115 V.c.a. a loscircuitos del panel de control y a la resistencia calefactora delevaporador. En la temporada de invierno, esto podría causargraves daños a la planta enfriadora por congelación delevaporador. No cortar el suministro eléctrico a menos que sehaya previsto algún otro medio alternativo que garantice elfuncionamiento de la resistencia calefactora del evaporador.

Cableado del Panel de Control

Todos los conductores que utilizan cierres de contactosque van a la regleta de conexiones del panel de control sonde 115 V.c.a. nominal y deben ir en cable blindado, con lapantalla conectada a tierra sólo en el lado del panel. Ponerel cable blindado separado del cable de potencia para evitar

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 21/72

 

21

Form No. 201.26 EG 04 (ES 02/10)

CONTACTOS LIBRES DE TENSIÓN

Arrancador Bomba de Líquido Frío

Los contactos 23 y 24 de 1TB cierran para arrancar la bombade líquido frío de la planta. Dicho contacto puede utilizarsecomo marcha/paro principal de la bomba, junto con laprogramación diaria de arranque/paro.

Contacto de Funcionamiento

Los contactos 21 y 22 de 1TB cierran para indicar que uncircuito está funcionando.

Contactos de Alarmas

Cada uno de los circuitos 1/3 & 2/4 llevan un solo contactolibre de tensión que funciona para alertar de una anomalíacuando se bloquea un circuito o se produce un fallo detensión. Para obtener una señal de alarma del sistema,conectar el circuito de alarma a los bornes libres de tensión25 & 26 (Circuito 1/3), bornes 27 & 28 (Circuito 2/4) de laregleta de conexiones 1TB.

ENTRADAS DEL SISTEMA

Interruptor de FlujoUn interruptor de flujo de líquido frío del tipo apropiadoDEBE conectarse entre los bornes 2 y 13 de 1TB con el finde proporcionar la protección adecuada contra pérdidas decaudal, que hará que el evaporador se congele si se permiteque la planta enfriadora funcione.

El circuito del interruptor de flujo funciona a 115 V.c.a. Loscontactos deben estar dimensionados para bajo amperaje(10 mA). Deben usarse contactos de oro.

Marcha/Paro Remoto

Hay una entrada de Marcha/Paro Remoto para cada par de

circuitos (1/3 & 2/4). Estas entradas precisan de un contactoseco para arrancar y parar el sistema. Los contactos secosremotos del circuito 1/3 van conectados a los bornes 2 y15 de la regleta de conexiones 1TB y los contactos secosremotos del circuito 2/4 van conectados a los bornes 2 y 16de la regleta 1TB. Si la entrada de Marcha/Paro Remoto nose utiliza, debe colocarse un puente entre los bornes parapermitir que el circuito funcione.

El circuito de Marcha/Paro Remoto funciona a 115 V.c.a. Loscontactos deben estar dimensionados para bajo amperaje(10 mA). Deben usarse contactos de oro.

Impresión a Distancia

El cierre de los contactos adecuados que hay conectadosa los bornes 2 y 14 de 1TB generará una copia impresade Historial de Datos de Funcionamiento/Anomalías si seconecta una impresora opcional al puerto RS-232.

El circuito de Impresión a Distancia funciona a 115 V.c.a. Loscontactos deben estar dimensionados para bajo amperaje(10 mA). Deben usarse contactos de oro.

Reajuste Remoto Opcional del Punto de Consigna de laTemperatura

Una señal de corriente o voltaje, conectada a los bornes 17y 18, proporcionará una función de reajuste remoto del puntode consigna del líquido frío, si es necesario.

Reajuste Remoto Opcional de la Limitación de laCorriente

Una señal de corriente o voltaje, conectada a los bornes 19 y

20, proporcionará un ajuste remoto del punto de consigna dela limitación de corriente, si es necesario.

Reajuste Remoto Opcional de la Limitación del NivelSonoro

Una señal de corriente o voltaje, conectada a los bornes 40 y41, proporcionará un ajuste remoto del punto de consigna dela limitación del nivel sonoro, si es necesario.

1 3

Variador de Velocidad

Controles del Variador de Velocidad

Transformador

de ControlEstándar

Controles del Equipo

Resistencia Calefactora

del Evaporador

Contactores de

los VentiladoresBobina de

Reactancia

Magnetotérmico

Tierra deProtección

Alimentación Eléctrica

Suministrada en Obra

2

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 22/72

 

22

Form No. 201.26 EG 04 (ES 02/10)

DATOS DE SELECCIÓN DE UNA PLANTA

Guía de Selección de Plantas de Agua Fría

INFORMACIÓN NECESARIA

Para seleccionar una planta enfriadora YCIV de York, seprecisa la información siguiente:

Capacidad frigorífica necesaria.

Temperaturas de diseño de entrada y salida del aguafría.

Caudal de diseño del agua, si se desconoce una de lastemperaturas del punto 3.

Temperatura de diseño de entrada del aire en elcondensador. Ésta será normalmente la temperaturaambiente de diseño del aire en verano, salvo que influyanel emplazamiento u otros factores.

Altitud sobre el nivel del mar.

Coeficiente de ensuciamiento de diseño delevaporador.

Resistencia de la presión estática contra el caudal de airede entrada y salida en el/del condensador (en los casosen que se utilicen conductos, rejillas, silenciadores, etc.)con el caudal de aire del equipo al máximo.

Nota: Los puntos 1, 2 y 3 deben relacionarse mediante lafórmula siguiente:

Capacidad frigorífica (kW) = Gama (ºC) x Caudal (litros/seg)x 4,18

En que:Gama = Temp. de entrada del líquido - Temp. de salida dellíquido

MÉTODO DE SELECCION DE UNA PLANTA

Determinar el modelo correcto de planta enfriadoraseleccionando el que más se aproxime a la capacidadrequerida en las condiciones de diseño de temperaturade salida del agua y temperatura de entrada del aire(Tablas de Capacidades Frigoríficas).

1.

2.

3.

4.

5.

6.

7.

1.

Aplicar los factores de corrección correspondientes alcoeficiente de ensuciamiento y altitud a la capacidady valores de potencia de las tablas de capacidades.Asegurarse de que la capacidad corregida sigue siendosuficiente para las necesidades en cuestión.

Utilizando la capacidad corregida de la plantaseleccionada, ajustar la gama de temperaturas dediseño, o caudal, para equilibrar la fórmula indicada enel apartado “Información Necesaria”.

A continuación pueden determinarse los Datos Físicosy las Características Eléctricas mediante las tablascorrespondientes

Siempre volver a verificar que las selecciones estén dentrode los límites de diseño especificados en los Límites deUtilización.

SELECCIÓN MUESTRA DE UNA PLANTA YCIV -ENFRIAMIENTO DE AGUA

Se precisa una planta estándar para enfriar agua de 12ºCa 7ºC, con una capacidad frigorífica de 865 kW y un caudalde diseño de 41 l/s. He aquí también otras condiciones dediseño que le atañen:

Aire ambiente de entrada en el condensador: 35ºC

Coeficiente de ensuciamiento: 0,044 m2 ºC/kW

Altitud: A nivel del mar

Mediante un examen rápido de la Tabla de Capacidades SE,observamos que un modelo YCIV0920 da, aproximadamente,la capacidad requerida:

Capacidad = 870,4 kW

Potencia del compresor = 271,3 kW

Así pues, no hay factores de corrección que sean de aplicación;después de calcular el caudal, las condiciones serán lassiguientes:

Capacidad frigorífica: 870,4 kW

Temperatura del agua: De 12ºC a 7ºC (Gama = 5ºC)

Caudal de agua: 41,6 l/s

2.

3.

4.

ContactosAlarma Cir 2

FuncionamientoPlanta

Enfriadora

Señal deArranque

BombaEvaporador

Marcha/Paro Cir 1

Marcha/Paro Cir 2

Interruptor de Flujo

Imprimir

LEYENDA

REGLETA PARA CONEXIONES DELCLIENTE (1TB)

REGLETA PARA CONEXIONESDE YORK (1TB)

CABLEADO Y CONEXIONES POR PARTE DE YO

EQUIPOS OPCIONALES

CABLEADO O CONEXIONES DE OTROS

PLACA DERELÉS Nº 2

PLACA DERELÉS Nº 1

PLACA DECONTROL

+Entrada de Señal

+Entrada de Señal

+Entrada de Señal

-Entrada de Señal (Tierra)

-Entrada de Señal (Tierra)

-Entrada de Señal (Tierra)

ReajusteRemotode la Temp.

LimitaciónRemota dela Corriente

LimitaciónRemota delSonido

ContactosAlarma Cir 1

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 23/72

 

23

Form No. 201.26 EG 04 (ES 02/10)

Potencia del compresor = 271,3 kW

Todos los valores se hallan dentro de las Limitaciones deFuncionamiento. En el Gráfico de Pérdida de Carga vemosque la pérdida de carga del agua del evaporador de una plantaYCIV0920 = 65 kPa, con un caudal calculado de 41,6 l/s.

Coeficientes de Ensuciamiento y Altitud

EVAPORADOR

Coef. Ensucia. m² °C/kW Factor de Capacidad Factor Pot. Absor. Comp.

0.044 1.000 1.000

0.088 0.987 0.9950.176 0.964 0.9850.352 0.915 0.962

Altitud (m) Factor de Capacidad Factor Pot. Absor. Comp.

0 1.000 1.000600 0.987 1.010

1200 0.973 1.0201800 0.958 1.0292400 0.943 1.038

Factores de Corrección de la Gama de Temperaturas delAgua

Gama de Factores de Corrección

Temperaturas ºC Capacidad Frigorífica Pot. Absorb. Comp. kW

3 0.98 0.994 0.99 1.005 1.00 1.006 1.01 1.007 1.02 1.008 1.02 1.019 1.03 1.01

10 1.04 1.01

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 24/72

 

24

Form No. 201.26 EG 04 (ES 02/10)

GRÁFICO DE PÉRDIDA DE CARGA

5 10 20 30 40 50 60 70 80

5

10

20

30

40

50

60

70

80

90

100

120

140

160

15

   P   é  r   d   i   d  a   d  e   C  a  r  g  a   (   k   P  a   )

Caudal de Agua (l/s)

Temperatura del agua (media): 9.4 °C

C

D E

F

BA

Linea Cálculo de Pérdida de Carga

A Pérdida de Carga [kPa] = 0.1724 x (Caudal [ l/s]^1.7925)

B Pérdida de Carga [kPa] = 0.1898 x (Ca udal [ l /s]^1.7475)

C Pérdida de Carga [kPa] = 0.1781 x (Caudal [l /s]^1.7468)

D Pérdida de Carga [kPa] = 0.1100 x (Caudal [l /s]^1.7183)E Pérdida de Carga [kPa] = 0.0602 x (Caudal [l /s]^1.6792)F Pérdida de Carga [kPa] = 0.0923 x (Caudal [ l /s]^1.6265)

Línea Modelo

A YCIV0600SEB YCIV0590HE, YCIV0630HE, YCIV0650SE. YCIV0700HE, YCIV0720SEC YCIV0760HE, YCIV0800HE, YCIV0830HE,D YCIV0770SE, YCIV0840SE, YCIV0920SE, YCIV0930HE, YCIV1000SEE YCIV1050HE, YCIV1070SE, YCIV1120HEF YCIV1180SE, YCIV1220HE, YCIV1340SE, YCIV1380HE,YCIV1500SE

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 25/72

 

25

Form No. 201.26 EG 04 (ES 02/10)

LÍMITES DE UTILIZACIÓN

YCIV0600 YCIV0650 YCIV0720 YCIV0770 YCIV0840 YCIV0920

Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.

Salida Agua oC De 4,4 a 15,6

Salida Glicol oC De -9 a 15.6

Gama de Temp. oC De 3 a 10

Caudal Evaporador l/s 8,8 42,6 10,1 47,3 10,1 47,3 11,4 47,3 11,4 47,3 11,4 50,5Pérdida de Carga Evaporador kPa 8,5 143,6 10,8 160,4 10,8 160,4 12,5 150,1 12,5 150,1 7,2 92,9Presión Máxima en el Lado Agua bar 10

Temp. de Entrada del Aire oC De -18 a 52Ventil. Estándar Pa 10Ventil. 2 Velocid. Pa 10Vent. Alta Pres Est Pa 100

Presión Máxima en el Lado Refrigerante bar 16Alimentación Eléctrica 400V, 3 ~, 50 Hz (nominal) V De 360 a 440Volumen Mín. de Agua Recomendado en el Sistema l 560

YCIV1000 YCIV1070 YCIV1180 YCIV1340 YCIV1500

Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.

Salida Agua oC De 4.4 a 15.6

Salida Glicol oC De -9 a 15.6

Gama de Temp. oC De 3 a 10

Caudal Evaporador l/s 11.4 50.5 15.8 75.7 18.9 75.7 18.9 75.7 18.9 78.9Pérdida de Carga Evaporador kPa 7.2 92.9 6.2 86.1 11.0 105.1 11.0 105.1 11.0 105.1Presión Máxima en el Lado Agua bar 10Temp. de Entrada del Aire o

C De -18 a 52Ventil. Estándar Pa 10Ventil. 2 Velocid. Pa 10Vent. Alta Pres Est Pa 100

Presión Máxima en el Lado Refrigerante bar 16Alimentación Eléctrica 400V, 3 ~, 50 Hz (nominal) V De 360 a 440Volumen Mín. de Agua Recomendado en el Sistema l

YCIV0590 YCIV0630 YCIV0700 YCIV0760 YCIV0800 YCIV0830

Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.

Salida Agua oC De 4.4 a 15.6Salida Glicol o

C De -9 a 15.6

Gama de Temp. oC De 3 a 10

Caudal Evaporador l/s 10.1 47.3 10.1 47.3 10.1 47.3 11.4 47.3 11.4 47.3 11.4 47.3Pérdida de Carga Evaporador kPa 10.8 160.4 10.8 160.4 10.8 160.4 12.5 150.1 12.5 150.1 12.5 150.1Presión Máxima en el Lado Agua bar 10Temp. de Entrada del Aire o

C De -18 a 52Ventil. Estándar Pa 10Ventil. 2 Velocid. Pa 10Vent. Alta Pres Est Pa 100

Presión Máxima en el Lado Refrigerante bar 16Alimentación Eléctrica 400V, 3 ~, 50 Hz (nominal) V De 360 a 440Volumen Mín. de Agua Recomendado en el Sistema l

YCIV0930 YCIV1050 YCIV1120 YCIV1220 YCIV1380

Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.

Salida Agua oC De 4.4 a 15.6

Salida Glicol oC De -9 a 15.6

Gama de Temp. oC De 3 a 10

Caudal Evaporador l/s 11.4 50.5 15.8 75.7 18.9 75.7 18.9 75.7 18.9 75.7Pérdida de Carga Evaporador kPa 7.2 92.9 6.2 86.1 11.0 105.1 11.0 105.1 11.0 105.1Presión Máxima en el Lado Agua bar 10Temp. de Entrada del Aire o

C De -18 a 52Ventil. Estándar Pa 10Ventil. 2 Velocid. Pa 10Vent. Alta Pres Est Pa 100

Presión Máxima en el Lado Refrigerante bar 16Alimentación Eléctrica 400V, 3 ~, 50 Hz (nominal) V De 360 a 440Volumen Mín. de Agua Recomendado en el Sistema l

(1) Los equipos que funcionen a temperaturas ambientes inferiores a -4°C deben llevar ventiladores de Dos Velocidades.

700

730

800 880

870

880 980 1050 1140 1300

550 600

Aire

Ambiente

760

950 1000 1100 1250 1400

620 680

Temp. Salida

del Líquido

800

Modelos de Rendimiento Estándar (SE)

Líquido Frío

Temp. Salida

del Líquido

Aire

Ambiente

Presión Est.

Disp. en los

Ventiladores

Temp. Salida

del Líquido

Modelos de Alto Rendimiento (HE)

Líquido Frío

Aire

Ambiente

Presión Est.

Disp. en los

Ventiladores

Temp. Salida

del Líquido

Modelos de Rendimiento Estándar (SE)

Líquido Frío

Presión Est.

Disp. en los

Ventiladores

Aire

Ambiente

Presión Est.

Disp. en los

Ventiladores

Modelos de Alto Rendimiento (HE)

Líquido Frío

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 26/72

 

26

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE RENDIMIENTO ESTÁNDAR (SE) CON VENTILADORES ESTÁNDAR - CAPACIDADESFRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 534.1 139.5 3.49 522.1 156.2 3.08 507.9 172.5 2.73 491.2 189.2 2.42 472.9 206.3 2.155 542.3 139.9 3.54 529.8 156.5 3.12 515.4 172.9 2.77 498.3 189.8 2.45 479.8 207.0 2.18  

6 559.0 140.8 3.62 545.6 157.0 3.20 530.4 173.7 2.83 512.9 191.1 2.51 493.7 208.5 2.227 575.9 141.7 3.71 561.6 157.7 3.28 545.8 174.7 2.90 527.5 192.3 2.56 508.0 210.0 2.27  

8 592.8 142.4 3.80 577.9 158.5 3.36 561.4 175.7 2.97 542.4 193.5 2.62 522.8 212.3 2.3210 627.2 144.0 3.98 611.2 160.3 3.52 593.3 177.9 3.10 573.0 196.2 2.73 553.1 216.6 2.40  

12 662.9 145.9 4.16 645.6 162.5 3.67 626.3 180.4 3.23 604.9 199.0 2.85 584.7 220.9 2.4915 718.7 149.1 4.42 699.7 165.9 3.90 678.7 184.0 3.44 655.7 203.0 3.03 605.7 206.4 2.75  

15.5 728.3 149.8 4.46 709.0 166.5 3.94 687.6 184.7 3.47 664.4 203.8 3.06 608.6 203.8 2.80  

4.5 576.5 148.1 3.57 565.9 167.4 3.13 553.1 190.2 2.72 527.3 208.4 2.38 492.7 218.4 2.135  584.6 149.4 3.59 573.9 167.8 3.17 560.9 190.7 2.75 534.1 208.8 2.40 495.5 216.5 2.15  

6 600.8 151.8 3.64 590.0 169.5 3.22 576.6 191.8 2.81 548.1 209.5 2.46 500.9 212.5 2.227 617.3 154.1 3.68 606.3 172.5 3.26 592.6 192.9 2.87 561.9 209.9 2.52 506.9 208.6 2.28  

8 634.1 156.5 3.73 622.8 175.2 3.30 608.6 194.3 2.93 575.6 210.3 2.57 513.3 204.9 2.3510 668.3 161.3 3.82 656.8 180.2 3.39 639.3 199.1 3.01 603.6 211.3 2.69 524.4 196.6 2.50  

12 703.2 166.0 3.92 691.4 185.3 3.48 670.7 202.9 3.10 631.5 215.8 2.75 533.6 188.5 2.6415 757.1 171.1 4.10 745.0 193.1 3.61 719.2 208.4 3.24 674.9 220.8 2.88 542.7 179.2 2.82  

15.5 766.3 172.0 4.13 754.1 194.1 3.63 727.4 209.4 3.26 682.1 221.7 2.90 543.8 177.4 2.85

4.5 627.4 159.0 3.60 617.2 179.9 3.16 605.6 204.5 2.76 585.2 229.7 2.39 562.4 251.5 2.115 636.1 160.5 3.62 625.8 180.4 3.20 613.8 205.0 2.79 592.3 229.9 2.42 568.9 251.9 2.13  

6 653.8 163.3 3.66 643.1 182.1 3.26 630.7 206.0 2.85 606.4 230.4 2.47 582.2 252.4 2.187 671.7 165.9 3.71 660.6 184.8 3.30 647.8 207.1 2.91 621.0 230.7 2.53 595.8 253.0 2.22  

8 689.9 168.6 3.76 678.4 187.8 3.34 665.1 208.8 2.97 635.7 231.1 2.58 609.7 253.4 2.2710 727.2 174.1 3.84 714.9 193.4 3.43 700.5 214.8 3.05 665.8 232.1 2.69 638.1 254.3 2.37  

12 765.8 179.6 3.93 752.6 199.1 3.51 737.2 220.8 3.13 695.7 236.4 2.77 658.0 248.3 2.5015 826.2 186.1 4.11 811.6 207.9 3.64 793.8 229.4 3.25 742.4 242.2 2.88 673.0 234.0 2.70  

15.5 836.6 187.2 4.14 821.7 209.3 3.66 802.9 230.6 3.27 750.4 243.1 2.91 675.7 231.8 2.74  

4.5 677.6 173.3 3.60 665.3 196.4 3.15 651.3 225.5 2.71 620.4 248.2 2.36 566.1 246.8 2.165 687.0 174.7 3.62 674.5 196.7 3.18 660.2 225.9 2.74 627.8 248.2 2.38 568.8 244.3 2.19  

6 706.3 177.4 3.67 693.1 199.4 3.23 678.0 226.6 2.81 642.7 248.1 2.44 574.2 239.0 2.267 725.9 180.1 3.72 712.1 202.6 3.27 695.4 226.7 2.88 658.0 247.8 2.50 580.8 234.2 2.33  

8 745.9 183.1 3.76 731.5 205.3 3.32 712.8 228.2 2.93 673.5 247.5 2.56 586.8 229.1 2.4010 787.1 189.5 3.85 771.5 211.0 3.41 748.4 233.1 3.02 705.2 247.7 2.68 598.5 219.2 2.55  

12 830.0 195.5 3.94 813.0 217.3 3.50 785.3 237.1 3.11 737.1 251.4 2.77 608.1 210.2 2.7015 897.0 204.5 4.08 878.1 227.1 3.62 843.1 243.8 3.26 787.0 255.0 2.91 618.5 199.8 2.88  

15.5 908.5 206.2 4.10 889.3 228.4 3.65 852.9 245.0 3.28 795.5 255.6 2.94 620.4 198.0 2.91

4.5 735.3 184.9 3.65 722.5 207.7 3.22 707.9 236.2 2.80 680.5 262.8 2.43 653.8 281.9 2.195 745.6 186.6 3.67 732.5 208.3 3.25 717.6 236.8 2.83 688.5 263.0 2.46 661.5 282.1 2.21

6 766.5 189.7 3.71 753.0 211.0 3.31 737.3 238.0 2.89 705.0 263.1 2.52 676.9 282.5 2.267 787.8 192.8 3.76 773.7 214.8 3.34 757.5 239.3 2.96 721.9 263.2 2.58 692.7 282.7 2.31

8 809.6 196.1 3.80 794.8 218.2 3.38 778.0 241.8 3.01 739.0 263.3 2.64 708.8 282.9 2.3610 854.3 202.8 3.89 838.4 224.8 3.47 820.1 249.7 3.08 773.8 264.0 2.76 741.7 283.2 2.47  

12 900.6 209.2 3.99 883.6 231.7 3.56 863.8 256.8 3.16 809.0 268.9 2.83 757.2 271.7 2.6215 972.8 217.0 4.16 953.8 242.3 3.68 926.6 264.8 3.29 863.9 274.2 2.97 773.4 255.8 2.84  

15.5 985.2 218.5 4.19 965.9 243.5 3.71 936.6 265.8 3.31 873.3 275.1 2.99 776.2 253.1 2.88  

4.5 806.5 202.9 3.64 793.1 228.1 3.22 777.5 258.7 2.80 750.9 289.2 2.44 731.6 316.6 2.185 817.7 204.9 3.66 804.0 228.8 3.25 788.1 259.5 2.84 760.1 289.6 2.47 740.4 317.1 2.21

6 840.4 208.5 3.70 826.2 231.2 3.31 809.7 261.0 2.90 778.7 290.2 2.52 758.1 317.9 2.257 863.6 212.0 3.75 848.8 235.5 3.34 831.6 262.6 2.96 797.8 290.8 2.58 776.2 318.7 2.30  

8 887.1 215.7 3.79 871.7 239.6 3.38 853.9 264.9 3.01 817.2 291.4 2.64 794.6 319.4 2.3510 935.6 223.1 3.87 919.0 247.0 3.46 899.7 273.8 3.08 856.6 293.0 2.75 811.9 307.1 2.49  

12 985.6 230.5 3.96 967.9 254.7 3.54 947.1 281.7 3.15 896.7 299.2 2.82 826.2 292.3 2.6615 1063.4 238.1 4.15 1043.9 266.0 3.67 1017.5 291.1 3.29 959.0 307.1 2.95 839.4 275.0 2.86  

15.5 1076.7 239.6 4.17 1056.9 267.5 3.70 1028.6 292.4 3.31 970.2 308.1 2.97 841.6 272.4 2.89

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

0650

YCIV

0720

YCIV

0770

YCIV

0840

YCIV

0920

Modelo

YCIV

0600

   L   W   T   °   C

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 534.1 139.5 3.49 522.1 156.2 3.08 507.9 172.5 2.73 491.2 189.2 2.42 472.9 206.3 2.155 542.3 139.9 3.54 529.8 156.5 3.12 515.4 172.9 2.77 498.3 189.8 2.45 479.8 207.0 2.18  

6 559.0 140.8 3.62 545.6 157.0 3.20 530.4 173.7 2.83 512.9 191.1 2.51 493.7 208.5 2.227 575.9 141.7 3.71 561.6 157.7 3.28 545.8 174.7 2.90 527.5 192.3 2.56 508.0 210.0 2.27  

8 592.8 142.4 3.80 577.9 158.5 3.36 561.4 175.7 2.97 542.4 193.5 2.62 522.8 212.3 2.3210 627.2 144.0 3.98 611.2 160.3 3.52 593.3 177.9 3.10 573.0 196.2 2.73 553.1 216.6 2.40  

12 662.9 145.9 4.16 645.6 162.5 3.67 626.3 180.4 3.23 604.9 199.0 2.85 584.7 220.9 2.4915 718.7 149.1 4.42 699.7 165.9 3.90 678.7 184.0 3.44 655.7 203.0 3.03 605.7 206.4 2.75  

15.5 728.3 149.8 4.46 709.0 166.5 3.94 687.6 184.7 3.47 664.4 203.8 3.06 608.6 203.8 2.80  

4.5 576.5 148.1 3.57 565.9 167.4 3.13 553.1 190.2 2.72 527.3 208.4 2.38 492.7 218.4 2.135  584.6 149.4 3.59 573.9 167.8 3.17 560.9 190.7 2.75 534.1 208.8 2.40 495.5 216.5 2.15  

6 600.8 151.8 3.64 590.0 169.5 3.22 576.6 191.8 2.81 548.1 209.5 2.46 500.9 212.5 2.227 617.3 154.1 3.68 606.3 172.5 3.26 592.6 192.9 2.87 561.9 209.9 2.52 506.9 208.6 2.28  

8 634.1 156.5 3.73 622.8 175.2 3.30 608.6 194.3 2.93 575.6 210.3 2.57 513.3 204.9 2.3510 668.3 161.3 3.82 656.8 180.2 3.39 639.3 199.1 3.01 603.6 211.3 2.69 524.4 196.6 2.50  

12 703.2 166.0 3.92 691.4 185.3 3.48 670.7 202.9 3.10 631.5 215.8 2.75 533.6 188.5 2.6415 757.1 171.1 4.10 745.0 193.1 3.61 719.2 208.4 3.24 674.9 220.8 2.88 542.7 179.2 2.82  

15.5 766.3 172.0 4.13 754.1 194.1 3.63 727.4 209.4 3.26 682.1 221.7 2.90 543.8 177.4 2.85

4.5 627.4 159.0 3.60 617.2 179.9 3.16 605.6 204.5 2.76 585.2 229.7 2.39 562.4 251.5 2.115 636.1 160.5 3.62 625.8 180.4 3.20 613.8 205.0 2.79 592.3 229.9 2.42 568.9 251.9 2.13  

6 653.8 163.3 3.66 643.1 182.1 3.26 630.7 206.0 2.85 606.4 230.4 2.47 582.2 252.4 2.187 671.7 165.9 3.71 660.6 184.8 3.30 647.8 207.1 2.91 621.0 230.7 2.53 595.8 253.0 2.22  

8 689.9 168.6 3.76 678.4 187.8 3.34 665.1 208.8 2.97 635.7 231.1 2.58 609.7 253.4 2.2710 727.2 174.1 3.84 714.9 193.4 3.43 700.5 214.8 3.05 665.8 232.1 2.69 638.1 254.3 2.37  

12 765.8 179.6 3.93 752.6 199.1 3.51 737.2 220.8 3.13 695.7 236.4 2.77 658.0 248.3 2.5015 826.2 186.1 4.11 811.6 207.9 3.64 793.8 229.4 3.25 742.4 242.2 2.88 673.0 234.0 2.70  

15.5 836.6 187.2 4.14 821.7 209.3 3.66 802.9 230.6 3.27 750.4 243.1 2.91 675.7 231.8 2.74  

4.5 677.6 173.3 3.60 665.3 196.4 3.15 651.3 225.5 2.71 620.4 248.2 2.36 566.1 246.8 2.165 687.0 174.7 3.62 674.5 196.7 3.18 660.2 225.9 2.74 627.8 248.2 2.38 568.8 244.3 2.19  

6 706.3 177.4 3.67 693.1 199.4 3.23 678.0 226.6 2.81 642.7 248.1 2.44 574.2 239.0 2.267 725.9 180.1 3.72 712.1 202.6 3.27 695.4 226.7 2.88 658.0 247.8 2.50 580.8 234.2 2.33  

8 745.9 183.1 3.76 731.5 205.3 3.32 712.8 228.2 2.93 673.5 247.5 2.56 586.8 229.1 2.4010 787.1 189.5 3.85 771.5 211.0 3.41 748.4 233.1 3.02 705.2 247.7 2.68 598.5 219.2 2.55  

12 830.0 195.5 3.94 813.0 217.3 3.50 785.3 237.1 3.11 737.1 251.4 2.77 608.1 210.2 2.7015 897.0 204.5 4.08 878.1 227.1 3.62 843.1 243.8 3.26 787.0 255.0 2.91 618.5 199.8 2.88  

15.5 908.5 206.2 4.10 889.3 228.4 3.65 852.9 245.0 3.28 795.5 255.6 2.94 620.4 198.0 2.91

4.5 735.3 184.9 3.65 722.5 207.7 3.22 707.9 236.2 2.80 680.5 262.8 2.43 653.8 281.9 2.195 745.6 186.6 3.67 732.5 208.3 3.25 717.6 236.8 2.83 688.5 263.0 2.46 661.5 282.1 2.21

6 766.5 189.7 3.71 753.0 211.0 3.31 737.3 238.0 2.89 705.0 263.1 2.52 676.9 282.5 2.267 787.8 192.8 3.76 773.7 214.8 3.34 757.5 239.3 2.96 721.9 263.2 2.58 692.7 282.7 2.31

8 809.6 196.1 3.80 794.8 218.2 3.38 778.0 241.8 3.01 739.0 263.3 2.64 708.8 282.9 2.3610 854.3 202.8 3.89 838.4 224.8 3.47 820.1 249.7 3.08 773.8 264.0 2.76 741.7 283.2 2.47  

12 900.6 209.2 3.99 883.6 231.7 3.56 863.8 256.8 3.16 809.0 268.9 2.83 757.2 271.7 2.6215 972.8 217.0 4.16 953.8 242.3 3.68 926.6 264.8 3.29 863.9 274.2 2.97 773.4 255.8 2.84  

15.5 985.2 218.5 4.19 965.9 243.5 3.71 936.6 265.8 3.31 873.3 275.1 2.99 776.2 253.1 2.88  

4.5 806.5 202.9 3.64 793.1 228.1 3.22 777.5 258.7 2.80 750.9 289.2 2.44 731.6 316.6 2.185 817.7 204.9 3.66 804.0 228.8 3.25 788.1 259.5 2.84 760.1 289.6 2.47 740.4 317.1 2.21

6 840.4 208.5 3.70 826.2 231.2 3.31 809.7 261.0 2.90 778.7 290.2 2.52 758.1 317.9 2.257 863.6 212.0 3.75 848.8 235.5 3.34 831.6 262.6 2.96 797.8 290.8 2.58 776.2 318.7 2.30  

8 887.1 215.7 3.79 871.7 239.6 3.38 853.9 264.9 3.01 817.2 291.4 2.64 794.6 319.4 2.3510 935.6 223.1 3.87 919.0 247.0 3.46 899.7 273.8 3.08 856.6 293.0 2.75 811.9 307.1 2.49  

12 985.6 230.5 3.96 967.9 254.7 3.54 947.1 281.7 3.15 896.7 299.2 2.82 826.2 292.3 2.6615 1063.4 238.1 4.15 1043.9 266.0 3.67 1017.5 291.1 3.29 959.0 307.1 2.95 839.4 275.0 2.86  

15.5 1076.7 239.6 4.17 1056.9 267.5 3.70 1028.6 292.4 3.31 970.2 308.1 2.97 841.6 272.4 2.89

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

0650

YCIV

0720

YCIV

0770

YCIV

0840

YCIV

0920

Modelo

YCIV

0600

   L   W   T   °   C

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 27/72

 

27

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Rendimiento Estándar (SE) con Ventiladores Estándar - Capacidades Frigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 878.0 220.7 3.64 863.9 248.3 3.22 847.4 281.0 2.81 821.6 315.3 2.45 809.8 350.9 2.185 890.2 223.1 3.66 875.7 249.2 3.25 858.9 281.9 2.84 831.9 315.9 2.48 819.6 351.6 2.20  

6 914.7 227.2 3.70 899.8 251.2 3.32 882.3 283.7 2.90 852.7 317.0 2.53 839.6 353.0 2.257 939.6 231.1 3.74 924.2 256.0 3.35 905.9 285.6 2.96 874.0 318.1 2.58 860.0 354.3 2.30  

8 965.0 235.1 3.78 948.9 260.8 3.38 930.2 287.5 3.02 895.6 319.2 2.64 880.8 355.5 2.3410 1017.1 243.2 3.86 999.8 269.0 3.46 979.5 297.6 3.08 939.7 321.5 2.75 899.0 340.7 2.49  

12 1071.0 251.5 3.94 1052.4 277.5 3.54 1030.7 306.5 3.16 984.7 329.2 2.82 915.0 324.3 2.6615 1154.3 258.8 4.14 1134.3 289.5 3.66 1108.6 317.1 3.29 1054.5 339.7 2.93 931.5 306.9 2.85  

15.5 1168.5 260.4 4.16 1148.2 291.1 3.69 1120.9 318.8 3.31 1067.5 340.9 2.96 934.1 304.2 2.88  

4.5 932.9 232.2 3.67 916.0 264.8 3.20 896.3 302.4 2.76 860.2 335.8 2.41 793.7 343.2 2.175 945.9 234.4 3.69 928.9 265.3 3.23 908.7 303.0 2.80 871.0 336.1 2.43 797.8 340.2 2.20  

6 972.4 238.4 3.74 954.9 266.8 3.31 934.0 304.3 2.86 892.9 336.6 2.49 806.6 334.0 2.277 999.5 242.1 3.79 981.3 270.9 3.35 959.5 305.5 2.93 914.5 336.9 2.55 815.2 327.3 2.33  

8 1027.0 245.8 3.84 1008.2 275.3 3.39 984.7 306.3 3.00 936.6 337.1 2.61 825.3 321.3 2.4110 1083.4 253.9 3.93 1063.6 283.0 3.49 1035.8 313.4 3.09 981.9 337.3 2.73 843.3 308.4 2.55  

12 1141.8 262.4 4.02 1120.9 291.2 3.58 1088.6 320.1 3.18 1027.5 342.4 2.82 858.7 295.6 2.7115 1233.1 272.4 4.19 1210.5 304.6 3.71 1171.0 330.1 3.33 1098.2 349.8 2.95 874.3 280.8 2.89  

15.5 1248.7 274.3 4.22 1225.8 306.6 3.73 1185.1 331.9 3.35 1110.1 350.9 2.98 876.9 278.3 2.92

4.5 1037.0 257.4 3.69 1018.7 293.3 3.22 998.0 336.8 2.77 956.8 374.4 2.40 871.0 371.1 2.215 1051.5 259.8 3.71 1032.8 293.9 3.25 1011.6 337.4 2.80 968.3 374.3 2.43 875.3 367.5 2.24  

6 1080.9 263.9 3.76 1061.4 296.1 3.32 1038.8 338.2 2.87 991.4 374.1 2.49 883.5 359.5 2.317 1111.0 268.0 3.81 1090.5 300.9 3.36 1066.0 338.7 2.94 1014.8 373.8 2.55 892.9 351.9 2.38  

8 1141.7 272.3 3.86 1120.3 305.3 3.41 1093.6 339.6 3.01 1038.9 373.3 2.62 903.2 344.7 2.4510 1204.8 281.8 3.95 1181.6 313.7 3.50 1149.7 348.0 3.09 1088.0 372.4 2.75 921.7 329.9 2.61

12 1270.5 291.5 4.03 1245.3 322.9 3.59 1208.0 354.8 3.19 1137.4 377.8 2.83 937.4 316.1 2.7615 1373.7 304.6 4.19 1345.3 338.3 3.72 1299.5 366.0 3.34 1214.9 383.6 2.98 954.1 300.6 2.94  

15.5 1391.5 307.1 4.21 1362.6 340.2 3.75 1315.2 368.0 3.36 1228.1 384.6 3.01 956.1 297.5 2.98  

4.5 1170.2 292.8 3.66 1150.5 331.1 3.21 1127.9 375.9 2.80 1089.0 420.3 2.44 1056.9 457.1 2.185 1186.5 295.8 3.68 1166.4 332.1 3.25 1143.3 376.9 2.83 1102.3 420.6 2.46 1069.3 457.6 2.21

6 1219.7 301.3 3.72 1198.8 334.7 3.32 1174.6 379.0 2.89 1128.9 421.4 2.52 1094.6 458.7 2.257 1253.5 306.3 3.76 1231.7 340.3 3.35 1206.5 381.3 2.96 1156.3 422.1 2.58 1120.5 459.6 2.30  

8 1287.9 311.5 3.81 1265.2 346.4 3.39 1239.1 383.7 3.02 1184.3 422.7 2.63 1146.9 460.5 2.3510 1358.9 322.2 3.89 1334.3 357.1 3.47 1305.9 396.0 3.09 1241.4 424.0 2.75 1179.2 447.9 2.48  

12 1432.2 333.3 3.98 1406.0 368.2 3.56 1375.3 407.7 3.16 1299.2 431.7 2.83 1200.6 426.9 2.6515 1546.5 344.8 4.16 1517.5 385.1 3.68 1479.2 421.9 3.30 1389.4 442.8 2.96 1220.6 399.8 2.86  

15.5 1566.0 347.0 4.19 1536.6 387.4 3.71 1495.4 423.7 3.32 1404.6 444.5 2.98 1223.4 395.9 2.89

4.5 1312.9 328.4 3.66 1291.6 371.5 3.21 1267.1 420.5 2.81 1229.7 472.3 2.45 1212.5 525.6 2.185 1331.1 331.8 3.68 1309.5 372.7 3.25 1284.4 421.8 2.84 1245.0 473.2 2.47 1227.1 526.6 2.20  

6 1368.1 338.6 3.71 1345.7 375.3 3.32 1319.4 424.4 2.90 1276.1 474.9 2.53 1256.9 528.6 2.257 1405.8 344.4 3.75 1382.5 381.2 3.36 1355.1 427.3 2.96 1308.0 476.5 2.58 1287.3 530.6 2.30  

8 1444.3 350.3 3.80 1419.8 388.6 3.39 1391.6 430.2 3.02 1340.5 478.2 2.64 1318.4 532.5 2.3410 1523.2 362.6 3.88 1497.0 401.2 3.47 1466.2 443.5 3.10 1407.0 481.6 2.75 1353.8 516.2 2.48  

12 1604.3 375.3 3.96 1576.9 414.1 3.55 1543.8 457.3 3.17 1475.2 491.3 2.83 1378.3 491.4 2.6415 1728.9 386.5 4.15 1699.1 431.6 3.68 1661.9 473.7 3.30 1581.0 507.8 2.94 1404.9 463.7 2.84  

15.5 1750.0 388.8 4.18 1719.9 434.8 3.70 1680.4 476.2 3.32 1599.2 510.3 2.96 1408.7 459.7 2.87

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).

Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

1000

YCIV

1070

YCIV

1340

YCIV

1500

YCIV

1180

Modelo

   L   W   T   °   C

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 878.0 220.7 3.64 863.9 248.3 3.22 847.4 281.0 2.81 821.6 315.3 2.45 809.8 350.9 2.185 890.2 223.1 3.66 875.7 249.2 3.25 858.9 281.9 2.84 831.9 315.9 2.48 819.6 351.6 2.20  

6 914.7 227.2 3.70 899.8 251.2 3.32 882.3 283.7 2.90 852.7 317.0 2.53 839.6 353.0 2.257 939.6 231.1 3.74 924.2 256.0 3.35 905.9 285.6 2.96 874.0 318.1 2.58 860.0 354.3 2.30  

8 965.0 235.1 3.78 948.9 260.8 3.38 930.2 287.5 3.02 895.6 319.2 2.64 880.8 355.5 2.3410 1017.1 243.2 3.86 999.8 269.0 3.46 979.5 297.6 3.08 939.7 321.5 2.75 899.0 340.7 2.49  

12 1071.0 251.5 3.94 1052.4 277.5 3.54 1030.7 306.5 3.16 984.7 329.2 2.82 915.0 324.3 2.6615 1154.3 258.8 4.14 1134.3 289.5 3.66 1108.6 317.1 3.29 1054.5 339.7 2.93 931.5 306.9 2.85  

15.5 1168.5 260.4 4.16 1148.2 291.1 3.69 1120.9 318.8 3.31 1067.5 340.9 2.96 934.1 304.2 2.88  

4.5 932.9 232.2 3.67 916.0 264.8 3.20 896.3 302.4 2.76 860.2 335.8 2.41 793.7 343.2 2.175 945.9 234.4 3.69 928.9 265.3 3.23 908.7 303.0 2.80 871.0 336.1 2.43 797.8 340.2 2.20  

6 972.4 238.4 3.74 954.9 266.8 3.31 934.0 304.3 2.86 892.9 336.6 2.49 806.6 334.0 2.277 999.5 242.1 3.79 981.3 270.9 3.35 959.5 305.5 2.93 914.5 336.9 2.55 815.2 327.3 2.33  

8 1027.0 245.8 3.84 1008.2 275.3 3.39 984.7 306.3 3.00 936.6 337.1 2.61 825.3 321.3 2.4110 1083.4 253.9 3.93 1063.6 283.0 3.49 1035.8 313.4 3.09 981.9 337.3 2.73 843.3 308.4 2.55  

12 1141.8 262.4 4.02 1120.9 291.2 3.58 1088.6 320.1 3.18 1027.5 342.4 2.82 858.7 295.6 2.7115 1233.1 272.4 4.19 1210.5 304.6 3.71 1171.0 330.1 3.33 1098.2 349.8 2.95 874.3 280.8 2.89  

15.5 1248.7 274.3 4.22 1225.8 306.6 3.73 1185.1 331.9 3.35 1110.1 350.9 2.98 876.9 278.3 2.92

4.5 1037.0 257.4 3.69 1018.7 293.3 3.22 998.0 336.8 2.77 956.8 374.4 2.40 871.0 371.1 2.215 1051.5 259.8 3.71 1032.8 293.9 3.25 1011.6 337.4 2.80 968.3 374.3 2.43 875.3 367.5 2.24  

6 1080.9 263.9 3.76 1061.4 296.1 3.32 1038.8 338.2 2.87 991.4 374.1 2.49 883.5 359.5 2.317 1111.0 268.0 3.81 1090.5 300.9 3.36 1066.0 338.7 2.94 1014.8 373.8 2.55 892.9 351.9 2.38  

8 1141.7 272.3 3.86 1120.3 305.3 3.41 1093.6 339.6 3.01 1038.9 373.3 2.62 903.2 344.7 2.4510 1204.8 281.8 3.95 1181.6 313.7 3.50 1149.7 348.0 3.09 1088.0 372.4 2.75 921.7 329.9 2.61

12 1270.5 291.5 4.03 1245.3 322.9 3.59 1208.0 354.8 3.19 1137.4 377.8 2.83 937.4 316.1 2.7615 1373.7 304.6 4.19 1345.3 338.3 3.72 1299.5 366.0 3.34 1214.9 383.6 2.98 954.1 300.6 2.94  

15.5 1391.5 307.1 4.21 1362.6 340.2 3.75 1315.2 368.0 3.36 1228.1 384.6 3.01 956.1 297.5 2.98  

4.5 1170.2 292.8 3.66 1150.5 331.1 3.21 1127.9 375.9 2.80 1089.0 420.3 2.44 1056.9 457.1 2.185 1186.5 295.8 3.68 1166.4 332.1 3.25 1143.3 376.9 2.83 1102.3 420.6 2.46 1069.3 457.6 2.21

6 1219.7 301.3 3.72 1198.8 334.7 3.32 1174.6 379.0 2.89 1128.9 421.4 2.52 1094.6 458.7 2.257 1253.5 306.3 3.76 1231.7 340.3 3.35 1206.5 381.3 2.96 1156.3 422.1 2.58 1120.5 459.6 2.30  

8 1287.9 311.5 3.81 1265.2 346.4 3.39 1239.1 383.7 3.02 1184.3 422.7 2.63 1146.9 460.5 2.3510 1358.9 322.2 3.89 1334.3 357.1 3.47 1305.9 396.0 3.09 1241.4 424.0 2.75 1179.2 447.9 2.48  

12 1432.2 333.3 3.98 1406.0 368.2 3.56 1375.3 407.7 3.16 1299.2 431.7 2.83 1200.6 426.9 2.6515 1546.5 344.8 4.16 1517.5 385.1 3.68 1479.2 421.9 3.30 1389.4 442.8 2.96 1220.6 399.8 2.86  

15.5 1566.0 347.0 4.19 1536.6 387.4 3.71 1495.4 423.7 3.32 1404.6 444.5 2.98 1223.4 395.9 2.89

4.5 1312.9 328.4 3.66 1291.6 371.5 3.21 1267.1 420.5 2.81 1229.7 472.3 2.45 1212.5 525.6 2.185 1331.1 331.8 3.68 1309.5 372.7 3.25 1284.4 421.8 2.84 1245.0 473.2 2.47 1227.1 526.6 2.20  

6 1368.1 338.6 3.71 1345.7 375.3 3.32 1319.4 424.4 2.90 1276.1 474.9 2.53 1256.9 528.6 2.257 1405.8 344.4 3.75 1382.5 381.2 3.36 1355.1 427.3 2.96 1308.0 476.5 2.58 1287.3 530.6 2.30  

8 1444.3 350.3 3.80 1419.8 388.6 3.39 1391.6 430.2 3.02 1340.5 478.2 2.64 1318.4 532.5 2.3410 1523.2 362.6 3.88 1497.0 401.2 3.47 1466.2 443.5 3.10 1407.0 481.6 2.75 1353.8 516.2 2.48  

12 1604.3 375.3 3.96 1576.9 414.1 3.55 1543.8 457.3 3.17 1475.2 491.3 2.83 1378.3 491.4 2.6415 1728.9 386.5 4.15 1699.1 431.6 3.68 1661.9 473.7 3.30 1581.0 507.8 2.94 1404.9 463.7 2.84  

15.5 1750.0 388.8 4.18 1719.9 434.8 3.70 1680.4 476.2 3.32 1599.2 510.3 2.96 1408.7 459.7 2.87

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).

Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

1000

YCIV

1070

YCIV

1340

YCIV

1500

YCIV

1180

Modelo

   L   W   T   °   C

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 28/72

 

28

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE RENDIMIENTO ESTÁNDAR (SE RS) CON VENTILADORES ULTRA SILENCIOSO -CAPACIDADES FRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 530.4 146.2 3.34 516.9 162.3 2.96 502.0 178.7 2.62 484.1 195.9 2.32 467.1 214.4 2.065 538.3 146.5 3.38 524.5 162.6 2.99 509.3 179.3 2.65 491.1 196.6 2.35 474.0 215.6 2.08  

6 554.2 147.1 3.47 539.8 163.5 3.07 523.9 180.5 2.71 505.3 198.0 2.40 487.9 218.1 2.117 570.5 147.9 3.55 555.4 164.4 3.14 538.6 181.8 2.77 519.6 199.7 2.45 502.0 220.5 2.15  

8 587.0 148.7 3.64 571.2 165.4 3.21 553.7 183.0 2.83 534.0 201.2 2.50 507.3 215.6 2.22

10 620.6 150.8 3.80 603.6 167.9 3.34 584.5 185.9 2.94 563.6 204.5 2.60 517.7 205.3 2.38  

12 655.3 153.2 3.95 637.0 170.6 3.48 616.6 188.9 3.06 594.5 208.0 2.69 527.2 194.9 2.5415 709.7 157.0 4.18 689.4 174.9 3.68 667.3 193.4 3.24 644.3 213.8 2.85 541.6 181.9 2.78  

15.5 719.0 157.8 4.22 698.5 175.7 3.71 676.0 194.2 3.27 653.0 214.9 2.87 543.9 179.8 2.83  

4.5 571.9 158.2 3.35 560.2 178.2 2.94 542.9 199.1 2.56 511.5 214.2 2.25 436.2 194.4 2.115  579.8 159.7 3.36 568.0 178.8 2.97 550.0 199.5 2.59 517.6 214.5 2.28 438.5 192.4 2.14  

6 595.9 162.4 3.40 583.8 181.2 3.01 564.1 200.2 2.65 529.9 215.3 2.32 443.1 188.4 2.207 612.2 165.1 3.44 599.6 184.7 3.04 578.5 200.8 2.71 542.6 215.9 2.37 447.5 184.5 2.27  

8 628.7 167.8 3.48 615.8 187.8 3.07 593.0 202.4 2.76 555.5 216.5 2.42 451.8 180.5 2.3410 662.4 173.3 3.56 648.9 193.7 3.15 622.1 207.7 2.82 581.6 218.3 2.52 459.2 172.2 2.48  

12 696.9 178.2 3.65 682.5 199.3 3.22 652.3 211.9 2.90 602.0 219.2 2.60 466.9 165.0 2.6315 750.2 183.8 3.82 730.2 205.0 3.36 697.3 217.8 3.03 615.4 208.0 2.79 475.9 156.2 2.82  

15.5 759.3 184.8 3.85 738.4 205.4 3.39 704.5 218.7 3.05 617.4 206.2 2.82 477.4 154.7 2.85

4.5 623.2 168.7 3.41 612.3 190.5 2.99 599.8 216.3 2.60 567.6 236.4 2.27 540.1 254.2 2.01

5 631.8 170.4 3.42 620.6 191.2 3.02 607.8 217.0 2.63 574.3 236.7 2.29 541.8 251.1 2.04  

6 649.1 173.6 3.46 637.6 193.3 3.07 624.2 218.4 2.68 587.7 237.2 2.34 545.6 245.2 2.107 666.7 176.5 3.50 654.7 196.7 3.10 640.9 219.9 2.74 601.3 237.8 2.39 550.1 239.7 2.17  

8 684.6 179.4 3.54 672.1 200.1 3.14 657.8 222.0 2.78 615.1 238.3 2.44 555.2 234.4 2.2310 721.2 185.6 3.61 707.7 206.4 3.21 689.8 227.8 2.85 643.3 239.8 2.53 566.5 224.6 2.37  

12 759.1 191.4 3.69 744.4 212.9 3.28 720.1 232.3 2.92 671.5 244.7 2.59 577.7 215.6 2.5115 818.3 198.2 3.85 802.0 222.6 3.39 766.7 238.6 3.03 715.0 250.9 2.70 590.2 205.3 2.69  

15.5 828.4 199.4 3.88 811.8 224.1 3.41 774.7 239.7 3.05 722.4 251.9 2.71 592.0 203.5 2.72  

4.5 671.8 186.0 3.35 658.6 210.5 2.93 637.8 236.6 2.54 599.8 253.8 2.24 498.1 217.3 2.155 681.0 187.5 3.38 667.6 211.0 2.96 645.8 236.8 2.57 606.7 253.9 2.26 500.7 215.1 2.18  

6 699.8 190.5 3.42 685.6 214.4 3.00 662.0 237.2 2.63 620.7 254.1 2.31 507.6 215.6 2.217 719.0 193.5 3.46 704.0 218.1 3.03 678.5 237.5 2.70 635.0 254.1 2.37 510.8 206.2 2.32  

8 738.4 196.8 3.50 722.8 221.4 3.07 695.0 239.8 2.74 649.4 254.0 2.42 515.8 201.9 2.3910 778.6 203.5 3.58 761.2 227.7 3.15 728.8 245.3 2.81 676.2 253.2 2.53 524.4 192.7 2.53  

12 820.2 209.4 3.67 798.1 232.5 3.23 762.1 248.8 2.90 686.3 244.1 2.66 532.9 184.5 2.6815 885.6 217.9 3.81 855.7 239.1 3.38 811.8 253.3 3.03 700.7 231.5 2.85 543.2 174.8 2.87  

15.5 896.7 219.5 3.84 865.5 239.9 3.41 820.2 254.1 3.06 702.9 229.7 2.88 544.9 173.2 2.91

4.5 729.6 196.7 3.43 716.0 220.6 3.03 700.4 250.5 2.63 659.2 268.6 2.32 622.2 279.8 2.115 739.8 198.6 3.45 725.7 221.4 3.06 709.8 251.3 2.66 666.8 268.8 2.34 624.8 277.2 2.13  

6 760.3 202.0 3.49 745.5 224.8 3.10 729.0 253.0 2.71 682.2 269.1 2.39 630.1 272.0 2.197 781.2 205.5 3.53 765.8 229.2 3.13 748.4 254.8 2.77 698.0 269.3 2.45 635.6 266.6 2.25  

8 802.4 209.0 3.57 786.4 233.0 3.16 767.0 257.3 2.81 714.0 269.5 2.50 641.5 261.0 2.3210 846.2 216.5 3.64 828.7 240.6 3.23 801.5 262.6 2.88 746.5 270.9 2.60 653.5 249.2 2.47  

12 891.6 222.9 3.74 872.6 248.4 3.30 836.9 266.8 2.96 779.3 276.0 2.67 0.0 0.0 0.0015 962.0 231.2 3.89 940.9 259.6 3.42 892.0 272.8 3.09 830.5 281.4 2.79 677.5 225.8 2.80  

15.5 974.1 232.8 3.92 952.7 261.0 3.44 901.3 273.7 3.11 839.0 282.4 2.81 678.9 223.6 2.84  

4.5 800.6 215.6 3.44 786.1 241.9 3.03 769.5 274.1 2.64 731.3 298.0 2.32 683.4 305.3 2.125 811.6 217.8 3.45 796.8 242.9 3.06 779.8 275.1 2.67 740.0 298.4 2.34 686.8 302.5 2.15  

6 833.9 221.8 3.49 818.5 246.0 3.11 800.8 277.0 2.72 757.6 299.2 2.39 693.4 296.5 2.217 856.6 225.7 3.52 840.4 250.9 3.13 822.1 279.1 2.77 775.6 300.1 2.44 699.6 290.1 2.28  

8 879.7 229.7 3.56 862.8 255.4 3.16 842.9 281.5 2.82 794.0 300.8 2.49 705.4 283.2 2.3510 927.2 238.0 3.63 908.8 264.0 3.23 882.0 288.8 2.88 831.2 302.9 2.59 714.8 268.6 2.50  

12 976.2 245.6 3.71 956.5 272.7 3.30 922.4 294.7 2.96 868.8 310.0 2.65 725.0 255.8 2.6515 1052.5 253.8 3.88 1030.7 285.0 3.41 984.8 303.3 3.07 927.6 318.4 2.76 736.9 242.7 2.83  

15.5 1065.5 255.4 3.91 1043.3 286.5 3.43 996.4 304.2 3.10 937.5 319.8 2.78 739.0 240.5 2.87

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

0840

YCIV

0920

Modelo

   L   W   T   °   C

YCIV

0600

YCIV

0650

YCIV

0720

YCIV

0770

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 530.4 146.2 3.34 516.9 162.3 2.96 502.0 178.7 2.62 484.1 195.9 2.32 467.1 214.4 2.065 538.3 146.5 3.38 524.5 162.6 2.99 509.3 179.3 2.65 491.1 196.6 2.35 474.0 215.6 2.08  

6 554.2 147.1 3.47 539.8 163.5 3.07 523.9 180.5 2.71 505.3 198.0 2.40 487.9 218.1 2.117 570.5 147.9 3.55 555.4 164.4 3.14 538.6 181.8 2.77 519.6 199.7 2.45 502.0 220.5 2.15  

8 587.0 148.7 3.64 571.2 165.4 3.21 553.7 183.0 2.83 534.0 201.2 2.50 507.3 215.6 2.22

10 620.6 150.8 3.80 603.6 167.9 3.34 584.5 185.9 2.94 563.6 204.5 2.60 517.7 205.3 2.38  

12 655.3 153.2 3.95 637.0 170.6 3.48 616.6 188.9 3.06 594.5 208.0 2.69 527.2 194.9 2.5415 709.7 157.0 4.18 689.4 174.9 3.68 667.3 193.4 3.24 644.3 213.8 2.85 541.6 181.9 2.78  

15.5 719.0 157.8 4.22 698.5 175.7 3.71 676.0 194.2 3.27 653.0 214.9 2.87 543.9 179.8 2.83  

4.5 571.9 158.2 3.35 560.2 178.2 2.94 542.9 199.1 2.56 511.5 214.2 2.25 436.2 194.4 2.115  579.8 159.7 3.36 568.0 178.8 2.97 550.0 199.5 2.59 517.6 214.5 2.28 438.5 192.4 2.14  

6 595.9 162.4 3.40 583.8 181.2 3.01 564.1 200.2 2.65 529.9 215.3 2.32 443.1 188.4 2.207 612.2 165.1 3.44 599.6 184.7 3.04 578.5 200.8 2.71 542.6 215.9 2.37 447.5 184.5 2.27  

8 628.7 167.8 3.48 615.8 187.8 3.07 593.0 202.4 2.76 555.5 216.5 2.42 451.8 180.5 2.3410 662.4 173.3 3.56 648.9 193.7 3.15 622.1 207.7 2.82 581.6 218.3 2.52 459.2 172.2 2.48  

12 696.9 178.2 3.65 682.5 199.3 3.22 652.3 211.9 2.90 602.0 219.2 2.60 466.9 165.0 2.6315 750.2 183.8 3.82 730.2 205.0 3.36 697.3 217.8 3.03 615.4 208.0 2.79 475.9 156.2 2.82  

15.5 759.3 184.8 3.85 738.4 205.4 3.39 704.5 218.7 3.05 617.4 206.2 2.82 477.4 154.7 2.85

4.5 623.2 168.7 3.41 612.3 190.5 2.99 599.8 216.3 2.60 567.6 236.4 2.27 540.1 254.2 2.01

5 631.8 170.4 3.42 620.6 191.2 3.02 607.8 217.0 2.63 574.3 236.7 2.29 541.8 251.1 2.04  

6 649.1 173.6 3.46 637.6 193.3 3.07 624.2 218.4 2.68 587.7 237.2 2.34 545.6 245.2 2.107 666.7 176.5 3.50 654.7 196.7 3.10 640.9 219.9 2.74 601.3 237.8 2.39 550.1 239.7 2.17  

8 684.6 179.4 3.54 672.1 200.1 3.14 657.8 222.0 2.78 615.1 238.3 2.44 555.2 234.4 2.2310 721.2 185.6 3.61 707.7 206.4 3.21 689.8 227.8 2.85 643.3 239.8 2.53 566.5 224.6 2.37  

12 759.1 191.4 3.69 744.4 212.9 3.28 720.1 232.3 2.92 671.5 244.7 2.59 577.7 215.6 2.5115 818.3 198.2 3.85 802.0 222.6 3.39 766.7 238.6 3.03 715.0 250.9 2.70 590.2 205.3 2.69  

15.5 828.4 199.4 3.88 811.8 224.1 3.41 774.7 239.7 3.05 722.4 251.9 2.71 592.0 203.5 2.72  

4.5 671.8 186.0 3.35 658.6 210.5 2.93 637.8 236.6 2.54 599.8 253.8 2.24 498.1 217.3 2.155 681.0 187.5 3.38 667.6 211.0 2.96 645.8 236.8 2.57 606.7 253.9 2.26 500.7 215.1 2.18  

6 699.8 190.5 3.42 685.6 214.4 3.00 662.0 237.2 2.63 620.7 254.1 2.31 507.6 215.6 2.217 719.0 193.5 3.46 704.0 218.1 3.03 678.5 237.5 2.70 635.0 254.1 2.37 510.8 206.2 2.32  

8 738.4 196.8 3.50 722.8 221.4 3.07 695.0 239.8 2.74 649.4 254.0 2.42 515.8 201.9 2.3910 778.6 203.5 3.58 761.2 227.7 3.15 728.8 245.3 2.81 676.2 253.2 2.53 524.4 192.7 2.53  

12 820.2 209.4 3.67 798.1 232.5 3.23 762.1 248.8 2.90 686.3 244.1 2.66 532.9 184.5 2.6815 885.6 217.9 3.81 855.7 239.1 3.38 811.8 253.3 3.03 700.7 231.5 2.85 543.2 174.8 2.87  

15.5 896.7 219.5 3.84 865.5 239.9 3.41 820.2 254.1 3.06 702.9 229.7 2.88 544.9 173.2 2.91

4.5 729.6 196.7 3.43 716.0 220.6 3.03 700.4 250.5 2.63 659.2 268.6 2.32 622.2 279.8 2.115 739.8 198.6 3.45 725.7 221.4 3.06 709.8 251.3 2.66 666.8 268.8 2.34 624.8 277.2 2.13  

6 760.3 202.0 3.49 745.5 224.8 3.10 729.0 253.0 2.71 682.2 269.1 2.39 630.1 272.0 2.197 781.2 205.5 3.53 765.8 229.2 3.13 748.4 254.8 2.77 698.0 269.3 2.45 635.6 266.6 2.25  

8 802.4 209.0 3.57 786.4 233.0 3.16 767.0 257.3 2.81 714.0 269.5 2.50 641.5 261.0 2.3210 846.2 216.5 3.64 828.7 240.6 3.23 801.5 262.6 2.88 746.5 270.9 2.60 653.5 249.2 2.47  

12 891.6 222.9 3.74 872.6 248.4 3.30 836.9 266.8 2.96 779.3 276.0 2.67 0.0 0.0 0.0015 962.0 231.2 3.89 940.9 259.6 3.42 892.0 272.8 3.09 830.5 281.4 2.79 677.5 225.8 2.80  

15.5 974.1 232.8 3.92 952.7 261.0 3.44 901.3 273.7 3.11 839.0 282.4 2.81 678.9 223.6 2.84  

4.5 800.6 215.6 3.44 786.1 241.9 3.03 769.5 274.1 2.64 731.3 298.0 2.32 683.4 305.3 2.125 811.6 217.8 3.45 796.8 242.9 3.06 779.8 275.1 2.67 740.0 298.4 2.34 686.8 302.5 2.15  

6 833.9 221.8 3.49 818.5 246.0 3.11 800.8 277.0 2.72 757.6 299.2 2.39 693.4 296.5 2.217 856.6 225.7 3.52 840.4 250.9 3.13 822.1 279.1 2.77 775.6 300.1 2.44 699.6 290.1 2.28  

8 879.7 229.7 3.56 862.8 255.4 3.16 842.9 281.5 2.82 794.0 300.8 2.49 705.4 283.2 2.3510 927.2 238.0 3.63 908.8 264.0 3.23 882.0 288.8 2.88 831.2 302.9 2.59 714.8 268.6 2.50  

12 976.2 245.6 3.71 956.5 272.7 3.30 922.4 294.7 2.96 868.8 310.0 2.65 725.0 255.8 2.6515 1052.5 253.8 3.88 1030.7 285.0 3.41 984.8 303.3 3.07 927.6 318.4 2.76 736.9 242.7 2.83  

15.5 1065.5 255.4 3.91 1043.3 286.5 3.43 996.4 304.2 3.10 937.5 319.8 2.78 739.0 240.5 2.87

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

0840

YCIV

0920

Modelo

   L   W   T   °   C

YCIV

0600

YCIV

0650

YCIV

0720

YCIV

0770

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 29/72

 

29

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Rendimiento Estándar (SE RS) con Ventiladores Ultra Silencioso - Capacidades Frigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 871.9 234.3 3.44 856.5 263.1 3.04 838.8 297.5 2.65 803.6 326.9 2.32 755.1 337.0 2.125 883.8 236.8 3.45 868.2 264.1 3.07 850.0 298.5 2.68 813.4 327.6 2.35 758.5 333.5 2.15  

6 907.9 241.4 3.49 891.6 267.0 3.12 872.8 300.8 2.73 833.3 329.0 2.39 765.6 326.3 2.227 932.4 245.8 3.52 915.4 272.5 3.14 895.9 303.1 2.78 853.5 330.5 2.44 772.9 319.0 2.29  

8 957.3 250.2 3.56 939.6 277.6 3.17 919.0 305.5 2.83 874.1 331.8 2.49 779.9 311.8 2.3610 1008.4 259.2 3.62 989.2 287.1 3.23 962.8 314.8 2.88 916.3 334.5 2.59 792.5 298.0 2.50  

12 1061.2 268.0 3.70 1040.5 296.7 3.30 1008.1 322.2 2.95 958.6 343.7 2.64 805.3 284.9 2.6515 1143.3 276.2 3.87 1120.7 310.1 3.41 1077.9 333.4 3.06 1025.0 355.0 2.74 819.0 270.6 2.83  

15.5 1157.2 277.7 3.90 1134.2 311.7 3.43 1091.7 334.3 3.09 1036.3 356.8 2.76 821. 5 268.1 2.86  

4.5 925.7 247.8 3.45 907.4 281.8 3.00 881.7 317.3 2.61 833.9 344.3 2.29 701.4 304.7 2.165 938.5 250.2 3.47 919.9 282.7 3.03 893.1 317.8 2.64 843.8 344.7 2.31 705.3 301.8 2.19  

6 964.5 254.6 3.51 945.3 284.7 3.10 916.4 319.0 2.70 863.6 345.5 2.36 712.6 295.8 2.257 991.1 258.7 3.55 971.1 289.7 3.13 940.1 320.0 2.76 884.0 346.0 2.41 719.9 289.7 2.32  

8 1018.1 262.9 3.59 997.3 294.8 3.16 964.4 321.3 2.82 904.7 346.5 2.46 727.0 283.6 2.3910 1073.5 271.7 3.67 1051.3 303.8 3.24 1013.1 329.9 2.89 947.0 347.3 2.57 738.8 270.8 2.54  

12 1130.8 280.6 3.76 1105.2 311.8 3.33 1063.5 337.2 2.97 970.4 341.0 2.68 751.7 258.8 2.6915 1220.4 290.6 3.92 1187.1 323.0 3.46 1135.6 345.4 3.10 993.2 324.3 2.88 766.9 245.4 2.88  

15.5 1235.7 292.5 3.95 1201.2 324.3 3.48 1147.6 346.7 3.13 995.7 321.4 2.91 769.3 243.1 2.92

4.5 1028.7 275.5 3.46 1009.1 313.6 3.01 981.0 354.4 2.61 926.3 382.7 2.29 766.9 326.6 2.205 1042.9 278.1 3.47 1022.9 314.3 3.04 993.6 354.9 2.64 936.9 382.9 2.31 770.8 323.4 2.23  

6 1071.7 282.6 3.52 1050.8 317.4 3.09 1019.1 355.8 2.70 958.6 383.1 2.37 778.7 316.8 2.307 1101.1 287.1 3.56 1079.0 323.1 3.13 1045.1 356.6 2.76 980.7 383.1 2.42 786.6 310.3 2.37  

8 1131.0 291.8 3.60 1107.9 328.1 3.16 1071.4 358.6 2.81 1003.1 383.0 2.48 794.3 303.7 2.4410 1192.6 301.8 3.68 1167.0 337.3 3.25 1125.1 368.2 2.88 1043.3 379.0 2.60 807.4 289.9 2.59  

12 1256.7 311.2 3.77 1225.4 345.4 3.33 1177.1 373.7 2.97 1058.8 365.6 2.73 821.6 277.3 2.7415 1357.2 323.7 3.92 1316.7 357.7 3.47 1254.3 380.6 3.11 1081.6 346.9 2.93 837.3 262.8 2.94  

15.5 1374.4 326.1 3.95 1332.5 359.0 3.50 1267.5 381.8 3.14 1085.2 344.3 2.96 839.9 260.4 2.97  

4.5 1161.7 311.2 3.45 1140.5 351.2 3.03 1116.4 398.2 2.64 1059.1 431.7 2.32 993.6 444.8 2.115 1177.7 314.5 3.47 1156.1 352.4 3.06 1131.3 399.5 2.66 1071.6 432.3 2.34 998.6 441.3 2.14  

6 1210.2 320.4 3.50 1187.6 355.9 3.12 1161.7 402.3 2.72 1096.8 433.3 2.39 1008.5 433.3 2.207 1243.3 326.1 3.54 1219.6 362.6 3.14 1192.7 405.2 2.77 1122.7 434.2 2.44 1017.8 424.5 2.26  

8 1277.1 331.8 3.58 1252.3 369.3 3.17 1224.3 408.4 2.82 1148.9 435.2 2.50 1026.5 414.9 2.3310 1346.5 343.8 3.65 1319.5 381.7 3.24 1280.9 418.2 2. 89 1202.6 436.9 2.60 1039.3 392.9 2.49  

12 1418.5 355.4 3.73 1389.3 394.2 3.31 1339.1 426.4 2.96 1256.8 446.0 2.67 1053.4 372.5 2.6515 1530.3 367.6 3.90 1497.9 412.7 3.42 1429.4 438.0 3. 09 1341.3 457.6 2.78 1070.9 353.1 2.83  

15.5 1549.4 369.9 3.92 1516.5 415.2 3.44 1444.6 439.9 3.11 1355.7 459.4 2.80 1073.9 349.8 2.86

4.5 1303.8 348.4 3.46 1280.8 393.4 3.04 1254.6 444.9 2.65 1203.1 489.6 2.32 1137.3 509.7 2.115 1321.7 352.2 3.47 1298.3 394.9 3.07 1271.4 446.5 2.68 1217.8 490.6 2.35 1142.5 504.5 2.14  

6 1358.0 359.5 3.50 1333.7 398.0 3.13 1305.4 449.8 2.73 1247.5 492.7 2.39 1153.0 493.8 2.217 1394.9 366.2 3.53 1369.5 405.5 3.16 1340.2 453.2 2.78 1277.8 494.7 2.44 1163.7 482.9 2.28  

8 1432.7 372.8 3.57 1406.0 413.7 3.18 1375.7 456.7 2.84 1308.5 496.9 2.49 1174.5 472.0 2.3510 1510.1 386.4 3.64 1481.1 428.1 3.24 1442.4 469.5 2. 90 1371.9 500.9 2.59 1193.7 451.2 2.49  

12 1590.2 400.6 3.71 1559.0 442.5 3.31 1510.9 481.2 2.96 1436.4 512.6 2.65 1213.3 431.4 2.6415 1712.6 412.4 3.88 1679.0 462.5 3.42 1616.7 498.2 3. 07 1536.4 530.4 2.75 1234.9 409.1 2.82  

15.5 1733.2 414.9 3.91 1699.1 465.7 3.44 1634.3 500.9 3.09 1553.6 533.1 2.77 1238.6 405.4 2.86

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).

Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

1500

YCIV

1000

YCIV

1070

YCIV

1180

YCIV

1340

Modelo

   L   W   T   °   C

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 871.9 234.3 3.44 856.5 263.1 3.04 838.8 297.5 2.65 803.6 326.9 2.32 755.1 337.0 2.125 883.8 236.8 3.45 868.2 264.1 3.07 850.0 298.5 2.68 813.4 327.6 2.35 758.5 333.5 2.15  

6 907.9 241.4 3.49 891.6 267.0 3.12 872.8 300.8 2.73 833.3 329.0 2.39 765.6 326.3 2.227 932.4 245.8 3.52 915.4 272.5 3.14 895.9 303.1 2.78 853.5 330.5 2.44 772.9 319.0 2.29  

8 957.3 250.2 3.56 939.6 277.6 3.17 919.0 305.5 2.83 874.1 331.8 2.49 779.9 311.8 2.3610 1008.4 259.2 3.62 989.2 287.1 3.23 962.8 314.8 2.88 916.3 334.5 2.59 792.5 298.0 2.50  

12 1061.2 268.0 3.70 1040.5 296.7 3.30 1008.1 322.2 2.95 958.6 343.7 2.64 805.3 284.9 2.6515 1143.3 276.2 3.87 1120.7 310.1 3.41 1077.9 333.4 3.06 1025.0 355.0 2.74 819.0 270.6 2.83  

15.5 1157.2 277.7 3.90 1134.2 311.7 3.43 1091.7 334.3 3.09 1036.3 356.8 2.76 821. 5 268.1 2.86  

4.5 925.7 247.8 3.45 907.4 281.8 3.00 881.7 317.3 2.61 833.9 344.3 2.29 701.4 304.7 2.165 938.5 250.2 3.47 919.9 282.7 3.03 893.1 317.8 2.64 843.8 344.7 2.31 705.3 301.8 2.19  

6 964.5 254.6 3.51 945.3 284.7 3.10 916.4 319.0 2.70 863.6 345.5 2.36 712.6 295.8 2.257 991.1 258.7 3.55 971.1 289.7 3.13 940.1 320.0 2.76 884.0 346.0 2.41 719.9 289.7 2.32  

8 1018.1 262.9 3.59 997.3 294.8 3.16 964.4 321.3 2.82 904.7 346.5 2.46 727.0 283.6 2.3910 1073.5 271.7 3.67 1051.3 303.8 3.24 1013.1 329.9 2.89 947.0 347.3 2.57 738.8 270.8 2.54  

12 1130.8 280.6 3.76 1105.2 311.8 3.33 1063.5 337.2 2.97 970.4 341.0 2.68 751.7 258.8 2.6915 1220.4 290.6 3.92 1187.1 323.0 3.46 1135.6 345.4 3.10 993.2 324.3 2.88 766.9 245.4 2.88  

15.5 1235.7 292.5 3.95 1201.2 324.3 3.48 1147.6 346.7 3.13 995.7 321.4 2.91 769.3 243.1 2.92

4.5 1028.7 275.5 3.46 1009.1 313.6 3.01 981.0 354.4 2.61 926.3 382.7 2.29 766.9 326.6 2.205 1042.9 278.1 3.47 1022.9 314.3 3.04 993.6 354.9 2.64 936.9 382.9 2.31 770.8 323.4 2.23  

6 1071.7 282.6 3.52 1050.8 317.4 3.09 1019.1 355.8 2.70 958.6 383.1 2.37 778.7 316.8 2.307 1101.1 287.1 3.56 1079.0 323.1 3.13 1045.1 356.6 2.76 980.7 383.1 2.42 786.6 310.3 2.37  

8 1131.0 291.8 3.60 1107.9 328.1 3.16 1071.4 358.6 2.81 1003.1 383.0 2.48 794.3 303.7 2.4410 1192.6 301.8 3.68 1167.0 337.3 3.25 1125.1 368.2 2.88 1043.3 379.0 2.60 807.4 289.9 2.59  

12 1256.7 311.2 3.77 1225.4 345.4 3.33 1177.1 373.7 2.97 1058.8 365.6 2.73 821.6 277.3 2.7415 1357.2 323.7 3.92 1316.7 357.7 3.47 1254.3 380.6 3.11 1081.6 346.9 2.93 837.3 262.8 2.94  

15.5 1374.4 326.1 3.95 1332.5 359.0 3.50 1267.5 381.8 3.14 1085.2 344.3 2.96 839.9 260.4 2.97  

4.5 1161.7 311.2 3.45 1140.5 351.2 3.03 1116.4 398.2 2.64 1059.1 431.7 2.32 993.6 444.8 2.115 1177.7 314.5 3.47 1156.1 352.4 3.06 1131.3 399.5 2.66 1071.6 432.3 2.34 998.6 441.3 2.14  

6 1210.2 320.4 3.50 1187.6 355.9 3.12 1161.7 402.3 2.72 1096.8 433.3 2.39 1008.5 433.3 2.207 1243.3 326.1 3.54 1219.6 362.6 3.14 1192.7 405.2 2.77 1122.7 434.2 2.44 1017.8 424.5 2.26  

8 1277.1 331.8 3.58 1252.3 369.3 3.17 1224.3 408.4 2.82 1148.9 435.2 2.50 1026.5 414.9 2.3310 1346.5 343.8 3.65 1319.5 381.7 3.24 1280.9 418.2 2. 89 1202.6 436.9 2.60 1039.3 392.9 2.49  

12 1418.5 355.4 3.73 1389.3 394.2 3.31 1339.1 426.4 2.96 1256.8 446.0 2.67 1053.4 372.5 2.6515 1530.3 367.6 3.90 1497.9 412.7 3.42 1429.4 438.0 3. 09 1341.3 457.6 2.78 1070.9 353.1 2.83  

15.5 1549.4 369.9 3.92 1516.5 415.2 3.44 1444.6 439.9 3.11 1355.7 459.4 2.80 1073.9 349.8 2.86

4.5 1303.8 348.4 3.46 1280.8 393.4 3.04 1254.6 444.9 2.65 1203.1 489.6 2.32 1137.3 509.7 2.115 1321.7 352.2 3.47 1298.3 394.9 3.07 1271.4 446.5 2.68 1217.8 490.6 2.35 1142.5 504.5 2.14  

6 1358.0 359.5 3.50 1333.7 398.0 3.13 1305.4 449.8 2.73 1247.5 492.7 2.39 1153.0 493.8 2.217 1394.9 366.2 3.53 1369.5 405.5 3.16 1340.2 453.2 2.78 1277.8 494.7 2.44 1163.7 482.9 2.28  

8 1432.7 372.8 3.57 1406.0 413.7 3.18 1375.7 456.7 2.84 1308.5 496.9 2.49 1174.5 472.0 2.3510 1510.1 386.4 3.64 1481.1 428.1 3.24 1442.4 469.5 2. 90 1371.9 500.9 2.59 1193.7 451.2 2.49  

12 1590.2 400.6 3.71 1559.0 442.5 3.31 1510.9 481.2 2.96 1436.4 512.6 2.65 1213.3 431.4 2.6415 1712.6 412.4 3.88 1679.0 462.5 3.42 1616.7 498.2 3. 07 1536.4 530.4 2.75 1234.9 409.1 2.82  

15.5 1733.2 414.9 3.91 1699.1 465.7 3.44 1634.3 500.9 3.09 1553.6 533.1 2.77 1238.6 405.4 2.86

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).

Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

1500

YCIV

1000

YCIV

1070

YCIV

1180

YCIV

1340

Modelo

   L   W   T   °   C

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 30/72

 

30

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE RENDIMIENTO ESTÁNDAR (SE LS) CON VENTILADORES DE DOS VELOCIDADES- CAPACIDADES FRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 530.4 146.2 3.35 516.9 162.3 2.97 502.0 178.7 2.63 484.1 195.9 2.33 467.1 214.4 2.065 538.3 146.5 3.40 524.5 162.6 3.00 509.3 179.3 2.66 491.1 196.6 2.35 474.0 215.6 2.08  

6 554.2 147.1 3.48 539.8 163.5 3.08 523.9 180.5 2.72 505.3 198.0 2.41 487.9 218.1 2.127 570.5 147.9 3.57 555.4 164.4 3.15 538.6 181.8 2.78 519.6 199.7 2.45 502.0 220.5 2.16  

8 587.0 148.7 3.65 571.2 165.4 3.22 553.7 183.0 2.84 534.0 201.2 2.50 507.3 215.6 2.2310 620.6 150.8 3.81 603.6 167.9 3.36 584.5 185.9 2.95 563.6 204.5 2.60 517.7 205.3 2.38  

12 655.3 153.2 3.97 637.0 170.6 3.49 616.6 188.9 3.07 594.5 208.0 2.70 527.2 194.9 2.5515 709.7 157.0 4.20 689.4 174.9 3.69 667.3 193.4 3.25 644.3 213.8 2.85 541.6 181.9 2.79  

15.5 719.0 157.8 4.24 698.5 175.7 3.72 676.0 194.2 3.28 653.0 214.9 2.88 543.9 179.8 2.84  

4.5 571.9 158.2 3.36 560.2 178.2 2.95 542.9 199.1 2.57 511.5 214.2 2.26 436.2 194.4 2.115  579.8 159.7 3.38 568.0 178.8 2.98 550.0 199.5 2.60 517.6 214.5 2.28 438.5 192.4 2.15  

6 595.9 162.4 3.42 583.8 181.2 3.02 564.1 200.2 2.66 529.9 215.3 2.33 443.1 188.4 2.217 612.2 165.1 3.46 599.6 184.7 3.05 578.5 200.8 2.72 542.6 215.9 2.38 447.5 184.5 2.28  

8 628.7 167.8 3.50 615.8 187.8 3.08 593.0 202.4 2.77 555.5 216.5 2.43 451.8 180.5 2.3510 662.4 173.3 3.57 648.9 193.7 3.15 622.1 207.7 2.83 581.6 218.3 2.53 459.2 172.2 2.49  

12 696.9 178.2 3.66 682.5 199.3 3.23 652.3 211.9 2.91 602.0 219.2 2.60 466.9 165.0 2.6415 750.2 183.8 3.83 730.2 205.0 3.37 697.3 217.8 3.03 615.4 208.0 2.80 475.9 156.2 2.83  

15.5 759.3 184.8 3.86 738.4 205.4 3.40 704.5 218.7 3.05 617.4 206.2 2.83 477.4 154.7 2.86

4.5 623.2 168.7 3.42 612.3 190.5 3.00 599.8 216.3 2.61 567.6 236.4 2.27 540.1 254.2 2.025 631.8 170.4 3.44 620.6 191.2 3.03 607.8 217.0 2.64 574.3 236.7 2.30 541.8 251.1 2.05  

6 649.1 173.6 3.47 637.6 193.3 3.08 624.2 218.4 2.69 587.7 237.2 2.34 545.6 245.2 2.117 666.7 176.5 3.51 654.7 196.7 3.11 640.9 219.9 2.75 601.3 237.8 2.39 550.1 239.7 2.17  

8 684.6 179.4 3.55 672.1 200.1 3.15 657.8 222.0 2.79 615.1 238.3 2.44 555.2 234.4 2.2410 721.2 185.6 3.62 707.7 206.4 3.22 689.8 227.8 2.86 643.3 239.8 2.54 566.5 224.6 2.38  

12 759.1 191.4 3.70 744.4 212.9 3.29 720.1 232.3 2.93 671.5 244.7 2.60 577.7 215.6 2.5215 818.3 198.2 3.87 802.0 222.6 3.40 766.7 238.6 3.04 715.0 250.9 2.70 590.2 205.3 2.70  

15.5 828.4 199.4 3.89 811.8 224.1 3.42 774.7 239.7 3.06 722.4 251.9 2.72 592.0 203.5 2.73  

4.5 671.8 186.0 3.37 658.6 210.5 2.94 637.8 236.6 2.55 599.8 253.8 2.24 498.1 217.3 2.165 681.0 187.5 3.39 667.6 211.0 2.97 645.8 236.8 2.58 606.7 253.9 2.27 500.7 215.1 2.19  

6 699.8 190.5 3.43 685.6 214.4 3.01 662.0 237.2 2.64 620.7 254.1 2.32 507.6 215.6 2.227 719.0 193.5 3.47 704.0 218.1 3.04 678.5 237.5 2.70 635.0 254.1 2.37 510.8 206.2 2.32  

8 738.4 196.8 3.51 722.8 221.4 3.08 695.0 239.8 2.74 649.4 254.0 2.43 515.8 201.9 2.4010 778.6 203.5 3.59 761.2 227.7 3.16 728.8 245.3 2.82 676.2 253.2 2.54 524.4 192.7 2.54  

12 820.2 209.4 3.68 798.1 232.5 3.24 762.1 248.8 2.91 686.3 244.1 2.66 532.9 184.5 2.6915 885.6 217.9 3.83 855.7 239.1 3.39 811.8 253.3 3.04 700.7 231.5 2.86 543.2 174.8 2.88  

15.5 896.7 219.5 3.85 865.5 239.9 3.42 820.2 254.1 3.07 702.9 229.7 2.89 544.9 173.2 2.92

4.5 729.6 196.7 3.45 716.0 220.6 3.04 700.4 250.5 2.64 659.2 268.6 2.32 622.2 279.8 2.115 739.8 198.6 3.46 725.7 221.4 3.07 709.8 251.3 2.67 666.8 268.8 2.35 624.8 277.2 2.14  

6 760.3 202.0 3.50 745.5 224.8 3.11 729.0 253.0 2.72 682.2 269.1 2.40 630.1 272.0 2.207 781.2 205.5 3.54 765.8 229.2 3.14 748.4 254.8 2.77 698.0 269.3 2.45 635.6 266.6 2.26  

8 802.4 209.0 3.58 786.4 233.0 3.17 767.0 257.3 2.82 714.0 269.5 2.51 641.5 261.0 2.3210 846.2 216.5 3.65 828.7 240.6 3.24 801.5 262.6 2.89 746.5 270.9 2.61 653.5 249.2 2.47  

12 891.6 222.9 3.75 872.6 248.4 3.31 836.9 266.8 2.97 779.3 276.0 2.68 0.0 0.0 0.0015 962.0 231.2 3.91 940.9 259.6 3.43 892.0 272.8 3.10 830.5 281.4 2.80 677.5 225.8 2.81

15.5 974.1 232.8 3.93 952.7 261.0 3.45 901.3 273.7 3.12 839.0 282.4 2.82 678.9 223.6 2.85  

4.5 800.6 215.6 3.45 786.1 241.9 3.04 769.5 274.1 2.65 731.3 298.0 2.33 683.4 305.3 2.125 811.6 217.8 3.46 796.8 242.9 3.07 779.8 275.1 2.67 740.0 298.4 2.35 686.8 302.5 2.15  

6 833.9 221.8 3.50 818.5 246.0 3.12 800.8 277.0 2.73 757.6 299.2 2.40 693.4 296.5 2.227 856.6 225.7 3.54 840.4 250.9 3.14 822.1 279.1 2.78 775.6 300.1 2.45 699.6 290.1 2.28  

8 879.7 229.7 3.57 862.8 255.4 3.17 842.9 281.5 2.83 794.0 300.8 2.50 705.4 283.2 2.3510 927.2 238.0 3.64 908.8 264.0 3.24 882.0 288.8 2.89 831.2 302.9 2.60 714.8 268.6 2.51

12 976.2 245.6 3.72 956.5 272.7 3.31 922.4 294.7 2.96 868.8 310.0 2.66 725.0 255.8 2.6615 1052.5 253.8 3.89 1030.7 285.0 3.42 984.8 303.3 3.08 927.6 318.4 2.77 736.9 242.7 2.84  

15.5 1065.5 255.4 3.92 1043.3 286.5 3.44 996.4 304.2 3.11 937.5 319.8 2.79 739.0 240.5 2.88

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

YCIV

0840

YCIV

0920

YCIV

0600

YCIV

0650

YCIV

0720

YCIV

0770

   L   W   T   °   C

Modelo

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 530.4 146.2 3.35 516.9 162.3 2.97 502.0 178.7 2.63 484.1 195.9 2.33 467.1 214.4 2.065 538.3 146.5 3.40 524.5 162.6 3.00 509.3 179.3 2.66 491.1 196.6 2.35 474.0 215.6 2.08  

6 554.2 147.1 3.48 539.8 163.5 3.08 523.9 180.5 2.72 505.3 198.0 2.41 487.9 218.1 2.127 570.5 147.9 3.57 555.4 164.4 3.15 538.6 181.8 2.78 519.6 199.7 2.45 502.0 220.5 2.16  

8 587.0 148.7 3.65 571.2 165.4 3.22 553.7 183.0 2.84 534.0 201.2 2.50 507.3 215.6 2.2310 620.6 150.8 3.81 603.6 167.9 3.36 584.5 185.9 2.95 563.6 204.5 2.60 517.7 205.3 2.38  

12 655.3 153.2 3.97 637.0 170.6 3.49 616.6 188.9 3.07 594.5 208.0 2.70 527.2 194.9 2.5515 709.7 157.0 4.20 689.4 174.9 3.69 667.3 193.4 3.25 644.3 213.8 2.85 541.6 181.9 2.79  

15.5 719.0 157.8 4.24 698.5 175.7 3.72 676.0 194.2 3.28 653.0 214.9 2.88 543.9 179.8 2.84  

4.5 571.9 158.2 3.36 560.2 178.2 2.95 542.9 199.1 2.57 511.5 214.2 2.26 436.2 194.4 2.115  579.8 159.7 3.38 568.0 178.8 2.98 550.0 199.5 2.60 517.6 214.5 2.28 438.5 192.4 2.15  

6 595.9 162.4 3.42 583.8 181.2 3.02 564.1 200.2 2.66 529.9 215.3 2.33 443.1 188.4 2.217 612.2 165.1 3.46 599.6 184.7 3.05 578.5 200.8 2.72 542.6 215.9 2.38 447.5 184.5 2.28  

8 628.7 167.8 3.50 615.8 187.8 3.08 593.0 202.4 2.77 555.5 216.5 2.43 451.8 180.5 2.3510 662.4 173.3 3.57 648.9 193.7 3.15 622.1 207.7 2.83 581.6 218.3 2.53 459.2 172.2 2.49  

12 696.9 178.2 3.66 682.5 199.3 3.23 652.3 211.9 2.91 602.0 219.2 2.60 466.9 165.0 2.6415 750.2 183.8 3.83 730.2 205.0 3.37 697.3 217.8 3.03 615.4 208.0 2.80 475.9 156.2 2.83  

15.5 759.3 184.8 3.86 738.4 205.4 3.40 704.5 218.7 3.05 617.4 206.2 2.83 477.4 154.7 2.86

4.5 623.2 168.7 3.42 612.3 190.5 3.00 599.8 216.3 2.61 567.6 236.4 2.27 540.1 254.2 2.025 631.8 170.4 3.44 620.6 191.2 3.03 607.8 217.0 2.64 574.3 236.7 2.30 541.8 251.1 2.05  

6 649.1 173.6 3.47 637.6 193.3 3.08 624.2 218.4 2.69 587.7 237.2 2.34 545.6 245.2 2.117 666.7 176.5 3.51 654.7 196.7 3.11 640.9 219.9 2.75 601.3 237.8 2.39 550.1 239.7 2.17  

8 684.6 179.4 3.55 672.1 200.1 3.15 657.8 222.0 2.79 615.1 238.3 2.44 555.2 234.4 2.2410 721.2 185.6 3.62 707.7 206.4 3.22 689.8 227.8 2.86 643.3 239.8 2.54 566.5 224.6 2.38  

12 759.1 191.4 3.70 744.4 212.9 3.29 720.1 232.3 2.93 671.5 244.7 2.60 577.7 215.6 2.5215 818.3 198.2 3.87 802.0 222.6 3.40 766.7 238.6 3.04 715.0 250.9 2.70 590.2 205.3 2.70  

15.5 828.4 199.4 3.89 811.8 224.1 3.42 774.7 239.7 3.06 722.4 251.9 2.72 592.0 203.5 2.73  

4.5 671.8 186.0 3.37 658.6 210.5 2.94 637.8 236.6 2.55 599.8 253.8 2.24 498.1 217.3 2.165 681.0 187.5 3.39 667.6 211.0 2.97 645.8 236.8 2.58 606.7 253.9 2.27 500.7 215.1 2.19  

6 699.8 190.5 3.43 685.6 214.4 3.01 662.0 237.2 2.64 620.7 254.1 2.32 507.6 215.6 2.227 719.0 193.5 3.47 704.0 218.1 3.04 678.5 237.5 2.70 635.0 254.1 2.37 510.8 206.2 2.32  

8 738.4 196.8 3.51 722.8 221.4 3.08 695.0 239.8 2.74 649.4 254.0 2.43 515.8 201.9 2.4010 778.6 203.5 3.59 761.2 227.7 3.16 728.8 245.3 2.82 676.2 253.2 2.54 524.4 192.7 2.54  

12 820.2 209.4 3.68 798.1 232.5 3.24 762.1 248.8 2.91 686.3 244.1 2.66 532.9 184.5 2.6915 885.6 217.9 3.83 855.7 239.1 3.39 811.8 253.3 3.04 700.7 231.5 2.86 543.2 174.8 2.88  

15.5 896.7 219.5 3.85 865.5 239.9 3.42 820.2 254.1 3.07 702.9 229.7 2.89 544.9 173.2 2.92

4.5 729.6 196.7 3.45 716.0 220.6 3.04 700.4 250.5 2.64 659.2 268.6 2.32 622.2 279.8 2.115 739.8 198.6 3.46 725.7 221.4 3.07 709.8 251.3 2.67 666.8 268.8 2.35 624.8 277.2 2.14  

6 760.3 202.0 3.50 745.5 224.8 3.11 729.0 253.0 2.72 682.2 269.1 2.40 630.1 272.0 2.207 781.2 205.5 3.54 765.8 229.2 3.14 748.4 254.8 2.77 698.0 269.3 2.45 635.6 266.6 2.26  

8 802.4 209.0 3.58 786.4 233.0 3.17 767.0 257.3 2.82 714.0 269.5 2.51 641.5 261.0 2.3210 846.2 216.5 3.65 828.7 240.6 3.24 801.5 262.6 2.89 746.5 270.9 2.61 653.5 249.2 2.47  

12 891.6 222.9 3.75 872.6 248.4 3.31 836.9 266.8 2.97 779.3 276.0 2.68 0.0 0.0 0.0015 962.0 231.2 3.91 940.9 259.6 3.43 892.0 272.8 3.10 830.5 281.4 2.80 677.5 225.8 2.81

15.5 974.1 232.8 3.93 952.7 261.0 3.45 901.3 273.7 3.12 839.0 282.4 2.82 678.9 223.6 2.85  

4.5 800.6 215.6 3.45 786.1 241.9 3.04 769.5 274.1 2.65 731.3 298.0 2.33 683.4 305.3 2.125 811.6 217.8 3.46 796.8 242.9 3.07 779.8 275.1 2.67 740.0 298.4 2.35 686.8 302.5 2.15  

6 833.9 221.8 3.50 818.5 246.0 3.12 800.8 277.0 2.73 757.6 299.2 2.40 693.4 296.5 2.227 856.6 225.7 3.54 840.4 250.9 3.14 822.1 279.1 2.78 775.6 300.1 2.45 699.6 290.1 2.28  

8 879.7 229.7 3.57 862.8 255.4 3.17 842.9 281.5 2.83 794.0 300.8 2.50 705.4 283.2 2.3510 927.2 238.0 3.64 908.8 264.0 3.24 882.0 288.8 2.89 831.2 302.9 2.60 714.8 268.6 2.51

12 976.2 245.6 3.72 956.5 272.7 3.31 922.4 294.7 2.96 868.8 310.0 2.66 725.0 255.8 2.6615 1052.5 253.8 3.89 1030.7 285.0 3.42 984.8 303.3 3.08 927.6 318.4 2.77 736.9 242.7 2.84  

15.5 1065.5 255.4 3.92 1043.3 286.5 3.44 996.4 304.2 3.11 937.5 319.8 2.79 739.0 240.5 2.88

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

YCIV

0840

YCIV

0920

YCIV

0600

YCIV

0650

YCIV

0720

YCIV

0770

   L   W   T   °   C

Modelo

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 31/72

 

31

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Rendimiento Estándar (SE LS) con Ventiladores de Dos Velocidades - Capacidades Frigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 871.9 234.3 3.46 856.5 263.1 3.05 838.8 297.5 2.66 803.6 326.9 2.33 755.1 337.0 2.135 883.8 236.8 3.47 868.2 264.1 3.08 850.0 298.5 2.69 813.4 327.6 2.35 758.5 333.5 2.16  

6 907.9 241.4 3.50 891.6 267.0 3.13 872.8 300.8 2.74 833.3 329.0 2.40 765.6 326.3 2.227 932.4 245.8 3.53 915.4 272.5 3.15 895.9 303.1 2.79 853.5 330.5 2.45 772.9 319.0 2.29  

8 957.3 250.2 3.57 939.6 277.6 3.18 919.0 305.5 2.84 874.1 331.8 2.50 779.9 311.8 2.36

10 1008.4 259.2 3.64 989.2 287.1 3.24 962.8 314.8 2.89 916.3 334.5 2.60 792.5 298.0 2.5112 1061.2 268.0 3.71 1040.5 296.7 3.31 1008.1 322.2 2.96 958.6 343.7 2.65 805.3 284.9 2.6615 1143.3 276.2 3.89 1120.7 310.1 3.42 1077.9 333.4 3.07 1025.0 355.0 2.75 819.0 270.6 2.84  

15.5 1157.2 277.7 3.91 1134.2 311.7 3.44 1091.7 334.3 3.10 1036.3 356.8 2.77 821.5 268.1 2.87  

4.5 925.7 247.8 3.46 907.4 281.8 3.01 881.7 317.3 2.62 833.9 344.3 2.29 701.4 304.7 2.165 938.5 250.2 3.48 919.9 282.7 3.04 893.1 317.8 2.65 843.8 344.7 2.32 705.3 301.8 2.20  

6 964.5 254.6 3.52 945.3 284.7 3.11 916.4 319.0 2.71 863.6 345.5 2.37 712.6 295.8 2.267 991.1 258.7 3.56 971.1 289.7 3.14 940.1 320.0 2.77 884.0 346.0 2.42 719.9 289.7 2.33  

8 1018.1 262.9 3.60 997.3 294.8 3.17 964.4 321.3 2.83 904.7 346.5 2.47 727.0 283.6 2.4010 1073.5 271.7 3.69 1051.3 303.8 3.25 1013.1 329.9 2.90 947.0 347.3 2.58 738.8 270.8 2.55  

12 1130.8 280.6 3.77 1105.2 311.8 3.34 1063.5 337.2 2.98 970.4 341.0 2.69 751.7 258.8 2.7015 1220.4 290.6 3.94 1187.1 323.0 3.47 1135.6 345.4 3.11 993.2 324.3 2.89 766.9 245.4 2.90  

15.5 1235.7 292.5 3.96 1201.2 324.3 3.49 1147.6 346.7 3.13 995.7 321.4 2.92 769.3 243.1 2.93

4.5 1028.7 275.5 3.47 1009.1 313.6 3.02 981.0 354.4 2.61 926.3 382.7 2.29 766.9 326.6 2.21

5 1042.9 278.1 3.49 1022.9 314.3 3.05 993.6 354.9 2.64 936.9 382.9 2.32 770.8 323.4 2.24  6 1071.7 282.6 3.53 1050.8 317.4 3.10 1019.1 355.8 2.70 958.6 383.1 2.37 778.7 316.8 2.307 1101.1 287.1 3.57 1079.0 323.1 3.14 1045.1 356.6 2.77 980.7 383.1 2.43 786.6 310.3 2.37  

8 1131.0 291.8 3.62 1107.9 328.1 3.17 1071.4 358.6 2.82 1003.1 383.0 2.48 794.3 303.7 2.4510 1192.6 301.8 3.70 1167.0 337.3 3.26 1125.1 368.2 2.89 1043.3 379.0 2.61 807.4 289.9 2.60  

12 1256.7 311.2 3.78 1225.4 345.4 3.34 1177.1 373.7 2.98 1058.8 365.6 2.74 821.6 277.3 2.7515 1357.2 323.7 3.94 1316.7 357.7 3.48 1254.3 380.6 3.12 1081.6 346.9 2.94 837.3 262.8 2.95  

15.5 1374.4 326.1 3.96 1332.5 359.0 3.51 1267.5 381.8 3.15 1085.2 344.3 2.97 839.9 260.4 2.99  

4.5 1161.7 311.2 3.47 1140.5 351.2 3.04 1116.4 398.2 2.64 1059.1 431.7 2.32 993.6 444.8 2.125 1177.7 314.5 3.48 1156.1 352.4 3.07 1131.3 399.5 2.67 1071.6 432.3 2.35 998.6 441.3 2.15  

6 1210.2 320.4 3.51 1187.6 355.9 3.13 1161.7 402.3 2.73 1096.8 433.3 2.40 1008.5 433.3 2.217 1243.3 326.1 3.55 1219.6 362.6 3.15 1192.7 405.2 2.78 1122.7 434.2 2.45 1017.8 424.5 2.27  

8 1277.1 331.8 3.59 1252.3 369.3 3.18 1224.3 408.4 2.83 1148.9 435.2 2.50 1026.5 414.9 2.3410 1346.5 343.8 3.66 1319.5 381.7 3.25 1280.9 418.2 2.90 1202.6 436.9 2.61 1039.3 392.9 2.49  

12 1418.5 355.4 3.74 1389.3 394.2 3.32 1339.1 426.4 2.97 1256.8 446.0 2.67 1053.4 372.5 2.6615 1530.3 367.6 3.91 1497.9 412.7 3.43 1429.4 438.0 3.09 1341.3 457.6 2.79 1070.9 353.1 2.84  

15.5 1549.4 369.9 3.93 1516.5 415.2 3.45 1444.6 439.9 3.11 1355.7 459.4 2.80 1073.9 349.8 2.87

4.5 1303.8 348.4 3.47 1280.8 393.4 3.05 1254.6 444.9 2.66 1203.1 489.6 2.33 1137.3 509.7 2.125 1321.7 352.2 3.49 1298.3 394.9 3.08 1271.4 446.5 2.68 1217.8 490.6 2.35 1142.5 504.5 2.15  

6 1358.0 359.5 3.51 1333.7 398.0 3.14 1305.4 449.8 2.74 1247.5 492.7 2.40 1153.0 493.8 2.217 1394.9 366.2 3.55 1369.5 405.5 3.17 1340.2 453.2 2.79 1277.8 494.7 2.45 1163.7 482.9 2.28  

8 1432.7 372.8 3.58 1406.0 413.7 3.19 1375.7 456.7 2.84 1308.5 496.9 2.50 1174.5 472.0 2.3510 1510.1 386.4 3.65 1481.1 428.1 3.25 1442.4 469.5 2.91 1371.9 500.9 2.60 1193.7 451.2 2.50  

12 1590.2 400.6 3.72 1559.0 442.5 3.32 1510.9 481.2 2.97 1436.4 512.6 2.66 1213.3 431.4 2.6515 1712.6 412.4 3.90 1679.0 462.5 3.43 1616.7 498.2 3.08 1536.4 530.4 2.76 1234.9 409.1 2.83  

15.5 1733.2 414.9 3.92 1699.1 465.7 3.45 1634.3 500.9 3.10 1553.6 533.1 2.77 1238.6 405.4 2.86  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.

EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

YCIV

1000

YCIV

1070

YCIV

1180

YCIV

1340

YCIV

1500

Modelo

   L   W   T   °   C

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 871.9 234.3 3.46 856.5 263.1 3.05 838.8 297.5 2.66 803.6 326.9 2.33 755.1 337.0 2.135 883.8 236.8 3.47 868.2 264.1 3.08 850.0 298.5 2.69 813.4 327.6 2.35 758.5 333.5 2.16  

6 907.9 241.4 3.50 891.6 267.0 3.13 872.8 300.8 2.74 833.3 329.0 2.40 765.6 326.3 2.227 932.4 245.8 3.53 915.4 272.5 3.15 895.9 303.1 2.79 853.5 330.5 2.45 772.9 319.0 2.29  

8 957.3 250.2 3.57 939.6 277.6 3.18 919.0 305.5 2.84 874.1 331.8 2.50 779.9 311.8 2.36

10 1008.4 259.2 3.64 989.2 287.1 3.24 962.8 314.8 2.89 916.3 334.5 2.60 792.5 298.0 2.5112 1061.2 268.0 3.71 1040.5 296.7 3.31 1008.1 322.2 2.96 958.6 343.7 2.65 805.3 284.9 2.6615 1143.3 276.2 3.89 1120.7 310.1 3.42 1077.9 333.4 3.07 1025.0 355.0 2.75 819.0 270.6 2.84  

15.5 1157.2 277.7 3.91 1134.2 311.7 3.44 1091.7 334.3 3.10 1036.3 356.8 2.77 821.5 268.1 2.87  

4.5 925.7 247.8 3.46 907.4 281.8 3.01 881.7 317.3 2.62 833.9 344.3 2.29 701.4 304.7 2.165 938.5 250.2 3.48 919.9 282.7 3.04 893.1 317.8 2.65 843.8 344.7 2.32 705.3 301.8 2.20  

6 964.5 254.6 3.52 945.3 284.7 3.11 916.4 319.0 2.71 863.6 345.5 2.37 712.6 295.8 2.267 991.1 258.7 3.56 971.1 289.7 3.14 940.1 320.0 2.77 884.0 346.0 2.42 719.9 289.7 2.33  

8 1018.1 262.9 3.60 997.3 294.8 3.17 964.4 321.3 2.83 904.7 346.5 2.47 727.0 283.6 2.4010 1073.5 271.7 3.69 1051.3 303.8 3.25 1013.1 329.9 2.90 947.0 347.3 2.58 738.8 270.8 2.55  

12 1130.8 280.6 3.77 1105.2 311.8 3.34 1063.5 337.2 2.98 970.4 341.0 2.69 751.7 258.8 2.7015 1220.4 290.6 3.94 1187.1 323.0 3.47 1135.6 345.4 3.11 993.2 324.3 2.89 766.9 245.4 2.90  

15.5 1235.7 292.5 3.96 1201.2 324.3 3.49 1147.6 346.7 3.13 995.7 321.4 2.92 769.3 243.1 2.93

4.5 1028.7 275.5 3.47 1009.1 313.6 3.02 981.0 354.4 2.61 926.3 382.7 2.29 766.9 326.6 2.21

5 1042.9 278.1 3.49 1022.9 314.3 3.05 993.6 354.9 2.64 936.9 382.9 2.32 770.8 323.4 2.24  6 1071.7 282.6 3.53 1050.8 317.4 3.10 1019.1 355.8 2.70 958.6 383.1 2.37 778.7 316.8 2.307 1101.1 287.1 3.57 1079.0 323.1 3.14 1045.1 356.6 2.77 980.7 383.1 2.43 786.6 310.3 2.37  

8 1131.0 291.8 3.62 1107.9 328.1 3.17 1071.4 358.6 2.82 1003.1 383.0 2.48 794.3 303.7 2.4510 1192.6 301.8 3.70 1167.0 337.3 3.26 1125.1 368.2 2.89 1043.3 379.0 2.61 807.4 289.9 2.60  

12 1256.7 311.2 3.78 1225.4 345.4 3.34 1177.1 373.7 2.98 1058.8 365.6 2.74 821.6 277.3 2.7515 1357.2 323.7 3.94 1316.7 357.7 3.48 1254.3 380.6 3.12 1081.6 346.9 2.94 837.3 262.8 2.95  

15.5 1374.4 326.1 3.96 1332.5 359.0 3.51 1267.5 381.8 3.15 1085.2 344.3 2.97 839.9 260.4 2.99  

4.5 1161.7 311.2 3.47 1140.5 351.2 3.04 1116.4 398.2 2.64 1059.1 431.7 2.32 993.6 444.8 2.125 1177.7 314.5 3.48 1156.1 352.4 3.07 1131.3 399.5 2.67 1071.6 432.3 2.35 998.6 441.3 2.15  

6 1210.2 320.4 3.51 1187.6 355.9 3.13 1161.7 402.3 2.73 1096.8 433.3 2.40 1008.5 433.3 2.217 1243.3 326.1 3.55 1219.6 362.6 3.15 1192.7 405.2 2.78 1122.7 434.2 2.45 1017.8 424.5 2.27  

8 1277.1 331.8 3.59 1252.3 369.3 3.18 1224.3 408.4 2.83 1148.9 435.2 2.50 1026.5 414.9 2.3410 1346.5 343.8 3.66 1319.5 381.7 3.25 1280.9 418.2 2.90 1202.6 436.9 2.61 1039.3 392.9 2.49  

12 1418.5 355.4 3.74 1389.3 394.2 3.32 1339.1 426.4 2.97 1256.8 446.0 2.67 1053.4 372.5 2.6615 1530.3 367.6 3.91 1497.9 412.7 3.43 1429.4 438.0 3.09 1341.3 457.6 2.79 1070.9 353.1 2.84  

15.5 1549.4 369.9 3.93 1516.5 415.2 3.45 1444.6 439.9 3.11 1355.7 459.4 2.80 1073.9 349.8 2.87

4.5 1303.8 348.4 3.47 1280.8 393.4 3.05 1254.6 444.9 2.66 1203.1 489.6 2.33 1137.3 509.7 2.125 1321.7 352.2 3.49 1298.3 394.9 3.08 1271.4 446.5 2.68 1217.8 490.6 2.35 1142.5 504.5 2.15  

6 1358.0 359.5 3.51 1333.7 398.0 3.14 1305.4 449.8 2.74 1247.5 492.7 2.40 1153.0 493.8 2.217 1394.9 366.2 3.55 1369.5 405.5 3.17 1340.2 453.2 2.79 1277.8 494.7 2.45 1163.7 482.9 2.28  

8 1432.7 372.8 3.58 1406.0 413.7 3.19 1375.7 456.7 2.84 1308.5 496.9 2.50 1174.5 472.0 2.3510 1510.1 386.4 3.65 1481.1 428.1 3.25 1442.4 469.5 2.91 1371.9 500.9 2.60 1193.7 451.2 2.50  

12 1590.2 400.6 3.72 1559.0 442.5 3.32 1510.9 481.2 2.97 1436.4 512.6 2.66 1213.3 431.4 2.6515 1712.6 412.4 3.90 1679.0 462.5 3.43 1616.7 498.2 3.08 1536.4 530.4 2.76 1234.9 409.1 2.83  

15.5 1733.2 414.9 3.92 1699.1 465.7 3.45 1634.3 500.9 3.10 1553.6 533.1 2.77 1238.6 405.4 2.86  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.

EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

YCIV

1000

YCIV

1070

YCIV

1180

YCIV

1340

YCIV

1500

Modelo

   L   W   T   °   C

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 32/72

 

32

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE RENDIMIENTO ESTÁNDAR (SE LS) CON VENTILADORES DE DOS VELOCIDADES(VELOCIDAD ALTA INHIBIDA) - CAPACIDADES FRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 520.5 158.1 3.12 505.7 174.8 2.75 488.4 191.9 2.43 470.1 208.9 2.165 527.9 158.7 3.15 513.1 175.5 2.78 495.3 192.7 2.46 476.7 210.1 2.18  

6 543.1 159.8 3.22 527.5 176.9 2.84 509.1 194.6 2.50 490.5 213.1 2.217 558.5 161.0 3.29 542.1 178.5 2.89 523.1 196.5 2.55 504.6 216.1 2.24  

8 574.1 162.4 3.35 556.8 180.1 2.95 537.2 198.4 2.59 518.9 219.3 2.2810 605.9 165.6 3.47 586.8 183.8 3.05 565.9 202.4 2.68 533.9 213.1 2.41

12 638.5 169.2 3.59 618.0 187.7 3.15 595.8 206.8 2.76 544.9 202.6 2.5815 689.6 174.7 3.76 667.4 193.3 3.30 644.2 213.9 2.89 559.5 188.3 2.84  

15.5 698.5 175.7 3.79 675.9 194.4 3.33 652.7 215.4 2.91 561.8 186.1 2.88  

4.5 560.9 180.4 2.97 543.0 197.8 2.63 517.0 212.1 2.34 452.3 202.4 2.145  568.5 182.4 2.97 549.8 198.4 2.65 522.8 212.6 2.36 455.0 200.6 2.17  

6 583.8 186.1 3.00 563.2 201.1 2.68 534.7 213.5 2.41 459.8 196.7 2.247 599.3 189.8 3.02 576.7 204.4 2.71 546.8 214.3 2.45 465.1 193.0 2.30  

8 615.1 193.4 3.04 590.2 207.2 2.73 558.7 216.8 2.48 469.8 189.0 2.3810 646.6 200.3 3.09 618.1 212.4 2.79 582.5 222.5 2.52 477.3 182.0 2.50  

12 676.5 203.7 3.18 646.7 217.5 2.86 594.7 217.1 2.63 483.0 176.0 2.6115 722.6 207.2 3.35 688.7 223.0 2.97 607.8 206.3 2.83 491.9 166.3 2.81

15.5 730.4 207.8 3.37 695.5 223.4 2.99 609.5 204.5 2.86 493.4 164.7 2.84

4.5 613.5 190.4 3.06 600.9 214.0 2.68 574.0 233.9 2.35 534.0 248.7 2.065 621.6 192.5 3.07 608.8 215.0 2.71 580.4 234.3 2.38 539.8 249.1 2.08  

6 638.3 196.5 3.09 624.9 218.2 2.74 593.4 235.1 2.42 551.5 250.0 2.127 655.2 200.2 3.12 641.1 222.9 2.75 606.5 235.8 2.47 563.4 250.9 2.16  

8 672.2 204.1 3.14 657.5 227.4 2.77 619.4 237.7 2.50 572.8 249.3 2.2110 707.1 211.9 3.19 687.3 233.1 2.83 645.2 244.0 2.54 582.3 238.2 2.35  

12 743.1 218.8 3.25 715.6 238.2 2.88 671.9 248.9 2.60 590.5 229.9 2.4615 799.4 226.8 3.38 759.3 244.7 2.98 712.5 256.0 2.68 603.8 217.8 2.65  

15.5 808.9 228.3 3.40 766.8 245.2 3.01 719.3 257.2 2.69 605.7 215.9 2.68  

4.5 658.5 214.9 2.93 636.7 235.4 2.60 604.1 252.6 2.30 517.5 228.8 2.175 667.2 216.9 2.94 644.4 235.9 2.62 610.7 252.8 2.32 520.2 226.4 2.20  

6 684.8 220.9 2.97 659.5 239.7 2.64 624.1 253.1 2.37 525.4 221.5 2.277 702.8 224.9 2.99 674.8 243.3 2.66 637.7 253.3 2.42 530.8 216.7 2.34  

8 720.7 228.7 3.02 690.6 246.2 2.70 650.8 255.9 2.45 535.8 212.1 2.4110 754.8 234.5 3.09 722.9 252.0 2.76 666.7 251.9 2.55 543.9 204.2 2.54  

12 790.2 237.9 3.19 753.3 255.9 2.83 677.5 242.6 2.68 550.7 197.7 2.6515 845.4 242.7 3.35 799.8 259.1 2.97 691.7 230.9 2.87 561.0 186.8 2.85  

15.5 854.7 243.7 3.37 807.8 259.2 3.00 693.7 229.1 2.90 562.7 185.1 2.89

4.5 716.7 223.1 3.06 701.2 249.0 2.70 665.2 267.0 2.39 618.6 278.5 2.145 726.3 225.4 3.07 710.4 250.3 2.72 672.6 267.3 2.42 625.3 278.8 2.16  

6 745.8 229.8 3.10 729.0 255.4 2.74 687.5 267.7 2.47 638.7 279.4 2.207 765.7 234.3 3.12 747.8 261.1 2.75 702.4 268.2 2.52 652.6 279.9 2.24  

8 785.8 238.8 3.15 764.2 263.9 2.78 717.2 270.8 2.54 658.5 274.4 2.3110 827.0 248.3 3.19 796.7 268.9 2.85 747.2 276.6 2.60 669.3 263.9 2.44  

12 870.0 255.6 3.26 829.7 273.7 2.91 778.2 281.1 2.66 678.7 254.3 2.5615 936.5 265.7 3.39 881.2 278.5 3.04 825.7 287.4 2.77 692.5 239.5 2.76  

15.5 946.6 266.7 3.41 890.1 278.8 3.07 833.8 288.4 2.79 694.6 237.4 2.80  

4.5 787.1 243.7 3.08 770.4 272.4 2.71 736.7 295.6 2.39 693.1 314.3 2.12

5 797.6 246.5 3.08 780.5 273.8 2.73 745.1 296.2 2.42 700.0 314.3 2.14  6 818.8 251.5 3.11 800.9 278.6 2.76 762.3 297.3 2.46 707.3 309.0 2.207 840.3 256.6 3.13 821.5 284.9 2.77 779.4 298.6 2.51 714.7 303.2 2.27  

8 862.3 261.7 3.15 840.4 289.2 2.79 796.7 301.3 2.54 721.8 296.9 2.3410  907.2 272.2 3.19 877.5 296.2 2.85 831.4 309.6 2.58 734.0 284.2 2.48  

12 953.7 281.0 3.25 915.5 303.0 2.91 867.0 316.3 2.64 741.4 273.1 2.6015 1025.9 291.9 3.37 974.4 311.4 3.01 915.9 320.4 2.75 753.1 257.5 2.79  

15.5 1037.9 292.8 3.40 984.5 312.1 3.04 919.2 316.6 2.80 755.3 255.2 2.83

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Tem eratura de Salida del A ua

Modelo

YCIV

0600

YCIV

0650

YCIV

0720

YCIV

0770

YCIV

0840

YCIV

0920

   L   W   T   °   C

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 520.5 158.1 3.12 505.7 174.8 2.75 488.4 191.9 2.43 470.1 208.9 2.165 527.9 158.7 3.15 513.1 175.5 2.78 495.3 192.7 2.46 476.7 210.1 2.18  

6 543.1 159.8 3.22 527.5 176.9 2.84 509.1 194.6 2.50 490.5 213.1 2.217 558.5 161.0 3.29 542.1 178.5 2.89 523.1 196.5 2.55 504.6 216.1 2.24  

8 574.1 162.4 3.35 556.8 180.1 2.95 537.2 198.4 2.59 518.9 219.3 2.2810 605.9 165.6 3.47 586.8 183.8 3.05 565.9 202.4 2.68 533.9 213.1 2.41

12 638.5 169.2 3.59 618.0 187.7 3.15 595.8 206.8 2.76 544.9 202.6 2.5815 689.6 174.7 3.76 667.4 193.3 3.30 644.2 213.9 2.89 559.5 188.3 2.84  

15.5 698.5 175.7 3.79 675.9 194.4 3.33 652.7 215.4 2.91 561.8 186.1 2.88  

4.5 560.9 180.4 2.97 543.0 197.8 2.63 517.0 212.1 2.34 452.3 202.4 2.145  568.5 182.4 2.97 549.8 198.4 2.65 522.8 212.6 2.36 455.0 200.6 2.17  

6 583.8 186.1 3.00 563.2 201.1 2.68 534.7 213.5 2.41 459.8 196.7 2.247 599.3 189.8 3.02 576.7 204.4 2.71 546.8 214.3 2.45 465.1 193.0 2.30  

8 615.1 193.4 3.04 590.2 207.2 2.73 558.7 216.8 2.48 469.8 189.0 2.3810 646.6 200.3 3.09 618.1 212.4 2.79 582.5 222.5 2.52 477.3 182.0 2.50  

12 676.5 203.7 3.18 646.7 217.5 2.86 594.7 217.1 2.63 483.0 176.0 2.6115 722.6 207.2 3.35 688.7 223.0 2.97 607.8 206.3 2.83 491.9 166.3 2.81

15.5 730.4 207.8 3.37 695.5 223.4 2.99 609.5 204.5 2.86 493.4 164.7 2.84

4.5 613.5 190.4 3.06 600.9 214.0 2.68 574.0 233.9 2.35 534.0 248.7 2.065 621.6 192.5 3.07 608.8 215.0 2.71 580.4 234.3 2.38 539.8 249.1 2.08  

6 638.3 196.5 3.09 624.9 218.2 2.74 593.4 235.1 2.42 551.5 250.0 2.127 655.2 200.2 3.12 641.1 222.9 2.75 606.5 235.8 2.47 563.4 250.9 2.16  

8 672.2 204.1 3.14 657.5 227.4 2.77 619.4 237.7 2.50 572.8 249.3 2.2110 707.1 211.9 3.19 687.3 233.1 2.83 645.2 244.0 2.54 582.3 238.2 2.35  

12 743.1 218.8 3.25 715.6 238.2 2.88 671.9 248.9 2.60 590.5 229.9 2.4615 799.4 226.8 3.38 759.3 244.7 2.98 712.5 256.0 2.68 603.8 217.8 2.65  

15.5 808.9 228.3 3.40 766.8 245.2 3.01 719.3 257.2 2.69 605.7 215.9 2.68  

4.5 658.5 214.9 2.93 636.7 235.4 2.60 604.1 252.6 2.30 517.5 228.8 2.175 667.2 216.9 2.94 644.4 235.9 2.62 610.7 252.8 2.32 520.2 226.4 2.20  

6 684.8 220.9 2.97 659.5 239.7 2.64 624.1 253.1 2.37 525.4 221.5 2.277 702.8 224.9 2.99 674.8 243.3 2.66 637.7 253.3 2.42 530.8 216.7 2.34  

8 720.7 228.7 3.02 690.6 246.2 2.70 650.8 255.9 2.45 535.8 212.1 2.4110 754.8 234.5 3.09 722.9 252.0 2.76 666.7 251.9 2.55 543.9 204.2 2.54  

12 790.2 237.9 3.19 753.3 255.9 2.83 677.5 242.6 2.68 550.7 197.7 2.6515 845.4 242.7 3.35 799.8 259.1 2.97 691.7 230.9 2.87 561.0 186.8 2.85  

15.5 854.7 243.7 3.37 807.8 259.2 3.00 693.7 229.1 2.90 562.7 185.1 2.89

4.5 716.7 223.1 3.06 701.2 249.0 2.70 665.2 267.0 2.39 618.6 278.5 2.145 726.3 225.4 3.07 710.4 250.3 2.72 672.6 267.3 2.42 625.3 278.8 2.16  

6 745.8 229.8 3.10 729.0 255.4 2.74 687.5 267.7 2.47 638.7 279.4 2.207 765.7 234.3 3.12 747.8 261.1 2.75 702.4 268.2 2.52 652.6 279.9 2.24  

8 785.8 238.8 3.15 764.2 263.9 2.78 717.2 270.8 2.54 658.5 274.4 2.3110 827.0 248.3 3.19 796.7 268.9 2.85 747.2 276.6 2.60 669.3 263.9 2.44  

12 870.0 255.6 3.26 829.7 273.7 2.91 778.2 281.1 2.66 678.7 254.3 2.5615 936.5 265.7 3.39 881.2 278.5 3.04 825.7 287.4 2.77 692.5 239.5 2.76  

15.5 946.6 266.7 3.41 890.1 278.8 3.07 833.8 288.4 2.79 694.6 237.4 2.80  

4.5 787.1 243.7 3.08 770.4 272.4 2.71 736.7 295.6 2.39 693.1 314.3 2.12

5 797.6 246.5 3.08 780.5 273.8 2.73 745.1 296.2 2.42 700.0 314.3 2.14  6 818.8 251.5 3.11 800.9 278.6 2.76 762.3 297.3 2.46 707.3 309.0 2.207 840.3 256.6 3.13 821.5 284.9 2.77 779.4 298.6 2.51 714.7 303.2 2.27  

8 862.3 261.7 3.15 840.4 289.2 2.79 796.7 301.3 2.54 721.8 296.9 2.3410  907.2 272.2 3.19 877.5 296.2 2.85 831.4 309.6 2.58 734.0 284.2 2.48  

12 953.7 281.0 3.25 915.5 303.0 2.91 867.0 316.3 2.64 741.4 273.1 2.6015 1025.9 291.9 3.37 974.4 311.4 3.01 915.9 320.4 2.75 753.1 257.5 2.79  

15.5 1037.9 292.8 3.40 984.5 312.1 3.04 919.2 316.6 2.80 755.3 255.2 2.83

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Tem eratura de Salida del A ua

Modelo

YCIV

0600

YCIV

0650

YCIV

0720

YCIV

0770

YCIV

0840

YCIV

0920

   L   W   T   °   C

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 33/72

 

33

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Rendimiento Estándar (SE LS) con Ventiladores de Dos Velocidades (Velocidad Alta Inhibida) - CapacidadesFrigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 857.7 264.2 3.09 839.8 295.6 2.72 808.4 323.9 2.40 767.8 349.7 2.125 869.0 267.4 3.10 850.9 297.1 2.74 817.9 324.8 2.42 776.0 350.2 2.14  

6 892.0 273.0 3.12 873.1 301.6 2.77 837.3 326.6 2.46 783.0 343.1 2.207 915.3 278.8 3.13 895.4 308.6 2.78 856.7 328.5 2.51 790.4 335.7 2.27  

8 939.1 284.4 3.16 916.9 314.1 2.80 876.5 331.5 2.54 797.9 328.2 2.34

10 987.6 295.8 3.20 958.6 323.2 2.85 915.7 342.2 2.58 811.9 313.6 2.48  12 1037.6 306.1 3.25 1001.6 332.0 2.90 956.1 351.2 2.62 821.4 303.4 2.5915 1115.4 317.8 3.37 1067.8 343.8 2.99 1 012.0 358.0 2.73 835.3 287.3 2.78  

15.5 1129.5 318.6 3.40 1079.2 344.9 3.01 1 015.8 354.1 2.77 837.8 284.7 2.81

4.5 908.9 282.2 3.07 882.3 314.0 2.69 843.5 341.0 2.37 729.2 317.9 2.205 921.1 285.4 3.07 893.5 314.8 2.71 852.8 341.6 2.40 733.3 315.0 2.23  

6 945.9 291.2 3.10 916.0 317.4 2.76 872.0 342.6 2.44 741.0 308.8 2.297 971.1 296.7 3.12 938.5 323.1 2.78 891.5 343.5 2.49 749.7 303.0 2.36  

8 996.8 302.2 3.15 961.3 328.3 2.81 911.1 344.9 2.54 757.6 296.9 2.4310 1047.3 311.8 3.21 1008.4 337.4 2.87 944.6 349.5 2.60 771.0 284.8 2.58  

12 1098.0 319.4 3.29 1055.9 345.8 2.93 960.5 337.8 2.73 780.1 276.0 2.6915 1177.5 326.9 3.45 1122.8 354.3 3.05 982.4 321.7 2.92 794.3 261.2 2.88  

15.5 1191.0 328.2 3.48 1134.2 354.8 3.07 985.4 319.2 2.96 796.9 258.7 2.92

4.5 1009.9 316.4 3.04 980.7 351.5 2.67 934.5 380.4 2.36 798.1 343.6 2.22

5 1023.3 319.9 3.05 992.9 352.3 2.70 944.8 380.7 2.39 802.3 340.1 2.26  

6 1050.5 325.7 3.08 1017.3 356.5 2.74 965.6 381.1 2.44 810.1 332.5 2.337 1078.2 331.5 3.11 1041.8 362.8 2.75 986.8 381.3 2.49 818.5 325.4 2.40  

8 1105.9 337.0 3.14 1067.0 368.0 2.78 1007.6 383.6 2.53 827.3 318.8 2.4810 1160.3 346.7 3.20 1118.7 377.7 2.85 1 030.4 376.7 2.63 840.7 306.2 2.61

12 1216.7 354.0 3.29 1166.1 383.8 2.92 1047.3 362.8 2.77 850.9 296.7 2.7315 1305.0 363.1 3.45 1238.5 389.8 3.06 1 070.0 345.7 2.96 866.7 280.5 2.93  

15.5 1320.0 364.7 3.47 1251.0 390.0 3.09 1 073.2 343.1 2.99 869.4 277.9 2.96  

4.5 1142.1 351.8 3.09 1117.9 395.2 2.71 1067.9 428.5 2.39 1001.5 452.8 2.135 1157.3 356.0 3.10 1132.6 397.2 2.73 1 080.0 429.2 2.42 1012.5 453.6 2.15  

6 1188.2 363.4 3.12 1162.3 402.6 2.77 1104.5 430.6 2.46 1027.1 449.3 2.207 1219.7 370.6 3.14 1192.3 411.6 2.78 1 129.3 432.0 2.51 1038.3 441.8 2.26  

8 1251.7 378.0 3.16 1221.2 419.0 2.80 1154.1 434.5 2.55 1049.1 433.5 2.3310 1317.4 393.1 3.21 1274.7 428.6 2.86 1 203.7 445.8 2.60 1068.2 415.0 2.47  

12 1385.4 406.7 3.27 1329.3 437.9 2.92 1255.2 454.9 2.66 1079.1 398.3 2.5915 1491.1 422.5 3.39 1414.1 449.8 3.03 1 332.0 466.0 2.75 1095.2 374.3 2.79  

15.5 1509.3 424.8 3.41 1428.8 450.7 3.05 1336.9 460.5 2.80 1098.2 370.9 2.83

4.5 1282.8 392.4 3.11 1256.4 441.4 2.72 1210.6 484.7 2.40 1150.4 523.2 2.125 1299.9 397.3 3.12 1272.8 443.8 2.75 1 224.9 486.1 2.42 1163.2 524.9 2.14  

6 1334.5 406.2 3.13 1306.3 448.3 2.79 1253.8 488.8 2.47 1179.3 519.0 2.197 1369.7 414.6 3.15 1339.9 458.7 2.80 1 282.9 491.7 2.51 1190.1 508.1 2.25  

8 1405.4 423.3 3.17 1373.5 468.5 2.81 1312.7 494.4 2.55 1201.4 497.0 2.3210 1479.0 440.5 3.21 1436.6 482.2 2.86 1 372.0 510.5 2.59 1223.7 474.2 2.48  

12 1554.8 457.2 3.26 1501.6 495.5 2.91 1433.3 524.0 2.64 1238.6 458.3 2.5915 1671.2 474.7 3.38 1602.0 514.5 3.00 1 525.3 541.6 2.72 1259.5 434.4 2.77  

15.5 1691.8 476.2 3.41 1 619.1 516.2 3.02 1531.1 535.6 2.76 1 263.2 430.5 2.81

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

1180

YCIV

1340

YCIV

1500

YCIV

1070

YCIV

1000

Modelo

   L   W   T   °   C

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 857.7 264.2 3.09 839.8 295.6 2.72 808.4 323.9 2.40 767.8 349.7 2.125 869.0 267.4 3.10 850.9 297.1 2.74 817.9 324.8 2.42 776.0 350.2 2.14  

6 892.0 273.0 3.12 873.1 301.6 2.77 837.3 326.6 2.46 783.0 343.1 2.207 915.3 278.8 3.13 895.4 308.6 2.78 856.7 328.5 2.51 790.4 335.7 2.27  

8 939.1 284.4 3.16 916.9 314.1 2.80 876.5 331.5 2.54 797.9 328.2 2.34

10 987.6 295.8 3.20 958.6 323.2 2.85 915.7 342.2 2.58 811.9 313.6 2.48  12 1037.6 306.1 3.25 1001.6 332.0 2.90 956.1 351.2 2.62 821.4 303.4 2.5915 1115.4 317.8 3.37 1067.8 343.8 2.99 1 012.0 358.0 2.73 835.3 287.3 2.78  

15.5 1129.5 318.6 3.40 1079.2 344.9 3.01 1 015.8 354.1 2.77 837.8 284.7 2.81

4.5 908.9 282.2 3.07 882.3 314.0 2.69 843.5 341.0 2.37 729.2 317.9 2.205 921.1 285.4 3.07 893.5 314.8 2.71 852.8 341.6 2.40 733.3 315.0 2.23  

6 945.9 291.2 3.10 916.0 317.4 2.76 872.0 342.6 2.44 741.0 308.8 2.297 971.1 296.7 3.12 938.5 323.1 2.78 891.5 343.5 2.49 749.7 303.0 2.36  

8 996.8 302.2 3.15 961.3 328.3 2.81 911.1 344.9 2.54 757.6 296.9 2.4310 1047.3 311.8 3.21 1008.4 337.4 2.87 944.6 349.5 2.60 771.0 284.8 2.58  

12 1098.0 319.4 3.29 1055.9 345.8 2.93 960.5 337.8 2.73 780.1 276.0 2.6915 1177.5 326.9 3.45 1122.8 354.3 3.05 982.4 321.7 2.92 794.3 261.2 2.88  

15.5 1191.0 328.2 3.48 1134.2 354.8 3.07 985.4 319.2 2.96 796.9 258.7 2.92

4.5 1009.9 316.4 3.04 980.7 351.5 2.67 934.5 380.4 2.36 798.1 343.6 2.22

5 1023.3 319.9 3.05 992.9 352.3 2.70 944.8 380.7 2.39 802.3 340.1 2.26  

6 1050.5 325.7 3.08 1017.3 356.5 2.74 965.6 381.1 2.44 810.1 332.5 2.337 1078.2 331.5 3.11 1041.8 362.8 2.75 986.8 381.3 2.49 818.5 325.4 2.40  

8 1105.9 337.0 3.14 1067.0 368.0 2.78 1007.6 383.6 2.53 827.3 318.8 2.4810 1160.3 346.7 3.20 1118.7 377.7 2.85 1 030.4 376.7 2.63 840.7 306.2 2.61

12 1216.7 354.0 3.29 1166.1 383.8 2.92 1047.3 362.8 2.77 850.9 296.7 2.7315 1305.0 363.1 3.45 1238.5 389.8 3.06 1 070.0 345.7 2.96 866.7 280.5 2.93  

15.5 1320.0 364.7 3.47 1251.0 390.0 3.09 1 073.2 343.1 2.99 869.4 277.9 2.96  

4.5 1142.1 351.8 3.09 1117.9 395.2 2.71 1067.9 428.5 2.39 1001.5 452.8 2.135 1157.3 356.0 3.10 1132.6 397.2 2.73 1 080.0 429.2 2.42 1012.5 453.6 2.15  

6 1188.2 363.4 3.12 1162.3 402.6 2.77 1104.5 430.6 2.46 1027.1 449.3 2.207 1219.7 370.6 3.14 1192.3 411.6 2.78 1 129.3 432.0 2.51 1038.3 441.8 2.26  

8 1251.7 378.0 3.16 1221.2 419.0 2.80 1154.1 434.5 2.55 1049.1 433.5 2.3310 1317.4 393.1 3.21 1274.7 428.6 2.86 1 203.7 445.8 2.60 1068.2 415.0 2.47  

12 1385.4 406.7 3.27 1329.3 437.9 2.92 1255.2 454.9 2.66 1079.1 398.3 2.5915 1491.1 422.5 3.39 1414.1 449.8 3.03 1 332.0 466.0 2.75 1095.2 374.3 2.79  

15.5 1509.3 424.8 3.41 1428.8 450.7 3.05 1336.9 460.5 2.80 1098.2 370.9 2.83

4.5 1282.8 392.4 3.11 1256.4 441.4 2.72 1210.6 484.7 2.40 1150.4 523.2 2.125 1299.9 397.3 3.12 1272.8 443.8 2.75 1 224.9 486.1 2.42 1163.2 524.9 2.14  

6 1334.5 406.2 3.13 1306.3 448.3 2.79 1253.8 488.8 2.47 1179.3 519.0 2.197 1369.7 414.6 3.15 1339.9 458.7 2.80 1 282.9 491.7 2.51 1190.1 508.1 2.25  

8 1405.4 423.3 3.17 1373.5 468.5 2.81 1312.7 494.4 2.55 1201.4 497.0 2.3210 1479.0 440.5 3.21 1436.6 482.2 2.86 1 372.0 510.5 2.59 1223.7 474.2 2.48  

12 1554.8 457.2 3.26 1501.6 495.5 2.91 1433.3 524.0 2.64 1238.6 458.3 2.5915 1671.2 474.7 3.38 1602.0 514.5 3.00 1 525.3 541.6 2.72 1259.5 434.4 2.77  

15.5 1691.8 476.2 3.41 1 619.1 516.2 3.02 1531.1 535.6 2.76 1 263.2 430.5 2.81

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

1180

YCIV

1340

YCIV

1500

YCIV

1070

YCIV

1000

Modelo

   L   W   T   °   C

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 34/72

 

34

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE ALTO RENDIMIENTO (HE) CON VENTILADORES ESTÁNDAR - CAPACIDADESFRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 531.2 128.6 3.74 517.3 143.0 3.31 499.4 156.8 2.93 479.0 171.1 2.60 456.8 186.3 2.295 539.7 129.1 3.79 525.5 143.4 3.35 507.3 157.3 2.97 486.6 171.7 2.63 464.0 187.0 2.32  

6 557.0 130.1 3.88 542.0 144.3 3.44 523.4 158.5 3.04 501.9 173.1 2.69 478.7 188.4 2.377 574.6 131.1 3.97 558.8 145.3 3.52 539.7 159.7 3.12 517.6 174.6 2.75 493.8 189.9 2.43  

8 592.1 132.1 4.07 575.9 146.3 3.60 556.3 161.0 3.19 533.5 176.0 2.82 509.1 191.6 2.48  

10 627.5 133.8 4.26 610.8 148.6 3.77 590.2 163.9 3.33 566.4 179.1 2.94 541.3 195.7 2.59  12 664.0 135.6 4.45 646.7 151.2 3.93 625.1 167.0 3.47 600.3 182.6 3.06 575.3 200.4 2.69  

15 721.0 138.4 4.75 703.1 154.9 4.18 680.6 171.4 3.68 654.7 187.7 3.26 610.0 196.5 2.91

15.5 730.7 138.9 4.80 712.7 155.6 4.22 690.1 172.2 3.72 664.1 188.5 3.29 611.8 194.0 2.95  

4.5 570.3 136.1 3.77 557.3 152.9 3.32 541.0 169.4 2.93 522.6 186.5 2.59 502.4 203.9 2.295 579.5 136.5 3.82 566.0 153.2 3.36 549.2 169.7 2.97 530.4 187.0 2.62 510.0 204.6 2.32  

6 597.8 137.3 3.92 583.5 153.8 3.45 566.0 170.5 3.05 546.4 188.0 2.69 525.3 206.1 2.377 616.5 138.1 4.02 601.5 154.5 3.55 583.2 171.4 3.13 562.7 189.1 2.76 541.2 207.8 2.43  

8 635.6 139.0 4.12 619.7 155.2 3.64 600.7 172.3 3.21 579.5 190.2 2.82 557.4 209.4 2.4810 675.1 141.3 4.32 657.2 157.2 3.81 636.6 174.6 3.36 613.9 192.8 2.95 591.0 212.9 2.59  

12 716.1 144.0 4.50 696.3 159.6 3.98 674.1 177.1 3.51 650.0 195.5 3.09 607.7 204.8 2.7615 778.8 148.4 4.76 757.1 164.2 4.22 732.9 181.8 3.72 706.9 200.3 3.28 624.9 190.1 3.04  

15.5 789.3 149.3 4.80 767.4 165.1 4.26 743.0 182.6 3.76 716.7 201.2 3.31 626.7 187.7 3.094.5 609.5 144.3 3.78 600.3 163.6 3.33 589.1 186.5 2.90 573.0 211.4 2.51 557.7 233.2 2.23

5 618.0 145.6 3.81 608.7 163.9 3.37 597.4 186.8 2.93 580.5 211.6 2.54 564.5 233.5 2.26  

6 635.3 148.0 3.85 625.8 165.1 3.44 614.1 187.6 3.00 595.6 212.0 2.60 578.3 234.0 2.317 652.9 150.2 3.91 643.2 167.5 3.49 631.1 188.3 3.08 611.1 212.3 2.67 592.5 234.4 2.36  

8 670.5 152.5 3.96 660.8 170.1 3.54 648.5 189.4 3.15 626.9 212.6 2.73 606.9 234.8 2.41

10 706.7 157.3 4.06 696.6 174.7 3.64 683.7 194.5 3.24 659.3 213.3 2.87 636.4 235.3 2.52  

12 744.0 162.3 4.15 733.5 179.6 3.74 720.0 199.5 3.33 692.1 217.2 2.96 666.9 235.7 2.64  

15 802.0 168.2 4.33 791.0 187.4 3.87 776.6 207.0 3.47 742.7 222.7 3.10 691.3 227.8 2.83  

15.5 811.9 169.3 4.36 800.8 188.6 3.90 786.3 208.3 3.49 750.9 223.5 3.12 694.0 225.6 2.86  

4.5 660.4 156.5 3.81 649.7 178.7 3.32 637.3 205.8 2.86 621.6 236.9 2.45 597.9 255.5 2.205 669.6 157.8 3.83 658.7 178.8 3.37 646.1 206.1 2.90 629.2 236.7 2.48 605.1 255.6 2.22  

6 688.4 160.4 3.89 677.1 179.8 3.44 663.9 206.4 2.97 644.7 236.3 2.55 619.6 255.7 2.277 707.5 162.8 3.94 695.7 182.5 3.49 682.1 206.8 3.05 660.5 235.9 2.61 634.4 255.7 2.33  

8 727.1 165.5 3.99 714.8 185.1 3.54 700.7 207.3 3.13 676.3 235.4 2.68 649.5 255.5 2.3910 767.1 171.5 4.07 754.0 190.0 3.65 738.7 213.0 3.22 709.1 234.3 2.82 680.5 254.8 2.51

12 808.7 178.2 4.15 794.6 195.5 3.74 778.2 217.8 3.32 742.1 237.3 2.92 712.4 253.9 2.63

15 873.0 187.2 4.28 857.8 205.3 3.86 840.1 226.1 3.46 793.3 240.9 3.08 761.2 257.9 2.77  

15.5 883.9 188.9 4.30 868.5 206.8 3.88 850.7 227.6 3.48 802.0 241.5 3.11 764.7 255.5 2.814.5 701.9 164.1 3.84 691.1 187.0 3.36 678.8 214.5 2.91 661.3 244.9 2.51 642.8 267.6 2.25

5 711.7 165.6 3.87 700.7 187.2 3.41 688.1 214.8 2.95 669.8 245.0 2.54 650.4 267.8 2.27  

6 731.7 168.5 3.91 720.2 188.0 3.49 707.0 215.3 3.02 686.9 245.2 2.61 665.9 267.9 2.337 752.1 171.1 3.97 740.1 190.9 3.53 726.3 215.9 3.10 704.4 245.3 2.67 681.7 267.9 2.38  

8 772.8 174.0 4.02 760.3 193.9 3.58 746.0 216.5 3.17 722.3 245.4 2.74 697.8 267.7 2.44  

10 815.5 180.1 4.11 802.0 199.2 3.68 786.4 222.3 3.27 759.1 245.6 2.87 730.8 267.2 2.56  

12 859.4 187.0 4.18 845.1 205.1 3.78 828.4 227.8 3.36 795.4 249.1 2.97 765.0 266.5 2.68  

15 927.2 195.8 4.33 911.4 215.0 3.90 893.3 236.5 3.50 850.3 253.5 3.13 788.9 253.7 2.90  

15.5 938.8 197.5 4.35 922.7 216.7 3.92 904.4 238.1 3.52 859.6 254.1 3.15 791.9 251.0 2.94  

4.5 729.1 169.5 3.84 718.3 192.1 3.38 705.8 218.9 2.95 690.6 250.1 2.56 674.5 275.0 2.295 739.3 171.1 3.87 728.3 192.6 3.42 715.5 219.3 2.99 699.9 250.6 2.59 682.6 275.1 2.31

6 760.1 174.2 3.91 748.7 193.6 3.50 735.3 220.1 3.06 719.0 251.5 2.65 699.1 275.3 2.377 781.2 177.0 3.96 769.4 196.4 3.55 755.6 221.0 3.13 738.5 252.5 2.71 715.7 275.4 2.42  

8 802.8 179.9 4.01 790.5 199.7 3.59 776.1 222.1 3.20 758.3 253.6 2.77 732.8 275.4 2.4810 846.9 185.9 4.11 833.9 205.5 3.69 818.5 227.9 3.30 797.6 254.8 2.90 768.0 275.4 2.60  

12 891.7 192.4 4.19 878.0 211.4 3.79 861.9 234.1 3.39 835.0 258.1 3.00 804.1 275.3 2.7215 961.6 200.3 4.36 946.7 221.1 3.92 929.0 243.1 3.53 892.2 263.6 3.14 859.6 280.0 2.86  

15.5 973.6 201.7 4.39 958.4 222.8 3.95 940.5 244.7 3.55 901.9 264.4 3.17 868.7 281.0 2.88

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

   L   W   T   °   C

Modelo

YCIV

0590

YCIV

0630

YCIV

0700

YCIV

0760

YCIV

0800

YCIV0830

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 531.2 128.6 3.74 517.3 143.0 3.31 499.4 156.8 2.93 479.0 171.1 2.60 456.8 186.3 2.295 539.7 129.1 3.79 525.5 143.4 3.35 507.3 157.3 2.97 486.6 171.7 2.63 464.0 187.0 2.32  

6 557.0 130.1 3.88 542.0 144.3 3.44 523.4 158.5 3.04 501.9 173.1 2.69 478.7 188.4 2.377 574.6 131.1 3.97 558.8 145.3 3.52 539.7 159.7 3.12 517.6 174.6 2.75 493.8 189.9 2.43  

8 592.1 132.1 4.07 575.9 146.3 3.60 556.3 161.0 3.19 533.5 176.0 2.82 509.1 191.6 2.48  

10 627.5 133.8 4.26 610.8 148.6 3.77 590.2 163.9 3.33 566.4 179.1 2.94 541.3 195.7 2.59  12 664.0 135.6 4.45 646.7 151.2 3.93 625.1 167.0 3.47 600.3 182.6 3.06 575.3 200.4 2.69  

15 721.0 138.4 4.75 703.1 154.9 4.18 680.6 171.4 3.68 654.7 187.7 3.26 610.0 196.5 2.91

15.5 730.7 138.9 4.80 712.7 155.6 4.22 690.1 172.2 3.72 664.1 188.5 3.29 611.8 194.0 2.95  

4.5 570.3 136.1 3.77 557.3 152.9 3.32 541.0 169.4 2.93 522.6 186.5 2.59 502.4 203.9 2.295 579.5 136.5 3.82 566.0 153.2 3.36 549.2 169.7 2.97 530.4 187.0 2.62 510.0 204.6 2.32  

6 597.8 137.3 3.92 583.5 153.8 3.45 566.0 170.5 3.05 546.4 188.0 2.69 525.3 206.1 2.377 616.5 138.1 4.02 601.5 154.5 3.55 583.2 171.4 3.13 562.7 189.1 2.76 541.2 207.8 2.43  

8 635.6 139.0 4.12 619.7 155.2 3.64 600.7 172.3 3.21 579.5 190.2 2.82 557.4 209.4 2.4810 675.1 141.3 4.32 657.2 157.2 3.81 636.6 174.6 3.36 613.9 192.8 2.95 591.0 212.9 2.59  

12 716.1 144.0 4.50 696.3 159.6 3.98 674.1 177.1 3.51 650.0 195.5 3.09 607.7 204.8 2.7615 778.8 148.4 4.76 757.1 164.2 4.22 732.9 181.8 3.72 706.9 200.3 3.28 624.9 190.1 3.04  

15.5 789.3 149.3 4.80 767.4 165.1 4.26 743.0 182.6 3.76 716.7 201.2 3.31 626.7 187.7 3.094.5 609.5 144.3 3.78 600.3 163.6 3.33 589.1 186.5 2.90 573.0 211.4 2.51 557.7 233.2 2.23

5 618.0 145.6 3.81 608.7 163.9 3.37 597.4 186.8 2.93 580.5 211.6 2.54 564.5 233.5 2.26  

6 635.3 148.0 3.85 625.8 165.1 3.44 614.1 187.6 3.00 595.6 212.0 2.60 578.3 234.0 2.317 652.9 150.2 3.91 643.2 167.5 3.49 631.1 188.3 3.08 611.1 212.3 2.67 592.5 234.4 2.36  

8 670.5 152.5 3.96 660.8 170.1 3.54 648.5 189.4 3.15 626.9 212.6 2.73 606.9 234.8 2.41

10 706.7 157.3 4.06 696.6 174.7 3.64 683.7 194.5 3.24 659.3 213.3 2.87 636.4 235.3 2.52  

12 744.0 162.3 4.15 733.5 179.6 3.74 720.0 199.5 3.33 692.1 217.2 2.96 666.9 235.7 2.64  

15 802.0 168.2 4.33 791.0 187.4 3.87 776.6 207.0 3.47 742.7 222.7 3.10 691.3 227.8 2.83  

15.5 811.9 169.3 4.36 800.8 188.6 3.90 786.3 208.3 3.49 750.9 223.5 3.12 694.0 225.6 2.86  

4.5 660.4 156.5 3.81 649.7 178.7 3.32 637.3 205.8 2.86 621.6 236.9 2.45 597.9 255.5 2.205 669.6 157.8 3.83 658.7 178.8 3.37 646.1 206.1 2.90 629.2 236.7 2.48 605.1 255.6 2.22  

6 688.4 160.4 3.89 677.1 179.8 3.44 663.9 206.4 2.97 644.7 236.3 2.55 619.6 255.7 2.277 707.5 162.8 3.94 695.7 182.5 3.49 682.1 206.8 3.05 660.5 235.9 2.61 634.4 255.7 2.33  

8 727.1 165.5 3.99 714.8 185.1 3.54 700.7 207.3 3.13 676.3 235.4 2.68 649.5 255.5 2.3910 767.1 171.5 4.07 754.0 190.0 3.65 738.7 213.0 3.22 709.1 234.3 2.82 680.5 254.8 2.51

12 808.7 178.2 4.15 794.6 195.5 3.74 778.2 217.8 3.32 742.1 237.3 2.92 712.4 253.9 2.63

15 873.0 187.2 4.28 857.8 205.3 3.86 840.1 226.1 3.46 793.3 240.9 3.08 761.2 257.9 2.77  

15.5 883.9 188.9 4.30 868.5 206.8 3.88 850.7 227.6 3.48 802.0 241.5 3.11 764.7 255.5 2.814.5 701.9 164.1 3.84 691.1 187.0 3.36 678.8 214.5 2.91 661.3 244.9 2.51 642.8 267.6 2.25

5 711.7 165.6 3.87 700.7 187.2 3.41 688.1 214.8 2.95 669.8 245.0 2.54 650.4 267.8 2.27  

6 731.7 168.5 3.91 720.2 188.0 3.49 707.0 215.3 3.02 686.9 245.2 2.61 665.9 267.9 2.337 752.1 171.1 3.97 740.1 190.9 3.53 726.3 215.9 3.10 704.4 245.3 2.67 681.7 267.9 2.38  

8 772.8 174.0 4.02 760.3 193.9 3.58 746.0 216.5 3.17 722.3 245.4 2.74 697.8 267.7 2.44  

10 815.5 180.1 4.11 802.0 199.2 3.68 786.4 222.3 3.27 759.1 245.6 2.87 730.8 267.2 2.56  

12 859.4 187.0 4.18 845.1 205.1 3.78 828.4 227.8 3.36 795.4 249.1 2.97 765.0 266.5 2.68  

15 927.2 195.8 4.33 911.4 215.0 3.90 893.3 236.5 3.50 850.3 253.5 3.13 788.9 253.7 2.90  

15.5 938.8 197.5 4.35 922.7 216.7 3.92 904.4 238.1 3.52 859.6 254.1 3.15 791.9 251.0 2.94  

4.5 729.1 169.5 3.84 718.3 192.1 3.38 705.8 218.9 2.95 690.6 250.1 2.56 674.5 275.0 2.295 739.3 171.1 3.87 728.3 192.6 3.42 715.5 219.3 2.99 699.9 250.6 2.59 682.6 275.1 2.31

6 760.1 174.2 3.91 748.7 193.6 3.50 735.3 220.1 3.06 719.0 251.5 2.65 699.1 275.3 2.377 781.2 177.0 3.96 769.4 196.4 3.55 755.6 221.0 3.13 738.5 252.5 2.71 715.7 275.4 2.42  

8 802.8 179.9 4.01 790.5 199.7 3.59 776.1 222.1 3.20 758.3 253.6 2.77 732.8 275.4 2.4810 846.9 185.9 4.11 833.9 205.5 3.69 818.5 227.9 3.30 797.6 254.8 2.90 768.0 275.4 2.60  

12 891.7 192.4 4.19 878.0 211.4 3.79 861.9 234.1 3.39 835.0 258.1 3.00 804.1 275.3 2.7215 961.6 200.3 4.36 946.7 221.1 3.92 929.0 243.1 3.53 892.2 263.6 3.14 859.6 280.0 2.86  

15.5 973.6 201.7 4.39 958.4 222.8 3.95 940.5 244.7 3.55 901.9 264.4 3.17 868.7 281.0 2.88

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

   L   W   T   °   C

Modelo

YCIV

0590

YCIV

0630

YCIV

0700

YCIV

0760

YCIV

0800

YCIV0830

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 35/72

 

35

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Alto Rendimiento (HE) con Ventiladores Estándar - Capacidades Frigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 809.6 196.2 3.74 796.8 220.6 3.31 781.9 250.4 2.89 760.8 283.1 2.51 746.0 313.3 2.245 820.9 198.2 3.76 807.9 221.3 3.35 792.7 251.0 2.92 770.8 283.7 2.54 755.0 313.6 2.26  

6 843.9 201.7 3.80 830.4 223.3 3.41 814.5 252.3 2.99 791.0 284.7 2.59 773.3 314.4 2.317 867.2 205.1 3.85 853.2 227.4 3.45 836.7 253.8 3.05 811.6 285.8 2.65 792.1 315.1 2.36  

8 891.0 208.6 3.89 876.4 231.3 3.48 859.4 255.6 3.12 832.6 286.9 2.71 811.2 315.7 2.41

10 939.9 215.9 3.98 924.2 238.4 3.57 905.8 264.0 3.19 874.2 288.4 2.83 828.9 303.0 2.57  

12 990.4 223.3 4.07 973.7 245.8 3.66 954.0 271.5 3.27 915.7 294.5 2.91 843.6 287.9 2.74  

15 1068.9 231.0 4.26 1050.7 257.0 3.79 1028.3 281.6 3.41 980.3 302.5 3.04 857.1 271.2 2.94  

15.5 1082.3 232.6 4.28 1063.9 258.5 3.82 1040.4 283.4 3.43 0.0 0.0 0.00 859.4 268.9 2.97  

4.5 919.4 215.4 3.85 903.5 245.5 3.36 884.6 280.8 2.91 861.5 321.6 2.50 828.1 350.8 2.215 932.4 217.3 3.87 916.3 245.9 3.40 897.1 281.3 2.94 872.9 321.9 2.53 838.2 351.1 2.24  

6 958.7 221.0 3.92 942.4 247.2 3.48 922.4 282.2 3.02 895.5 322.2 2.59 858.7 351.7 2.297 985.6 224.5 3.97 968.8 250.6 3.53 948.3 283.2 3.09 918.5 322.3 2.66 879.7 352.1 2.34  

8 1012.9 228.1 4.03 995.6 254.6 3.58 974.7 284.3 3.17 941.1 322.4 2.72 901.0 352.5 2.4010 1069.0 235.9 4.12 1051.1 261.6 3.69 1028.8 291.7 3.26 987.8 322.3 2.86 944.9 352.9 2.51

12 1126.9 244.3 4.21 1108.3 269.2 3.79 1084.9 299.2 3.36 1035.1 326.6 2.96 990.4 353.0 2.6315 1217.3 255.0 4.37 1197.7 281.9 3.92 1172.8 310.9 3.51 1107.9 333.8 3.10 1060.2 359.7 2.77  

15.5 1232.7 257.0 4.39 1213.0 284.1 3.94 1187.8 313.0 3.53 1120.4 334.9 3.13 1072.1 360.9 2.794.5 978.3 226.2 3.89 961.7 259.4 3.38 942.8 298.5 2.91 919.6 343.8 2.49 887.1 372.6 2.23

5 992.1 228.2 3.92 975.4 259.6 3.42 955.9 298.7 2.95 932.2 344.3 2.52 897.8 372.8 2.26  

6 1020.2 232.0 3.97 1003.0 260.3 3.51 982.6 299.4 3.03 957.4 344.9 2.59 919.4 373.0 2.31

7 1048.7 235.7 4.02 1031.0 263.7 3.57 1009.9 299.9 3.11 981.0 344.3 2.66 941.6 373.0 2.36  

8 1077.9 239.6 4.07 1059.5 267.8 3.62 1037.8 300.6 3.19 1005.1 343.6 2.73 964.1 372.9 2.42  

10 1137.9 248.1 4.16 1118.4 274.9 3.73 1095.2 307.5 3.29 1054.4 342.3 2.87 1010.8 372.1 2.54  

12 1200.1 258.1 4.24 1179.5 283.0 3.83 1154.7 315.1 3.39 1104.6 345.3 2.98 1059.2 370.8 2.67  

15 1297.9 271.6 4.37 1275.3 297.1 3.96 1248.3 327.2 3.54 1182.2 351.2 3.14 1133.3 375.5 2.83  

15.5 1314.6 274.2 4.39 1291.6 299.9 3.97 1264.4 329.4 3.57 1195.6 352.1 3.17 1145.9 376.6 2.85  

4.5 1063.9 249.9 3.84 1046.5 284.1 3.36 1026.8 325.9 2.91 997.6 370.9 2.51 965.7 403.0 2.255 1078.9 252.3 3.86 1061.2 284.6 3.41 1040.9 326.3 2.95 1010.1 371.0 2.54 977.0 403.3 2.27  

6 1109.3 256.4 3.92 1090.9 286.2 3.48 1069.7 327.2 3.02 1035.5 371.1 2.60 1000.2 403.5 2.327 1140.5 260.5 3.97 1121.2 290.8 3.53 1099.1 328.1 3.10 1061.6 371.1 2.67 1023.9 403.6 2.38  

8 1172.3 264.8 4.02 1152.1 295.3 3.58 1129.2 329.3 3.17 1088.1 371.0 2.73 1048.0 403.5 2.4410 1237.7 274.3 4.11 1215.8 303.5 3.68 1190.8 338.7 3.26 1142.8 370.9 2.87 1097.6 402.9 2.55  

12 1305.8 284.6 4.19 1282.1 312.6 3.78 1255.1 347.1 3.36 1197.0 376.4 2.97 1149.2 401.8 2.6815 1412.8 298.3 4.34 1386.3 328.3 3.90 1356.3 361.1 3.50 1280.2 382.9 3.12 1184.1 382.7 2.89  

15.5 1431.2 300.9 4.37 1404.3 330.5 3.93 1373.8 363.6 3.52 1294.4 383.9 3.15 1188.5 378.7 2.934.5 1206.1 287.7 3.79 1185.1 323.9 3.35 1160.1 366.4 2.92 1127.6 415.0 2.53 1106.8 461.5 2.255 1223.1 290.7 3.81 1201.9 325.0 3.38 1176.5 367.5 2.96 1142.6 415.7 2.56 1120.7 462.1 2.28  

6 1257.6 296.4 3.85 1236.0 327.4 3.46 1209.7 369.7 3.02 1173.1 417.2 2.62 1148.8 463.4 2.337 1292.8 301.6 3.90 1270.5 332.9 3.50 1243.6 371.9 3.09 1204.2 418.8 2.68 1177.7 464.6 2.38  

8 1328.6 306.9 3.94 1305.7 339.2 3.53 1278.0 374.5 3.16 1235.9 420.3 2.74 1207.2 465.8 2.43  

10 1401.9 318.0 4.03 1378.0 350.3 3.62 1348.6 386.2 3.24 1301.2 423.6 2.87 1268.0 468.1 2.54  

12 1477.7 329.7 4.11 1452.8 361.7 3.71 1421.9 398.1 3.32 1366.5 432.5 2.95 1306.5 455.1 2.69  

15 1594.7 341.4 4.29 1569.0 378.5 3.84 1537.2 414.8 3.45 1466.4 446.1 3.08 1330.0 428.0 2.90  

15.5 1614.4 343.7 4.32 1588.7 381.4 3.86 1556.3 417.9 3.47 1485.4 447.3 3.11 1333.4 424.3 2.93  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.

LWT = Temperatura de Salida del Agua

YCIV

1380

YCIV

0930

Modelo

YCIV

1050

   L   W   T   °   C

YCIV

1120

YCIV

1220

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 809.6 196.2 3.74 796.8 220.6 3.31 781.9 250.4 2.89 760.8 283.1 2.51 746.0 313.3 2.245 820.9 198.2 3.76 807.9 221.3 3.35 792.7 251.0 2.92 770.8 283.7 2.54 755.0 313.6 2.26  

6 843.9 201.7 3.80 830.4 223.3 3.41 814.5 252.3 2.99 791.0 284.7 2.59 773.3 314.4 2.317 867.2 205.1 3.85 853.2 227.4 3.45 836.7 253.8 3.05 811.6 285.8 2.65 792.1 315.1 2.36  

8 891.0 208.6 3.89 876.4 231.3 3.48 859.4 255.6 3.12 832.6 286.9 2.71 811.2 315.7 2.41

10 939.9 215.9 3.98 924.2 238.4 3.57 905.8 264.0 3.19 874.2 288.4 2.83 828.9 303.0 2.57  

12 990.4 223.3 4.07 973.7 245.8 3.66 954.0 271.5 3.27 915.7 294.5 2.91 843.6 287.9 2.74  

15 1068.9 231.0 4.26 1050.7 257.0 3.79 1028.3 281.6 3.41 980.3 302.5 3.04 857.1 271.2 2.94  

15.5 1082.3 232.6 4.28 1063.9 258.5 3.82 1040.4 283.4 3.43 0.0 0.0 0.00 859.4 268.9 2.97  

4.5 919.4 215.4 3.85 903.5 245.5 3.36 884.6 280.8 2.91 861.5 321.6 2.50 828.1 350.8 2.215 932.4 217.3 3.87 916.3 245.9 3.40 897.1 281.3 2.94 872.9 321.9 2.53 838.2 351.1 2.24  

6 958.7 221.0 3.92 942.4 247.2 3.48 922.4 282.2 3.02 895.5 322.2 2.59 858.7 351.7 2.297 985.6 224.5 3.97 968.8 250.6 3.53 948.3 283.2 3.09 918.5 322.3 2.66 879.7 352.1 2.34  

8 1012.9 228.1 4.03 995.6 254.6 3.58 974.7 284.3 3.17 941.1 322.4 2.72 901.0 352.5 2.4010 1069.0 235.9 4.12 1051.1 261.6 3.69 1028.8 291.7 3.26 987.8 322.3 2.86 944.9 352.9 2.51

12 1126.9 244.3 4.21 1108.3 269.2 3.79 1084.9 299.2 3.36 1035.1 326.6 2.96 990.4 353.0 2.6315 1217.3 255.0 4.37 1197.7 281.9 3.92 1172.8 310.9 3.51 1107.9 333.8 3.10 1060.2 359.7 2.77  

15.5 1232.7 257.0 4.39 1213.0 284.1 3.94 1187.8 313.0 3.53 1120.4 334.9 3.13 1072.1 360.9 2.794.5 978.3 226.2 3.89 961.7 259.4 3.38 942.8 298.5 2.91 919.6 343.8 2.49 887.1 372.6 2.23

5 992.1 228.2 3.92 975.4 259.6 3.42 955.9 298.7 2.95 932.2 344.3 2.52 897.8 372.8 2.26  

6 1020.2 232.0 3.97 1003.0 260.3 3.51 982.6 299.4 3.03 957.4 344.9 2.59 919.4 373.0 2.31

7 1048.7 235.7 4.02 1031.0 263.7 3.57 1009.9 299.9 3.11 981.0 344.3 2.66 941.6 373.0 2.36  

8 1077.9 239.6 4.07 1059.5 267.8 3.62 1037.8 300.6 3.19 1005.1 343.6 2.73 964.1 372.9 2.42  

10 1137.9 248.1 4.16 1118.4 274.9 3.73 1095.2 307.5 3.29 1054.4 342.3 2.87 1010.8 372.1 2.54  

12 1200.1 258.1 4.24 1179.5 283.0 3.83 1154.7 315.1 3.39 1104.6 345.3 2.98 1059.2 370.8 2.67  

15 1297.9 271.6 4.37 1275.3 297.1 3.96 1248.3 327.2 3.54 1182.2 351.2 3.14 1133.3 375.5 2.83  

15.5 1314.6 274.2 4.39 1291.6 299.9 3.97 1264.4 329.4 3.57 1195.6 352.1 3.17 1145.9 376.6 2.85  

4.5 1063.9 249.9 3.84 1046.5 284.1 3.36 1026.8 325.9 2.91 997.6 370.9 2.51 965.7 403.0 2.255 1078.9 252.3 3.86 1061.2 284.6 3.41 1040.9 326.3 2.95 1010.1 371.0 2.54 977.0 403.3 2.27  

6 1109.3 256.4 3.92 1090.9 286.2 3.48 1069.7 327.2 3.02 1035.5 371.1 2.60 1000.2 403.5 2.327 1140.5 260.5 3.97 1121.2 290.8 3.53 1099.1 328.1 3.10 1061.6 371.1 2.67 1023.9 403.6 2.38  

8 1172.3 264.8 4.02 1152.1 295.3 3.58 1129.2 329.3 3.17 1088.1 371.0 2.73 1048.0 403.5 2.4410 1237.7 274.3 4.11 1215.8 303.5 3.68 1190.8 338.7 3.26 1142.8 370.9 2.87 1097.6 402.9 2.55  

12 1305.8 284.6 4.19 1282.1 312.6 3.78 1255.1 347.1 3.36 1197.0 376.4 2.97 1149.2 401.8 2.6815 1412.8 298.3 4.34 1386.3 328.3 3.90 1356.3 361.1 3.50 1280.2 382.9 3.12 1184.1 382.7 2.89  

15.5 1431.2 300.9 4.37 1404.3 330.5 3.93 1373.8 363.6 3.52 1294.4 383.9 3.15 1188.5 378.7 2.934.5 1206.1 287.7 3.79 1185.1 323.9 3.35 1160.1 366.4 2.92 1127.6 415.0 2.53 1106.8 461.5 2.255 1223.1 290.7 3.81 1201.9 325.0 3.38 1176.5 367.5 2.96 1142.6 415.7 2.56 1120.7 462.1 2.28  

6 1257.6 296.4 3.85 1236.0 327.4 3.46 1209.7 369.7 3.02 1173.1 417.2 2.62 1148.8 463.4 2.337 1292.8 301.6 3.90 1270.5 332.9 3.50 1243.6 371.9 3.09 1204.2 418.8 2.68 1177.7 464.6 2.38  

8 1328.6 306.9 3.94 1305.7 339.2 3.53 1278.0 374.5 3.16 1235.9 420.3 2.74 1207.2 465.8 2.43  

10 1401.9 318.0 4.03 1378.0 350.3 3.62 1348.6 386.2 3.24 1301.2 423.6 2.87 1268.0 468.1 2.54  

12 1477.7 329.7 4.11 1452.8 361.7 3.71 1421.9 398.1 3.32 1366.5 432.5 2.95 1306.5 455.1 2.69  

15 1594.7 341.4 4.29 1569.0 378.5 3.84 1537.2 414.8 3.45 1466.4 446.1 3.08 1330.0 428.0 2.90  

15.5 1614.4 343.7 4.32 1588.7 381.4 3.86 1556.3 417.9 3.47 1485.4 447.3 3.11 1333.4 424.3 2.93  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.

LWT = Temperatura de Salida del Agua

YCIV

1380

YCIV

0930

Modelo

YCIV

1050

   L   W   T   °   C

YCIV

1120

YCIV

1220

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 36/72

 

36

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE RENDIMIENTO ESTÁNDAR (HE RS) CON VENTILADORES ULTRA SILENCIOSO -CAPACIDADES FRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 527.3 134.4 3.59 511.1 148.0 3.18 492.3 161.9 2.82 471.0 176.5 2.49 448.9 192.0 2.195 535.5 134.9 3.63 519.0 148.5 3.22 500.0 162.6 2.85 478.4 177.3 2.52 456.1 193.1 2.22  

6 552.0 135.8 3.72 535.2 149.7 3.30 515.7 164.0 2.92 493.1 178.9 2.57 470.7 195.3 2.267 569.0 136.7 3.81 551.6 150.9 3.37 531.4 165.5 2.98 508.4 180.5 2.63 485.7 197.6 2.31

8 586.0 137.8 3.90 568.3 152.2 3.45 547.4 167.0 3.05 523.8 182.2 2.69 501.1 200.0 2.36  

10 620.9 140.1 4.07 602.3 155.2 3.59 580.2 170.4 3.17 555.6 185.9 2.80 520.6 196.8 2.49  12 656.7 142.7 4.23 637.2 158.5 3.72 614.1 174.1 3.29 588.4 189.9 2.90 530.0 187.7 2.64  

15 712.9 146.4 4.48 692.2 163.4 3.93 668.2 179.4 3.48 641.1 196.2 3.07 543.1 175.1 2.89  

15.5 722.5 147.1 4.52 701.7 164.2 3.97 677.5 180.3 3.51 650.5 197.5 3.10 545.2 173.1 2.93  

4.5 566.3 142.2 3.62 551.6 158.8 3.19 534.6 175.5 2.82 515.2 192.9 2.49 495.9 211.7 2.205 575.2 142.6 3.67 560.0 159.1 3.23 542.6 176.0 2.85 522.9 193.6 2.52 503.3 212.6 2.22  

6 593.2 143.5 3.76 577.1 159.9 3.31 558.8 177.1 2.92 538.3 194.8 2.57 511.7 209.9 2.287 611.6 144.5 3.85 594.6 160.9 3.40 575.4 178.3 2.99 554.2 196.2 2.63 517.5 205.2 2.36  

8 630.3 145.6 3.94 612.4 161.9 3.48 592.3 179.5 3.06 570.3 197.6 2.69 523.4 200.4 2.4410 668.3 147.9 4.12 648.8 164.4 3.63 627.2 182.3 3.19 603.7 200.7 2.81 533.7 190.5 2.61

12 707.6 150.6 4.29 686.6 167.3 3.78 663.5 185.3 3.33 638.7 204.2 2.92 543.2 181.8 2.7715 768.7 155.7 4.52 745.7 172.6 3.99 720.4 190.6 3.52 694.7 210.8 3.09 556.2 169.5 3.03  

15.5 779.0 156.7 4.56 755.7 173.6 4.02 730.2 191.6 3.55 704.3 212.0 3.11 558.3 167.6 3.074.5 606.2 152.2 3.61 596.2 172.4 3.17 584.2 196.3 2.75 561.5 217.6 2.41 542.0 238.2 2.13

5 614.7 153.6 3.63 604.5 172.8 3.20 592.3 196.8 2.79 568.8 217.9 2.43 548.3 238.6 2.16  

6 631.7 156.2 3.67 621.3 174.3 3.27 608.7 197.8 2.85 583.4 218.5 2.49 560.6 238.6 2.207 649.1 158.7 3.72 638.3 177.3 3.31 625.4 198.8 2.91 598.2 219.0 2.55 565.5 233.4 2.27  

8 666.7 161.2 3.77 655.7 180.2 3.35 642.3 200.3 2.97 613.4 219.5 2.61 570.8 228.3 2.34  

10 702.5 166.3 3.86 691.0 185.3 3.44 676.9 206.4 3.05 643.7 220.4 2.72 582.7 218.9 2.48  

12 739.4 171.6 3.95 727.3 190.7 3.52 710.0 210.5 3.14 673.2 224.7 2.80 594.3 209.8 2.63  

15 796.8 177.4 4.12 783.9 199.1 3.65 761.0 216.4 3.28 718.8 230.0 2.92 606.8 199.9 2.81

15.5 806.6 178.5 4.15 793.6 200.3 3.67 769.7 217.4 3.30 726.5 230.8 2.95 608.5 198.1 2.85  

4.5 656.2 166.1 3.61 644.7 189.7 3.14 631.5 218.2 2.70 604.0 242.3 2.34 580.2 259.5 2.115 665.3 167.6 3.63 653.6 190.0 3.18 640.1 218.5 2.73 611.2 242.3 2.37 586.9 259.8 2.13  

6 683.8 170.1 3.68 671.6 191.4 3.24 657.6 219.2 2.80 625.9 242.1 2.43 600.4 260.3 2.177 702.6 172.8 3.73 689.9 194.4 3.28 675.3 219.9 2.87 640.7 241.9 2.49 614.3 260.5 2.22  

8 721.8 175.5 3.77 708.5 197.3 3.32 693.4 221.0 2.93 655.8 241.5 2.55 628.5 260.6 2.2710 761.2 181.4 3.86 746.8 202.5 3.42 730.4 227.6 3.00 686.7 240.9 2.68 643.9 251.1 2.41

12 802.0 187.8 3.94 786.5 208.4 3.51 768.8 233.1 3.09 717.7 244.5 2.76 655.5 239.0 2.5715 865.3 196.0 4.09 848.6 218.2 3.63 820.9 237.9 3.24 765.8 248.1 2.90 668.5 227.0 2.75  

15.5 876.1 197.6 4.11 859.0 219.3 3.65 829.7 238.6 3.26 774.0 248.7 2.93 669.8 224.7 2.784.5 697.8 173.5 3.66 686.3 197.7 3.19 673.2 226.6 2.76 649.0 253.4 2.40 624.7 271.9 2.16

5 707.5 175.1 3.68 695.7 198.1 3.23 682.3 227.0 2.79 656.9 253.5 2.42 631.9 272.2 2.18  

6 727.2 178.1 3.72 714.9 199.2 3.30 700.8 227.9 2.86 672.4 253.4 2.48 643.0 270.4 2.237 747.2 180.9 3.77 734.3 202.6 3.34 719.7 228.7 2.92 688.3 253.3 2.54 648.8 264.8 2.30  

8 767.6 183.9 3.81 754.1 205.8 3.38 738.9 229.8 2.99 704.5 253.0 2.61 654.9 259.1 2.37  

10 809.6 190.2 3.90 794.9 211.6 3.47 778.1 236.5 3.07 737.6 252.5 2.73 667.5 247.2 2.52  

12 852.9 197.0 3.98 837.2 217.9 3.56 816.2 240.9 3.16 770.8 256.2 2.82 679.7 235.5 2.69  

15 919.4 205.1 4.13 902.2 228.1 3.68 874.9 247.9 3.30 822.5 260.5 2.96 693.3 224.2 2.87  

15.5 930.8 206.7 4.15 913.2 229.6 3.70 884.8 249.1 3.32 831.3 261.2 2.98 694.8 222.0 2.90  

4.5 725.3 178.1 3.68 713.8 201.8 3.23 700.6 229.7 2.82 681.5 260.1 2.44 656.8 279.5 2.205 735.4 179.8 3.70 723.7 202.4 3.27 710.1 230.3 2.85 689.7 260.2 2.47 664.3 279.7 2.22  

6 755.9 183.2 3.74 743.7 203.6 3.34 729.5 231.5 2.91 706.3 260.4 2.53 679.9 280.1 2.27

7 776.8 186.1 3.79 764.0 207.1 3.38 749.3 232.7 2.98 723.2 260.4 2.59 695.7 280.3 2.32  8 798.1 189.2 3.83 784.8 210.7 3.42 769.5 233.9 3.04 740.3 260.5 2.65 711.9 280.5 2.38

10 841.7 195.7 3.92 827.4 216.9 3.51 810.8 241.0 3.12 775.3 260.7 2.77 745.1 280.6 2.49  

12 885.9 202.4 4.00 870.9 223.5 3.59 853.5 247.7 3.20 810.8 264.6 2.86 779.2 280.7 2.6015 954.9 210.0 4.17 938.3 233.7 3.71 919.1 257.9 3.32 865.3 270.2 2.99 814.6 275.1 2.77  

15.5 966.7 211.4 4.20 949.8 235.6 3.73 930.4 259.6 3.34 874.5 271.0 3.02 817.6 272.0 2.81

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

0630

YCIV

0700

YCIV

0760

YCIV

0800

Modelo

   L   W   T   °   C

YCIV

0590

YCIV

0830

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 527.3 134.4 3.59 511.1 148.0 3.18 492.3 161.9 2.82 471.0 176.5 2.49 448.9 192.0 2.195 535.5 134.9 3.63 519.0 148.5 3.22 500.0 162.6 2.85 478.4 177.3 2.52 456.1 193.1 2.22  

6 552.0 135.8 3.72 535.2 149.7 3.30 515.7 164.0 2.92 493.1 178.9 2.57 470.7 195.3 2.267 569.0 136.7 3.81 551.6 150.9 3.37 531.4 165.5 2.98 508.4 180.5 2.63 485.7 197.6 2.31

8 586.0 137.8 3.90 568.3 152.2 3.45 547.4 167.0 3.05 523.8 182.2 2.69 501.1 200.0 2.36  

10 620.9 140.1 4.07 602.3 155.2 3.59 580.2 170.4 3.17 555.6 185.9 2.80 520.6 196.8 2.49  12 656.7 142.7 4.23 637.2 158.5 3.72 614.1 174.1 3.29 588.4 189.9 2.90 530.0 187.7 2.64  

15 712.9 146.4 4.48 692.2 163.4 3.93 668.2 179.4 3.48 641.1 196.2 3.07 543.1 175.1 2.89  

15.5 722.5 147.1 4.52 701.7 164.2 3.97 677.5 180.3 3.51 650.5 197.5 3.10 545.2 173.1 2.93  

4.5 566.3 142.2 3.62 551.6 158.8 3.19 534.6 175.5 2.82 515.2 192.9 2.49 495.9 211.7 2.205 575.2 142.6 3.67 560.0 159.1 3.23 542.6 176.0 2.85 522.9 193.6 2.52 503.3 212.6 2.22  

6 593.2 143.5 3.76 577.1 159.9 3.31 558.8 177.1 2.92 538.3 194.8 2.57 511.7 209.9 2.287 611.6 144.5 3.85 594.6 160.9 3.40 575.4 178.3 2.99 554.2 196.2 2.63 517.5 205.2 2.36  

8 630.3 145.6 3.94 612.4 161.9 3.48 592.3 179.5 3.06 570.3 197.6 2.69 523.4 200.4 2.4410 668.3 147.9 4.12 648.8 164.4 3.63 627.2 182.3 3.19 603.7 200.7 2.81 533.7 190.5 2.61

12 707.6 150.6 4.29 686.6 167.3 3.78 663.5 185.3 3.33 638.7 204.2 2.92 543.2 181.8 2.7715 768.7 155.7 4.52 745.7 172.6 3.99 720.4 190.6 3.52 694.7 210.8 3.09 556.2 169.5 3.03  

15.5 779.0 156.7 4.56 755.7 173.6 4.02 730.2 191.6 3.55 704.3 212.0 3.11 558.3 167.6 3.074.5 606.2 152.2 3.61 596.2 172.4 3.17 584.2 196.3 2.75 561.5 217.6 2.41 542.0 238.2 2.13

5 614.7 153.6 3.63 604.5 172.8 3.20 592.3 196.8 2.79 568.8 217.9 2.43 548.3 238.6 2.16  

6 631.7 156.2 3.67 621.3 174.3 3.27 608.7 197.8 2.85 583.4 218.5 2.49 560.6 238.6 2.207 649.1 158.7 3.72 638.3 177.3 3.31 625.4 198.8 2.91 598.2 219.0 2.55 565.5 233.4 2.27  

8 666.7 161.2 3.77 655.7 180.2 3.35 642.3 200.3 2.97 613.4 219.5 2.61 570.8 228.3 2.34  

10 702.5 166.3 3.86 691.0 185.3 3.44 676.9 206.4 3.05 643.7 220.4 2.72 582.7 218.9 2.48  

12 739.4 171.6 3.95 727.3 190.7 3.52 710.0 210.5 3.14 673.2 224.7 2.80 594.3 209.8 2.63  

15 796.8 177.4 4.12 783.9 199.1 3.65 761.0 216.4 3.28 718.8 230.0 2.92 606.8 199.9 2.81

15.5 806.6 178.5 4.15 793.6 200.3 3.67 769.7 217.4 3.30 726.5 230.8 2.95 608.5 198.1 2.85  

4.5 656.2 166.1 3.61 644.7 189.7 3.14 631.5 218.2 2.70 604.0 242.3 2.34 580.2 259.5 2.115 665.3 167.6 3.63 653.6 190.0 3.18 640.1 218.5 2.73 611.2 242.3 2.37 586.9 259.8 2.13  

6 683.8 170.1 3.68 671.6 191.4 3.24 657.6 219.2 2.80 625.9 242.1 2.43 600.4 260.3 2.177 702.6 172.8 3.73 689.9 194.4 3.28 675.3 219.9 2.87 640.7 241.9 2.49 614.3 260.5 2.22  

8 721.8 175.5 3.77 708.5 197.3 3.32 693.4 221.0 2.93 655.8 241.5 2.55 628.5 260.6 2.2710 761.2 181.4 3.86 746.8 202.5 3.42 730.4 227.6 3.00 686.7 240.9 2.68 643.9 251.1 2.41

12 802.0 187.8 3.94 786.5 208.4 3.51 768.8 233.1 3.09 717.7 244.5 2.76 655.5 239.0 2.5715 865.3 196.0 4.09 848.6 218.2 3.63 820.9 237.9 3.24 765.8 248.1 2.90 668.5 227.0 2.75  

15.5 876.1 197.6 4.11 859.0 219.3 3.65 829.7 238.6 3.26 774.0 248.7 2.93 669.8 224.7 2.784.5 697.8 173.5 3.66 686.3 197.7 3.19 673.2 226.6 2.76 649.0 253.4 2.40 624.7 271.9 2.16

5 707.5 175.1 3.68 695.7 198.1 3.23 682.3 227.0 2.79 656.9 253.5 2.42 631.9 272.2 2.18  

6 727.2 178.1 3.72 714.9 199.2 3.30 700.8 227.9 2.86 672.4 253.4 2.48 643.0 270.4 2.237 747.2 180.9 3.77 734.3 202.6 3.34 719.7 228.7 2.92 688.3 253.3 2.54 648.8 264.8 2.30  

8 767.6 183.9 3.81 754.1 205.8 3.38 738.9 229.8 2.99 704.5 253.0 2.61 654.9 259.1 2.37  

10 809.6 190.2 3.90 794.9 211.6 3.47 778.1 236.5 3.07 737.6 252.5 2.73 667.5 247.2 2.52  

12 852.9 197.0 3.98 837.2 217.9 3.56 816.2 240.9 3.16 770.8 256.2 2.82 679.7 235.5 2.69  

15 919.4 205.1 4.13 902.2 228.1 3.68 874.9 247.9 3.30 822.5 260.5 2.96 693.3 224.2 2.87  

15.5 930.8 206.7 4.15 913.2 229.6 3.70 884.8 249.1 3.32 831.3 261.2 2.98 694.8 222.0 2.90  

4.5 725.3 178.1 3.68 713.8 201.8 3.23 700.6 229.7 2.82 681.5 260.1 2.44 656.8 279.5 2.205 735.4 179.8 3.70 723.7 202.4 3.27 710.1 230.3 2.85 689.7 260.2 2.47 664.3 279.7 2.22  

6 755.9 183.2 3.74 743.7 203.6 3.34 729.5 231.5 2.91 706.3 260.4 2.53 679.9 280.1 2.27

7 776.8 186.1 3.79 764.0 207.1 3.38 749.3 232.7 2.98 723.2 260.4 2.59 695.7 280.3 2.32  8 798.1 189.2 3.83 784.8 210.7 3.42 769.5 233.9 3.04 740.3 260.5 2.65 711.9 280.5 2.38

10 841.7 195.7 3.92 827.4 216.9 3.51 810.8 241.0 3.12 775.3 260.7 2.77 745.1 280.6 2.49  

12 885.9 202.4 4.00 870.9 223.5 3.59 853.5 247.7 3.20 810.8 264.6 2.86 779.2 280.7 2.6015 954.9 210.0 4.17 938.3 233.7 3.71 919.1 257.9 3.32 865.3 270.2 2.99 814.6 275.1 2.77  

15.5 966.7 211.4 4.20 949.8 235.6 3.73 930.4 259.6 3.34 874.5 271.0 3.02 817.6 272.0 2.81

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

YCIV

0630

YCIV

0700

YCIV

0760

YCIV

0800

Modelo

   L   W   T   °   C

YCIV

0590

YCIV

0830

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 37/72

 

37

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Rendimiento Estándar (HE RS) con Ventiladores Ultra Silencioso - Capacidades Frigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 804.6 207.4 3.55 790.7 233.0 3.14 774.8 264.1 2.74 746.6 293.8 2.39 698.0 302.0 2.175 815.6 209.6 3.57 801.6 233.8 3.17 785.3 265.0 2.77 755.7 294.2 2.41 701.5 299.1 2.21

6 838.3 213.3 3.61 823.5 236.5 3.22 806.6 266.7 2.82 774.0 294.9 2.47 708.4 292.9 2.277 861.2 217.1 3.65 845.9 241.1 3.25 828.3 268.4 2.88 792.7 295.7 2.52 714.9 286.4 2.34  

8 884.6 220.9 3.69 868.7 245.3 3.29 850.2 270.7 2.94 811.7 296.4 2.57 720.9 279.5 2.42  

10 932.7 228.8 3.76 915.4 253.3 3.36 893.4 279.2 3.00 850.6 298.0 2.68 730.8 265.2 2.57  

12982.3 236.5 3.85 963.8 261.5 3.44 938.1 286.3 3.07 889.8 305.0 2.75 741.4 252.9 2.73  

15 1059.6 244.5 4.02 1039.3 273.6 3.55 1007.5 297.3 3.19 951.0 313.4 2.86 753.2 240.2 2.91

15.5 1072.8 246.1 4.05 1052.1 275.0 3.58 1020.3 298.6 3.21 961.4 314.7 2.88 755.3 237.9 2.94  

4.5 913.5 227.8 3.65 896.2 259.5 3.18 876.0 296.4 2.75 838.7 330.2 2.38 803.1 357.7 2.115 926.4 230.0 3.67 908.8 260.1 3.22 888.2 297.1 2.78 848.9 330.4 2.41 812.6 358.2 2.14  

6 952.4 233.9 3.72 934.4 261.7 3.29 913.0 298.4 2.85 869.7 330.8 2.46 831.8 359.2 2.187 978.8 237.6 3.77 960.3 265.8 3.34 938.3 299.8 2.92 890.7 331.1 2.52 851.3 360.0 2.23  

8 1005.9 241.5 3.82 986.6 270.3 3.37 964.1 301.4 2.98 911.9 331.4 2.58 871.3 360.6 2.2810 1061.3 249.6 3.91 1041.1 278.1 3.47 1016.7 310.3 3.06 955.9 331.8 2.70 900.6 353.4 2.40  

12 1118.5 258.2 3.99 1097.2 286.4 3.56 1071.5 318.8 3.14 1000.2 337.1 2.78 917.8 338.0 2.5515 1207.9 268.3 4.16 1185.0 299.7 3.68 1149.2 328.2 3.28 1068.6 344.6 2.91 938.6 321.4 2.73  

15.5 1223.2 270.2 4.18 1200.1 301.7 3.71 1161.6 329.5 3.30 1080.3 345.7 2.94 941.4 318.6 2.764.5 972.2 239.5 3.69 954.4 274.8 3.20 934.3 315.5 2.75 896.9 353.2 2.38 861.2 378.3 2.14

5 985.8 241.7 3.71 967.7 275.2 3.24 947.0 316.1 2.79 907.7 353.2 2.41 871.2 378.8 2.16  

6 1013.5 245.7 3.76 994.7 276.0 3.32 973.2 317.1 2.86 929.7 353.0 2.47 891.6 379.5 2.217 1041.6 249.6 3.81 1022.3 280.2 3.36 999.8 318.1 2.93 952.0 352.7 2.53 912.4 379.9 2.26  

8 1070.4 253.5 3.86 1050.2 284.8 3.40 1027.1 319.3 2.99 974.8 352.3 2.59 933.4 380.1 2.31

10 1129.5 262.1 3.95 1107.9 292.5 3.50 1082.8 327.9 3.08 1021.3 351.4 2.72 977.3 379.9 2.42  

12 1190.7 272.0 4.03 1167.8 300.8 3.60 1140.8 336.3 3.17 1068.4 355.4 2.82 997.3 363.4 2.58  

15 1286.8 284.0 4.18 1261.6 315.4 3.72 1225.9 346.5 3.31 1141.3 361.4 2.96 1018.8 344.0 2.77  

15.5 1303.3 286.3 4.20 1277.7 317.6 3.74 1239.2 347.7 3.34 1153.7 362.2 2.99 1021.8 341.0 2.80  

4.5 1057.1 264.7 3.65 1038.6 301.0 3.18 1017.6 344.8 2.75 974.9 382.3 2.39 937.1 409.4 2.165 1071.9 267.2 3.67 1052.9 301.6 3.22 1031.4 345.5 2.78 986.6 382.4 2.42 947.7 409.9 2.18  

6 1101.7 271.7 3.71 1082.0 304.1 3.29 1059.5 346.9 2.85 1009.8 382.3 2.48 964.6 407.5 2.237 1132.3 276.0 3.76 1111.6 309.2 3.32 1088.2 348.3 2.91 1033.6 382.1 2.54 973.1 399.4 2.29  

8 1163.5 280.5 3.80 1141.8 314.1 3.36 1117.4 350.3 2.97 1057.9 381.9 2.60 981.9 391.0 2.3610 1227.7 290.4 3.89 1204.1 323.0 3.46 1176.5 360.8 3.05 1107.5 381.1 2.73 1000.6 373.4 2.51

12 1294.5 300.3 3.98 1268.8 332.9 3.54 1233.0 366.8 3.14 1157.3 387.1 2.81 1018.6 355.8 2.6715 1399.3 313.1 4.14 1370.4 348.7 3.66 1320.7 376.5 3.29 1235.3 393.7 2.95 1039.1 338.4 2.86  

15.5 1417.3 315.5 4.16 1387.8 350.8 3.69 1335.8 378.2 3.31 1248.6 394.7 2.97 1042.2 335.4 2.894.5 1198.0 303.2 3.61 1175.0 341.1 3.18 1148.5 385.6 2.77 1107.0 430.9 2.41 1079.6 474.3 2.155 1214.8 306.5 3.63 1191.5 342.4 3.21 1164.4 387.0 2.80 1121.1 431.6 2.44 1084.9 469.8 2.18  

6 1248.8 312.7 3.66 1225.0 345.3 3.28 1196.8 389.7 2.86 1149.6 432.9 2.49 1095.4 460.3 2.247 1283.5 318.6 3.70 1258.8 351.9 3.31 1229.9 392.4 2.92 1178.5 434.2 2.55 1105.7 450.3 2.31

8 1318.8 324.4 3.74 1293.3 358.9 3.34 1263.6 395.3 2.98 1207.7 435.7 2.60 1115.6 439.8 2.38  

10 1391.2 336.4 3.81 1364.3 371.0 3.42 1332.0 409.0 3.04 1268.0 438.4 2.72 1132.2 418.7 2.53  

12 1466.0 348.9 3.89 1437.6 383.7 3.49 1399.2 419.9 3.12 1329.2 448.1 2.79 1149.3 399.3 2.69  

15 1582.2 360.9 4.06 1552.3 402.4 3.60 1503.8 436.1 3.24 1423.8 462.4 2.90 1169.0 378.7 2.87  

15.5 1601.7 363.3 4.09 1571.4 405.1 3.62 1523.1 438.1 3.26 1440.0 464.6 2.92 1172.3 375.2 2.90  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.

LWT = Temperatura de Salida del Agua

YCIV

1380

Modelo

   L   W   T   °   C

YCIV

0930

YCIV

1050

YCIV

1120

YCIV

1220

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 804.6 207.4 3.55 790.7 233.0 3.14 774.8 264.1 2.74 746.6 293.8 2.39 698.0 302.0 2.175 815.6 209.6 3.57 801.6 233.8 3.17 785.3 265.0 2.77 755.7 294.2 2.41 701.5 299.1 2.21

6 838.3 213.3 3.61 823.5 236.5 3.22 806.6 266.7 2.82 774.0 294.9 2.47 708.4 292.9 2.277 861.2 217.1 3.65 845.9 241.1 3.25 828.3 268.4 2.88 792.7 295.7 2.52 714.9 286.4 2.34  

8 884.6 220.9 3.69 868.7 245.3 3.29 850.2 270.7 2.94 811.7 296.4 2.57 720.9 279.5 2.42  

10 932.7 228.8 3.76 915.4 253.3 3.36 893.4 279.2 3.00 850.6 298.0 2.68 730.8 265.2 2.57  

12982.3 236.5 3.85 963.8 261.5 3.44 938.1 286.3 3.07 889.8 305.0 2.75 741.4 252.9 2.73  

15 1059.6 244.5 4.02 1039.3 273.6 3.55 1007.5 297.3 3.19 951.0 313.4 2.86 753.2 240.2 2.91

15.5 1072.8 246.1 4.05 1052.1 275.0 3.58 1020.3 298.6 3.21 961.4 314.7 2.88 755.3 237.9 2.94  

4.5 913.5 227.8 3.65 896.2 259.5 3.18 876.0 296.4 2.75 838.7 330.2 2.38 803.1 357.7 2.115 926.4 230.0 3.67 908.8 260.1 3.22 888.2 297.1 2.78 848.9 330.4 2.41 812.6 358.2 2.14  

6 952.4 233.9 3.72 934.4 261.7 3.29 913.0 298.4 2.85 869.7 330.8 2.46 831.8 359.2 2.187 978.8 237.6 3.77 960.3 265.8 3.34 938.3 299.8 2.92 890.7 331.1 2.52 851.3 360.0 2.23  

8 1005.9 241.5 3.82 986.6 270.3 3.37 964.1 301.4 2.98 911.9 331.4 2.58 871.3 360.6 2.2810 1061.3 249.6 3.91 1041.1 278.1 3.47 1016.7 310.3 3.06 955.9 331.8 2.70 900.6 353.4 2.40  

12 1118.5 258.2 3.99 1097.2 286.4 3.56 1071.5 318.8 3.14 1000.2 337.1 2.78 917.8 338.0 2.5515 1207.9 268.3 4.16 1185.0 299.7 3.68 1149.2 328.2 3.28 1068.6 344.6 2.91 938.6 321.4 2.73  

15.5 1223.2 270.2 4.18 1200.1 301.7 3.71 1161.6 329.5 3.30 1080.3 345.7 2.94 941.4 318.6 2.764.5 972.2 239.5 3.69 954.4 274.8 3.20 934.3 315.5 2.75 896.9 353.2 2.38 861.2 378.3 2.14

5 985.8 241.7 3.71 967.7 275.2 3.24 947.0 316.1 2.79 907.7 353.2 2.41 871.2 378.8 2.16  

6 1013.5 245.7 3.76 994.7 276.0 3.32 973.2 317.1 2.86 929.7 353.0 2.47 891.6 379.5 2.217 1041.6 249.6 3.81 1022.3 280.2 3.36 999.8 318.1 2.93 952.0 352.7 2.53 912.4 379.9 2.26  

8 1070.4 253.5 3.86 1050.2 284.8 3.40 1027.1 319.3 2.99 974.8 352.3 2.59 933.4 380.1 2.31

10 1129.5 262.1 3.95 1107.9 292.5 3.50 1082.8 327.9 3.08 1021.3 351.4 2.72 977.3 379.9 2.42  

12 1190.7 272.0 4.03 1167.8 300.8 3.60 1140.8 336.3 3.17 1068.4 355.4 2.82 997.3 363.4 2.58  

15 1286.8 284.0 4.18 1261.6 315.4 3.72 1225.9 346.5 3.31 1141.3 361.4 2.96 1018.8 344.0 2.77  

15.5 1303.3 286.3 4.20 1277.7 317.6 3.74 1239.2 347.7 3.34 1153.7 362.2 2.99 1021.8 341.0 2.80  

4.5 1057.1 264.7 3.65 1038.6 301.0 3.18 1017.6 344.8 2.75 974.9 382.3 2.39 937.1 409.4 2.165 1071.9 267.2 3.67 1052.9 301.6 3.22 1031.4 345.5 2.78 986.6 382.4 2.42 947.7 409.9 2.18  

6 1101.7 271.7 3.71 1082.0 304.1 3.29 1059.5 346.9 2.85 1009.8 382.3 2.48 964.6 407.5 2.237 1132.3 276.0 3.76 1111.6 309.2 3.32 1088.2 348.3 2.91 1033.6 382.1 2.54 973.1 399.4 2.29  

8 1163.5 280.5 3.80 1141.8 314.1 3.36 1117.4 350.3 2.97 1057.9 381.9 2.60 981.9 391.0 2.3610 1227.7 290.4 3.89 1204.1 323.0 3.46 1176.5 360.8 3.05 1107.5 381.1 2.73 1000.6 373.4 2.51

12 1294.5 300.3 3.98 1268.8 332.9 3.54 1233.0 366.8 3.14 1157.3 387.1 2.81 1018.6 355.8 2.6715 1399.3 313.1 4.14 1370.4 348.7 3.66 1320.7 376.5 3.29 1235.3 393.7 2.95 1039.1 338.4 2.86  

15.5 1417.3 315.5 4.16 1387.8 350.8 3.69 1335.8 378.2 3.31 1248.6 394.7 2.97 1042.2 335.4 2.894.5 1198.0 303.2 3.61 1175.0 341.1 3.18 1148.5 385.6 2.77 1107.0 430.9 2.41 1079.6 474.3 2.155 1214.8 306.5 3.63 1191.5 342.4 3.21 1164.4 387.0 2.80 1121.1 431.6 2.44 1084.9 469.8 2.18  

6 1248.8 312.7 3.66 1225.0 345.3 3.28 1196.8 389.7 2.86 1149.6 432.9 2.49 1095.4 460.3 2.247 1283.5 318.6 3.70 1258.8 351.9 3.31 1229.9 392.4 2.92 1178.5 434.2 2.55 1105.7 450.3 2.31

8 1318.8 324.4 3.74 1293.3 358.9 3.34 1263.6 395.3 2.98 1207.7 435.7 2.60 1115.6 439.8 2.38  

10 1391.2 336.4 3.81 1364.3 371.0 3.42 1332.0 409.0 3.04 1268.0 438.4 2.72 1132.2 418.7 2.53  

12 1466.0 348.9 3.89 1437.6 383.7 3.49 1399.2 419.9 3.12 1329.2 448.1 2.79 1149.3 399.3 2.69  

15 1582.2 360.9 4.06 1552.3 402.4 3.60 1503.8 436.1 3.24 1423.8 462.4 2.90 1169.0 378.7 2.87  

15.5 1601.7 363.3 4.09 1571.4 405.1 3.62 1523.1 438.1 3.26 1440.0 464.6 2.92 1172.3 375.2 2.90  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.

LWT = Temperatura de Salida del Agua

YCIV

1380

Modelo

   L   W   T   °   C

YCIV

0930

YCIV

1050

YCIV

1120

YCIV

1220

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 38/72

 

38

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE ALTO RENDIMIENTO (HE LS) CON VENTILADORES DE DOS VELOCIDADES -CAPACIDADES FRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 527.3 134.4 3.60 511.1 148.0 3.19 492.3 161.9 2.83 471.0 176.5 2.50 448.9 192.0 2.205 535.5 134.9 3.65 519.0 148.5 3.23 500.0 162.6 2.86 478.4 177.3 2.53 456.1 193.1 2.22  

6 552.0 135.8 3.73 535.2 149.7 3.31 515.7 164.0 2.93 493.1 178.9 2.58 470.7 195.3 2.277 569.0 136.7 3.83 551.6 150.9 3.39 531.4 165.5 2.99 508.4 180.5 2.64 485.7 197.6 2.32  

8 586.0 137.8 3.91 568.3 152.2 3.46 547.4 167.0 3.06 523.8 182.2 2.70 501.1 200.0 2.36  

10 620.9 140.1 4.08 602.3 155.2 3.60 580.2 170.4 3.18 555.6 185.9 2.81 520.6 196.8 2.49  12 656.7 142.7 4.25 637.2 158.5 3.74 614.1 174.1 3.30 588.4 189.9 2.91 530.0 187.7 2.65  

15 712.9 146.4 4.50 692.2 163.4 3.95 668.2 179.4 3.49 641.1 196.2 3.08 543.1 175.1 2.90  

15.5 722.5 147.1 4.54 701.7 164.2 3.98 677.5 180.3 3.52 650.5 197.5 3.11 545.2 173.1 2.94  

4.5 566.3 142.2 3.64 551.6 158.8 3.20 534.6 175.5 2.83 515.2 192.9 2.50 495.9 211.7 2.205 575.2 142.6 3.68 560.0 159.1 3.24 542.6 176.0 2.86 522.9 193.6 2.53 503.3 212.6 2.23  

6 593.2 143.5 3.78 577.1 159.9 3.33 558.8 177.1 2.93 538.3 194.8 2.58 511.7 209.9 2.297 611.6 144.5 3.87 594.6 160.9 3.41 575.4 178.3 3.00 554.2 196.2 2.64 517.5 205.2 2.37  

8 630.3 145.6 3.96 612.4 161.9 3.49 592.3 179.5 3.07 570.3 197.6 2.70 523.4 200.4 2.4510 668.3 147.9 4.14 648.8 164.4 3.65 627.2 182.3 3.20 603.7 200.7 2.82 533.7 190.5 2.62  

12 707.6 150.6 4.31 686.6 167.3 3.80 663.5 185.3 3.34 638.7 204.2 2.93 543.2 181.8 2.7815 768.7 155.7 4.54 745.7 172.6 4.01 720.4 190.6 3.53 694.7 210.8 3.10 556.2 169.5 3.04  

15.5 779.0 156.7 4.58 755.7 173.6 4.04 730.2 191.6 3.56 704.3 212.0 3.12 558.3 167.6 3.084.5 606.2 152.2 3.63 596.2 172.4 3.18 584.2 196.3 2.77 561.5 217.6 2.41 542.0 238.2 2.14

5 614.7 153.6 3.65 604.5 172.8 3.22 592.3 196.8 2.80 568.8 217.9 2.44 548.3 238.6 2.16  

6 631.7 156.2 3.69 621.3 174.3 3.28 608.7 197.8 2.86 583.4 218.5 2.50 560.6 238.6 2.217 649.1 158.7 3.74 638.3 177.3 3.32 625.4 198.8 2.92 598.2 219.0 2.56 565.5 233.4 2.28  

8 666.7 161.2 3.78 655.7 180.2 3.36 642.3 200.3 2.98 613.4 219.5 2.62 570.8 228.3 2.35  

10 702.5 166.3 3.87 691.0 185.3 3.45 676.9 206.4 3.06 643.7 220.4 2.73 582.7 218.9 2.49  

12 739.4 171.6 3.96 727.3 190.7 3.54 710.0 210.5 3.15 673.2 224.7 2.81 594.3 209.8 2.64  

15 796.8 177.4 4.14 783.9 199.1 3.66 761.0 216.4 3.29 718.8 230.0 2.93 606.8 199.9 2.82  

15.5 806.6 178.5 4.17 793.6 200.3 3.69 769.7 217.4 3.31 726.5 230.8 2.96 608.5 198.1 2.86  

4.5 656.2 166.1 3.62 644.7 189.7 3.15 631.5 218.2 2.71 604.0 242.3 2.35 580.2 259.5 2.115 665.3 167.6 3.64 653.6 190.0 3.19 640.1 218.5 2.74 611.2 242.3 2.38 586.9 259.8 2.14  

6 683.8 170.1 3.69 671.6 191.4 3.25 657.6 219.2 2.81 625.9 242.1 2.43 600.4 260.3 2.187 702.6 172.8 3.74 689.9 194.4 3.29 675.3 219.9 2.88 640.7 241.9 2.49 614.3 260.5 2.23  

8 721.8 175.5 3.79 708.5 197.3 3.34 693.4 221.0 2.94 655.8 241.5 2.56 628.5 260.6 2.2810 761.2 181.4 3.88 746.8 202.5 3.43 730.4 227.6 3.01 686.7 240.9 2.68 643.9 251.1 2.42  

12 802.0 187.8 3.96 786.5 208.4 3.52 768.8 233.1 3.10 717.7 244.5 2.77 655.5 239.0 2.5815 865.3 196.0 4.10 848.6 218.2 3.64 820.9 237.9 3.25 765.8 248.1 2.91 668.5 227.0 2.76  

15.5 876.1 197.6 4.12 859.0 219.3 3.67 829.7 238.6 3.27 774.0 248.7 2.94 669.8 224.7 2.794.5 697.8 173.5 3.67 686.3 197.7 3.20 673.2 226.6 2.77 649.0 253.4 2.40 624.7 271.9 2.17

5 707.5 175.1 3.69 695.7 198.1 3.24 682.3 227.0 2.80 656.9 253.5 2.43 631.9 272.2 2.19  

6 727.2 178.1 3.74 714.9 199.2 3.31 700.8 227.9 2.87 672.4 253.4 2.49 643.0 270.4 2.247 747.2 180.9 3.78 734.3 202.6 3.35 719.7 228.7 2.93 688.3 253.3 2.55 648.8 264.8 2.31

8 767.6 183.9 3.83 754.1 205.8 3.39 738.9 229.8 3.00 704.5 253.0 2.61 654.9 259.1 2.38  

10 809.6 190.2 3.92 794.9 211.6 3.49 778.1 236.5 3.08 737.6 252.5 2.74 667.5 247.2 2.53  

12 852.9 197.0 4.00 837.2 217.9 3.57 816.2 240.9 3.17 770.8 256.2 2.83 679.7 235.5 2.70  

15 919.4 205.1 4.15 902.2 228.1 3.69 874.9 247.9 3.31 822.5 260.5 2.97 693.3 224.2 2.88  

15.5 930.8 206.7 4.17 913.2 229.6 3.71 884.8 249.1 3.33 831.3 261.2 2.99 694.8 222.0 2.91

4.5 725.3 178.1 3.70 713.8 201.8 3.25 700.6 229.7 2.83 681.5 260.1 2.45 656.8 279.5 2.215 735.4 179.8 3.72 723.7 202.4 3.28 710.1 230.3 2.86 689.7 260.2 2.48 664.3 279.7 2.23  

6 755.9 183.2 3.76 743.7 203.6 3.36 729.5 231.5 2.92 706.3 260.4 2.54 679.9 280.1 2.287 776.8 186.1 3.81 764.0 207.1 3.39 749.3 232.7 2.99 723.2 260.4 2.60 695.7 280.3 2.33  

8 798.1 189.2 3.85 784.8 210.7 3.43 769.5 233.9 3.05 740.3 260.5 2.66 711.9 280.5 2.3910 841.7 195.7 3.94 827.4 216.9 3.52 810.8 241.0 3.13 775.3 260.7 2.78 745.1 280.6 2.50  

12 885.9 202.4 4.02 870.9 223.5 3.61 853.5 247.7 3.21 810.8 264.6 2.87 779.2 280.7 2.6115 954.9 210.0 4.19 938.3 233.7 3.73 919.1 257.9 3.33 865.3 270.2 3.00 814.6 275.1 2.78  

15.5 966.7 211.4 4.21 949.8 235.6 3.75 930.4 259.6 3.35 874.5 271.0 3.03 817.6 272.0 2.82

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

   L   W   T   °   C

Modelo

YCIV

0590

YCIV

0630

YCIV

0700

YCIV

0760

YCIV

0800

YCIV

0830

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 527.3 134.4 3.60 511.1 148.0 3.19 492.3 161.9 2.83 471.0 176.5 2.50 448.9 192.0 2.205 535.5 134.9 3.65 519.0 148.5 3.23 500.0 162.6 2.86 478.4 177.3 2.53 456.1 193.1 2.22  

6 552.0 135.8 3.73 535.2 149.7 3.31 515.7 164.0 2.93 493.1 178.9 2.58 470.7 195.3 2.277 569.0 136.7 3.83 551.6 150.9 3.39 531.4 165.5 2.99 508.4 180.5 2.64 485.7 197.6 2.32  

8 586.0 137.8 3.91 568.3 152.2 3.46 547.4 167.0 3.06 523.8 182.2 2.70 501.1 200.0 2.36  

10 620.9 140.1 4.08 602.3 155.2 3.60 580.2 170.4 3.18 555.6 185.9 2.81 520.6 196.8 2.49  12 656.7 142.7 4.25 637.2 158.5 3.74 614.1 174.1 3.30 588.4 189.9 2.91 530.0 187.7 2.65  

15 712.9 146.4 4.50 692.2 163.4 3.95 668.2 179.4 3.49 641.1 196.2 3.08 543.1 175.1 2.90  

15.5 722.5 147.1 4.54 701.7 164.2 3.98 677.5 180.3 3.52 650.5 197.5 3.11 545.2 173.1 2.94  

4.5 566.3 142.2 3.64 551.6 158.8 3.20 534.6 175.5 2.83 515.2 192.9 2.50 495.9 211.7 2.205 575.2 142.6 3.68 560.0 159.1 3.24 542.6 176.0 2.86 522.9 193.6 2.53 503.3 212.6 2.23  

6 593.2 143.5 3.78 577.1 159.9 3.33 558.8 177.1 2.93 538.3 194.8 2.58 511.7 209.9 2.297 611.6 144.5 3.87 594.6 160.9 3.41 575.4 178.3 3.00 554.2 196.2 2.64 517.5 205.2 2.37  

8 630.3 145.6 3.96 612.4 161.9 3.49 592.3 179.5 3.07 570.3 197.6 2.70 523.4 200.4 2.4510 668.3 147.9 4.14 648.8 164.4 3.65 627.2 182.3 3.20 603.7 200.7 2.82 533.7 190.5 2.62  

12 707.6 150.6 4.31 686.6 167.3 3.80 663.5 185.3 3.34 638.7 204.2 2.93 543.2 181.8 2.7815 768.7 155.7 4.54 745.7 172.6 4.01 720.4 190.6 3.53 694.7 210.8 3.10 556.2 169.5 3.04  

15.5 779.0 156.7 4.58 755.7 173.6 4.04 730.2 191.6 3.56 704.3 212.0 3.12 558.3 167.6 3.084.5 606.2 152.2 3.63 596.2 172.4 3.18 584.2 196.3 2.77 561.5 217.6 2.41 542.0 238.2 2.14

5 614.7 153.6 3.65 604.5 172.8 3.22 592.3 196.8 2.80 568.8 217.9 2.44 548.3 238.6 2.16  

6 631.7 156.2 3.69 621.3 174.3 3.28 608.7 197.8 2.86 583.4 218.5 2.50 560.6 238.6 2.217 649.1 158.7 3.74 638.3 177.3 3.32 625.4 198.8 2.92 598.2 219.0 2.56 565.5 233.4 2.28  

8 666.7 161.2 3.78 655.7 180.2 3.36 642.3 200.3 2.98 613.4 219.5 2.62 570.8 228.3 2.35  

10 702.5 166.3 3.87 691.0 185.3 3.45 676.9 206.4 3.06 643.7 220.4 2.73 582.7 218.9 2.49  

12 739.4 171.6 3.96 727.3 190.7 3.54 710.0 210.5 3.15 673.2 224.7 2.81 594.3 209.8 2.64  

15 796.8 177.4 4.14 783.9 199.1 3.66 761.0 216.4 3.29 718.8 230.0 2.93 606.8 199.9 2.82  

15.5 806.6 178.5 4.17 793.6 200.3 3.69 769.7 217.4 3.31 726.5 230.8 2.96 608.5 198.1 2.86  

4.5 656.2 166.1 3.62 644.7 189.7 3.15 631.5 218.2 2.71 604.0 242.3 2.35 580.2 259.5 2.115 665.3 167.6 3.64 653.6 190.0 3.19 640.1 218.5 2.74 611.2 242.3 2.38 586.9 259.8 2.14  

6 683.8 170.1 3.69 671.6 191.4 3.25 657.6 219.2 2.81 625.9 242.1 2.43 600.4 260.3 2.187 702.6 172.8 3.74 689.9 194.4 3.29 675.3 219.9 2.88 640.7 241.9 2.49 614.3 260.5 2.23  

8 721.8 175.5 3.79 708.5 197.3 3.34 693.4 221.0 2.94 655.8 241.5 2.56 628.5 260.6 2.2810 761.2 181.4 3.88 746.8 202.5 3.43 730.4 227.6 3.01 686.7 240.9 2.68 643.9 251.1 2.42  

12 802.0 187.8 3.96 786.5 208.4 3.52 768.8 233.1 3.10 717.7 244.5 2.77 655.5 239.0 2.5815 865.3 196.0 4.10 848.6 218.2 3.64 820.9 237.9 3.25 765.8 248.1 2.91 668.5 227.0 2.76  

15.5 876.1 197.6 4.12 859.0 219.3 3.67 829.7 238.6 3.27 774.0 248.7 2.94 669.8 224.7 2.794.5 697.8 173.5 3.67 686.3 197.7 3.20 673.2 226.6 2.77 649.0 253.4 2.40 624.7 271.9 2.17

5 707.5 175.1 3.69 695.7 198.1 3.24 682.3 227.0 2.80 656.9 253.5 2.43 631.9 272.2 2.19  

6 727.2 178.1 3.74 714.9 199.2 3.31 700.8 227.9 2.87 672.4 253.4 2.49 643.0 270.4 2.247 747.2 180.9 3.78 734.3 202.6 3.35 719.7 228.7 2.93 688.3 253.3 2.55 648.8 264.8 2.31

8 767.6 183.9 3.83 754.1 205.8 3.39 738.9 229.8 3.00 704.5 253.0 2.61 654.9 259.1 2.38  

10 809.6 190.2 3.92 794.9 211.6 3.49 778.1 236.5 3.08 737.6 252.5 2.74 667.5 247.2 2.53  

12 852.9 197.0 4.00 837.2 217.9 3.57 816.2 240.9 3.17 770.8 256.2 2.83 679.7 235.5 2.70  

15 919.4 205.1 4.15 902.2 228.1 3.69 874.9 247.9 3.31 822.5 260.5 2.97 693.3 224.2 2.88  

15.5 930.8 206.7 4.17 913.2 229.6 3.71 884.8 249.1 3.33 831.3 261.2 2.99 694.8 222.0 2.91

4.5 725.3 178.1 3.70 713.8 201.8 3.25 700.6 229.7 2.83 681.5 260.1 2.45 656.8 279.5 2.215 735.4 179.8 3.72 723.7 202.4 3.28 710.1 230.3 2.86 689.7 260.2 2.48 664.3 279.7 2.23  

6 755.9 183.2 3.76 743.7 203.6 3.36 729.5 231.5 2.92 706.3 260.4 2.54 679.9 280.1 2.287 776.8 186.1 3.81 764.0 207.1 3.39 749.3 232.7 2.99 723.2 260.4 2.60 695.7 280.3 2.33  

8 798.1 189.2 3.85 784.8 210.7 3.43 769.5 233.9 3.05 740.3 260.5 2.66 711.9 280.5 2.3910 841.7 195.7 3.94 827.4 216.9 3.52 810.8 241.0 3.13 775.3 260.7 2.78 745.1 280.6 2.50  

12 885.9 202.4 4.02 870.9 223.5 3.61 853.5 247.7 3.21 810.8 264.6 2.87 779.2 280.7 2.6115 954.9 210.0 4.19 938.3 233.7 3.73 919.1 257.9 3.33 865.3 270.2 3.00 814.6 275.1 2.78  

15.5 966.7 211.4 4.21 949.8 235.6 3.75 930.4 259.6 3.35 874.5 271.0 3.03 817.6 272.0 2.82

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

   L   W   T   °   C

Modelo

YCIV

0590

YCIV

0630

YCIV

0700

YCIV

0760

YCIV

0800

YCIV

0830

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 39/72

 

39

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Alto Rendimiento (HE LS) con Ventiladores de Dos Velocidades - Capacidades Frigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 804.6 207.4 3.6 790.7 233.0 3.2 774.8 264.1 2.8 746.6 293.8 2.4 698.0 302.0 2.25 815.6 209.6 3.6 801.6 233.8 3.2 785.3 265.0 2.8 755.7 294.2 2.4 701.5 299.1 2.2  

6 838.3 213.3 3.6 823.5 236.5 3.2 806.6 266.7 2.8 774.0 294.9 2.5 708.4 292.9 2.37 861.2 217.1 3.7 845.9 241.1 3.3 828.3 268.4 2.9 792.7 295.7 2.5 714.9 286.4 2.4  

8 884.6 220.9 3.7 868.7 245.3 3.3 850.2 270.7 3.0 811.7 296.4 2.6 720.9 279.5 2.4  

10 932.7 228.8 3.8 915.4 253.3 3.4 893.4 279.2 3.0 850.6 298.0 2.7 730.8 265.2 2.6  

12 982.3 236.5 3.9 963.8 261.5 3.5 938.1 286.3 3.1 889.8 305.0 2.8 741.4 252.9 2.7  

15 1059.6 244.5 4.0 1039.3 273.6 3.6 1007.5 297.3 3.2 951.0 313.4 2.9 753.2 240.2 2.9  

15.5 1072.8 246.1 4.1 1052.1 275.0 3.6 1020.3 298.6 3.2 961.4 314.7 2.9 755.3 237.9 3.0  

4.5 913.5 227.8 3.7 896.2 259.5 3.2 876.0 296.4 2.8 838.7 330.2 2.4 803.1 357.7 2.15 926.4 230.0 3.7 908.8 260.1 3.2 888.2 297.1 2.8 848.9 330.4 2.4 812.6 358.2 2.1

6 952.4 233.9 3.7 934.4 261.7 3.3 913.0 298.4 2.9 869.7 330.8 2.5 831.8 359.2 2.27 978.8 237.6 3.8 960.3 265.8 3.4 938.3 299.8 2.9 890.7 331.1 2.5 851.3 360.0 2.2  

8 1005.9 241.5 3.8 986.6 270.3 3.4 964.1 301.4 3.0 911.9 331.4 2.6 871.3 360.6 2.310 1061.3 249.6 3.9 1041.1 278.1 3.5 1016.7 310.3 3.1 955.9 331.8 2.7 900.6 353.4 2.4  

12 1118.5 258.2 4.0 1097.2 286.4 3.6 1071.5 318.8 3.2 1000.2 337.1 2.8 917.8 338.0 2.615 1207.9 268.3 4.2 1185.0 299.7 3.7 1149.2 3 28.2 3.3 1068.6 344.6 2.9 938.6 321.4 2.7  

15.5 1223.2 270.2 4.2 1200.1 301.7 3.7 1161.6 329.5 3.3 1080.3 345.7 3.0 941.4 318.6 2.84.5 972.2 239.5 3.7 954.4 274.8 3.2 934.3 315.5 2.8 896.9 353.2 2.4 861.2 378.3 2.2

5 985.8 241.7 3.7 967.7 275.2 3.3 947.0 316.1 2.8 907.7 353.2 2.4 871.2 378.8 2.2  

6 1013.5 245.7 3.8 994.7 276.0 3.3 973.2 317.1 2.9 929.7 353.0 2.5 891.6 379.5 2.2

7 1041.6 2 49.6 3.8 1022.3 280.2 3.4 999.8 318.1 2.9 952.0 352.7 2.5 912.4 379.9 2.3  8 1070.4 253.5 3.9 1050.2 284.8 3.4 1027.1 319.3 3.0 974.8 352.3 2.6 933.4 380.1 2.3  

10 1129.5 262.1 4.0 1107.9 292.5 3.5 1082.8 3 27.9 3.1 1021.3 351.4 2.7 977.3 379.9 2.4  

12 1190.7 272.0 4.0 1167.8 300.8 3.6 1140.8 336.3 3.2 1068.4 355.4 2.8 997.3 363.4 2.6  

15 1286.8 284.0 4.2 1261.6 3 15.4 3.7 1225.9 346.5 3.3 1141.3 3 61.4 3.0 1018.8 344.0 2.8  

15.5 1303.3 286.3 4.2 1277.7 3 17.6 3.8 1239.2 347.7 3.4 1153.7 3 62.2 3.0 1021.8 341.0 2.8  

4.5 1057.1 264.7 3.7 1038.6 301.0 3.2 1017.6 344.8 2.8 974.9 382.3 2.4 937.1 409.4 2.25 1071.9 267.2 3.7 1052.9 301.6 3.2 1031.4 345.5 2.8 986.6 382.4 2.4 947.7 409.9 2.2  

6 1101.7 271.7 3.7 1082.0 304.1 3.3 1059.5 346.9 2.9 1009.8 382.3 2.5 964.6 407.5 2.27 1132.3 276.0 3.8 1111.6 309.2 3.3 1088.2 348.3 2.9 1033.6 382.1 2.5 973.1 399.4 2.3  

8 1163.5 280.5 3.8 1141.8 314.1 3.4 1117.4 350.3 3.0 1057.9 381.9 2.6 981.9 391.0 2.410 1227.7 290.4 3.9 1204.1 3 23.0 3.5 1176.5 360.8 3.1 1107.5 3 81.1 2.7 1000.6 373.4 2.5  

12 1294.5 300.3 4.0 1268.8 332.9 3.6 1233.0 366.8 3.2 1157.3 387.1 2.8 1018.6 355.8 2.715 1399.3 313.1 4.2 1370.4 3 48.7 3.7 1320.7 376.5 3.3 1235.3 3 93.7 3.0 1039.1 338.4 2.9  

15.5 1417.3 315.5 4.2 1387.8 350.8 3.7 1335.8 378.2 3.3 1248.6 394.7 3.0 1042.2 335.4 2.9

4.5 1198.0 303.2 3.6 1175.0 341.1 3.2 1148.5 385.6 2.8 1107.0 430.9 2.4 1079.6 474.3 2.25 1214.8 306.5 3.6 1191.5 342.4 3.2 1164.4 387.0 2.8 1121.1 431.6 2.4 1084.9 469.8 2.2  

6 1248.8 312.7 3.7 1225.0 345.3 3.3 1196.8 389.7 2.9 1149.6 432.9 2.5 1095.4 460.3 2.37 1283.5 318.6 3.7 1258.8 351.9 3.3 1229.9 392.4 2.9 1178.5 434.2 2.6 1105.7 450.3 2.3  

8 1318.8 324.4 3.8 1293.3 3 58.9 3.4 1263.6 395.3 3.0 1207.7 4 35.7 2.6 1115.6 439.8 2.4  

10 1391.2 336.4 3.8 1364.3 3 71.0 3.4 1332.0 409.0 3.1 1268.0 4 38.4 2.7 1132.2 418.7 2.5  

12 1466.0 348.9 3.9 1437.6 3 83.7 3.5 1399.2 419.9 3.1 1329.2 4 48.1 2.8 1149.3 399.3 2.7  

15 1582.2 360.9 4.1 1552.3 4 02.4 3.6 1503.8 436.1 3.3 1423.8 4 62.4 2.9 1169.0 378.7 2.9  

15.5 1601.7 363.3 4.1 1571.4 405.1 3.6 1523.1 438.1 3.3 1440.0 464.6 2.9 1172.3 375.2 2.9

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

   L   W   T   °   C

Modelo

YCIV

1220

YCIV

1380

YCIV

0930

YCIV

1050

YCIV

1120

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40 45

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 804.6 207.4 3.6 790.7 233.0 3.2 774.8 264.1 2.8 746.6 293.8 2.4 698.0 302.0 2.25 815.6 209.6 3.6 801.6 233.8 3.2 785.3 265.0 2.8 755.7 294.2 2.4 701.5 299.1 2.2  

6 838.3 213.3 3.6 823.5 236.5 3.2 806.6 266.7 2.8 774.0 294.9 2.5 708.4 292.9 2.37 861.2 217.1 3.7 845.9 241.1 3.3 828.3 268.4 2.9 792.7 295.7 2.5 714.9 286.4 2.4  

8 884.6 220.9 3.7 868.7 245.3 3.3 850.2 270.7 3.0 811.7 296.4 2.6 720.9 279.5 2.4  

10 932.7 228.8 3.8 915.4 253.3 3.4 893.4 279.2 3.0 850.6 298.0 2.7 730.8 265.2 2.6  

12 982.3 236.5 3.9 963.8 261.5 3.5 938.1 286.3 3.1 889.8 305.0 2.8 741.4 252.9 2.7  

15 1059.6 244.5 4.0 1039.3 273.6 3.6 1007.5 297.3 3.2 951.0 313.4 2.9 753.2 240.2 2.9  

15.5 1072.8 246.1 4.1 1052.1 275.0 3.6 1020.3 298.6 3.2 961.4 314.7 2.9 755.3 237.9 3.0  

4.5 913.5 227.8 3.7 896.2 259.5 3.2 876.0 296.4 2.8 838.7 330.2 2.4 803.1 357.7 2.15 926.4 230.0 3.7 908.8 260.1 3.2 888.2 297.1 2.8 848.9 330.4 2.4 812.6 358.2 2.1

6 952.4 233.9 3.7 934.4 261.7 3.3 913.0 298.4 2.9 869.7 330.8 2.5 831.8 359.2 2.27 978.8 237.6 3.8 960.3 265.8 3.4 938.3 299.8 2.9 890.7 331.1 2.5 851.3 360.0 2.2  

8 1005.9 241.5 3.8 986.6 270.3 3.4 964.1 301.4 3.0 911.9 331.4 2.6 871.3 360.6 2.310 1061.3 249.6 3.9 1041.1 278.1 3.5 1016.7 310.3 3.1 955.9 331.8 2.7 900.6 353.4 2.4  

12 1118.5 258.2 4.0 1097.2 286.4 3.6 1071.5 318.8 3.2 1000.2 337.1 2.8 917.8 338.0 2.615 1207.9 268.3 4.2 1185.0 299.7 3.7 1149.2 3 28.2 3.3 1068.6 344.6 2.9 938.6 321.4 2.7  

15.5 1223.2 270.2 4.2 1200.1 301.7 3.7 1161.6 329.5 3.3 1080.3 345.7 3.0 941.4 318.6 2.84.5 972.2 239.5 3.7 954.4 274.8 3.2 934.3 315.5 2.8 896.9 353.2 2.4 861.2 378.3 2.2

5 985.8 241.7 3.7 967.7 275.2 3.3 947.0 316.1 2.8 907.7 353.2 2.4 871.2 378.8 2.2  

6 1013.5 245.7 3.8 994.7 276.0 3.3 973.2 317.1 2.9 929.7 353.0 2.5 891.6 379.5 2.2

7 1041.6 2 49.6 3.8 1022.3 280.2 3.4 999.8 318.1 2.9 952.0 352.7 2.5 912.4 379.9 2.3  8 1070.4 253.5 3.9 1050.2 284.8 3.4 1027.1 319.3 3.0 974.8 352.3 2.6 933.4 380.1 2.3  

10 1129.5 262.1 4.0 1107.9 292.5 3.5 1082.8 3 27.9 3.1 1021.3 351.4 2.7 977.3 379.9 2.4  

12 1190.7 272.0 4.0 1167.8 300.8 3.6 1140.8 336.3 3.2 1068.4 355.4 2.8 997.3 363.4 2.6  

15 1286.8 284.0 4.2 1261.6 3 15.4 3.7 1225.9 346.5 3.3 1141.3 3 61.4 3.0 1018.8 344.0 2.8  

15.5 1303.3 286.3 4.2 1277.7 3 17.6 3.8 1239.2 347.7 3.4 1153.7 3 62.2 3.0 1021.8 341.0 2.8  

4.5 1057.1 264.7 3.7 1038.6 301.0 3.2 1017.6 344.8 2.8 974.9 382.3 2.4 937.1 409.4 2.25 1071.9 267.2 3.7 1052.9 301.6 3.2 1031.4 345.5 2.8 986.6 382.4 2.4 947.7 409.9 2.2  

6 1101.7 271.7 3.7 1082.0 304.1 3.3 1059.5 346.9 2.9 1009.8 382.3 2.5 964.6 407.5 2.27 1132.3 276.0 3.8 1111.6 309.2 3.3 1088.2 348.3 2.9 1033.6 382.1 2.5 973.1 399.4 2.3  

8 1163.5 280.5 3.8 1141.8 314.1 3.4 1117.4 350.3 3.0 1057.9 381.9 2.6 981.9 391.0 2.410 1227.7 290.4 3.9 1204.1 3 23.0 3.5 1176.5 360.8 3.1 1107.5 3 81.1 2.7 1000.6 373.4 2.5  

12 1294.5 300.3 4.0 1268.8 332.9 3.6 1233.0 366.8 3.2 1157.3 387.1 2.8 1018.6 355.8 2.715 1399.3 313.1 4.2 1370.4 3 48.7 3.7 1320.7 376.5 3.3 1235.3 3 93.7 3.0 1039.1 338.4 2.9  

15.5 1417.3 315.5 4.2 1387.8 350.8 3.7 1335.8 378.2 3.3 1248.6 394.7 3.0 1042.2 335.4 2.9

4.5 1198.0 303.2 3.6 1175.0 341.1 3.2 1148.5 385.6 2.8 1107.0 430.9 2.4 1079.6 474.3 2.25 1214.8 306.5 3.6 1191.5 342.4 3.2 1164.4 387.0 2.8 1121.1 431.6 2.4 1084.9 469.8 2.2  

6 1248.8 312.7 3.7 1225.0 345.3 3.3 1196.8 389.7 2.9 1149.6 432.9 2.5 1095.4 460.3 2.37 1283.5 318.6 3.7 1258.8 351.9 3.3 1229.9 392.4 2.9 1178.5 434.2 2.6 1105.7 450.3 2.3  

8 1318.8 324.4 3.8 1293.3 3 58.9 3.4 1263.6 395.3 3.0 1207.7 4 35.7 2.6 1115.6 439.8 2.4  

10 1391.2 336.4 3.8 1364.3 3 71.0 3.4 1332.0 409.0 3.1 1268.0 4 38.4 2.7 1132.2 418.7 2.5  

12 1466.0 348.9 3.9 1437.6 3 83.7 3.5 1399.2 419.9 3.1 1329.2 4 48.1 2.8 1149.3 399.3 2.7  

15 1582.2 360.9 4.1 1552.3 4 02.4 3.6 1503.8 436.1 3.3 1423.8 4 62.4 2.9 1169.0 378.7 2.9  

15.5 1601.7 363.3 4.1 1571.4 405.1 3.6 1523.1 438.1 3.3 1440.0 464.6 2.9 1172.3 375.2 2.9

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Temperatura de Salida del Agua

Los ventiladores funcionan a baja velocidad a 28°C de temp. ambiente e inferior.

   L   W   T   °   C

Modelo

YCIV

1220

YCIV

1380

YCIV

0930

YCIV

1050

YCIV

1120

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 40/72

 

40

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE ALTO RENDIMIENTO (HE LS) CON VENTILADORES DE DOS VELOCIDADES(VELOCIDAD ALTA INHIBIDA) - CAPACIDADES FRIGORÍFICAS

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 515.7 144.3 3.37 497.3 158.3 2.98 476.8 172.6 2.63 454.8 187.6 2.325 523.5 145.0 3.40 505.0 159.0 3.01 484.0 173.4 2.66 461.6 188.6 2.34  

6 539.4 146.4 3.48 520.2 160.8 3.07 498.5 175.4 2.71 475.5 190.5 2.397 555.5 147.9 3.55 535.7 162.6 3.13 513.3 177.3 2.76 489.7 192.7 2.43  

8 571.8 149.5 3.61 551.5 164.4 3.19 528.3 179.4 2.81 504.8 195.6 2.47  

10 605.0 153.1 3.74 583.2 168.5 3.29 558.9 183.8 2.90 535.4 202.0 2.54  

12 639.0 157.1 3.85 616.0 172.9 3.39 590.5 188.6 2.99 547.9 194.0 2.70  

15 692.5 163.2 4.03 668.3 179.3 3.55 641.3 196.0 3.13 560.8 180.8 2.96  

15.5 701.7 164.2 4.06 677.2 180.5 3.58 650.4 197.6 3.15 562.9 178.7 3.00  

4.5 556.0 154.2 3.39 539.3 171.0 2.98 520.5 188.3 2.63 500.7 206.3 2.325 564.4 154.7 3.43 547.3 171.6 3.02 528.0 189.1 2.65 508.1 207.5 2.34  

6 581.3 155.9 3.51 563.4 172.9 3.08 543.2 190.7 2.71 522.9 209.8 2.387 598.6 157.1 3.58 579.7 174.4 3.15 558.8 192.3 2.76 535.5 210.4 2.43  

8 616.1 158.5 3.66 596.4 176.0 3.21 574.7 194.1 2.82 541.6 205.5 2.5110 651.9 161.7 3.80 630.4 179.5 3.33 607.1 198.0 2.92 553.5 195.7 2.69  

12 688.9 165.4 3.93 665.8 183.5 3.44 641.1 202.3 3.02 564.2 186.4 2.8715 746.4 172.0 4.10 721.1 190.2 3.60 695.4 210.6 3.15 576.7 173.6 3.14  

15.5 756.1 173.2 4.13 730.6 191.4 3.63 700.4 209.1 3.20 578.7 171.6 3.194.5 598.5 169.9 3.31 586.8 191.7 2.90 567.7 212.6 2.54 535.0 228.3 2.24

5 606.7 171.6 3.32 594.8 192.4 2.92 574.8 213.0 2.57 541.2 228.7 2.26  6 623.3 174.9 3.35 611.0 194.7 2.97 589.2 213.8 2.62 553.7 229.5 2.307 640.1 177.9 3.39 627.3 198.8 2.99 603.7 214.6 2.68 566.4 230.2 2.35  

8 657.3 181.0 3.42 643.9 202.4 3.02 618.4 216.1 2.72 579.3 230.8 2.40  

10 692.0 187.3 3.49 677.5 208.8 3.08 648.0 222.0 2.78 602.3 230.0 2.50  

12 727.8 193.2 3.56 709.2 213.4 3.16 678.7 226.7 2.86 611.0 222.4 2.62  

15 783.5 199.7 3.72 758.3 219.9 3.28 722.1 232.8 2.96 624.5 210.7 2.82  

15.5 793.0 201.0 3.74 766.7 220.5 3.31 729.4 233.7 2.98 626.5 208.8 2.85  

4.5 646.7 188.1 3.25 633.5 214.0 2.82 612.6 239.7 2.44 570.3 251.4 2.175 655.4 189.9 3.26 642.0 214.5 2.85 619.6 239.7 2.47 576.7 251.7 2.20  

6 673.1 193.0 3.30 659.2 217.3 2.89 633.9 239.7 2.53 589.7 252.0 2.247 691.2 196.1 3.34 676.5 221.4 2.91 648.3 239.6 2.59 602.7 252.3 2.29  

8 709.6 199.3 3.37 694.1 225.0 2.94 662.7 240.6 2.63 616.2 252.3 2.3410 747.3 206.0 3.44 730.5 231.8 3.01 691.3 245.0 2.70 643.7 253.1 2.44  

12 786.3 212.2 3.52 767.3 238.6 3.07 721.0 247.9 2.78 669.1 256.1 2.5115 847.3 220.0 3.67 816.1 242.8 3.22 766.4 252.3 2.91 683.0 240.9 2.71

15.5 857.6 221.4 3.69 824.5 243.0 3.25 774.1 253.0 2.93 685.2 238.7 2.744.5 688.6 194.8 3.33 675.6 221.4 2.89 654.9 247.6 2.52 614.9 263.0 2.24

5 697.9 196.9 3.34 684.7 222.0 2.92 662.9 248.0 2.55 621.8 263.2 2.26  

6 716.8 200.3 3.38 702.9 224.5 2.97 679.2 248.7 2.60 635.7 263.6 2.317 736.1 203.6 3.41 721.4 228.8 2.99 695.7 249.4 2.66 650.0 263.8 2.36  

8 755.7 207.1 3.45 740.2 232.7 3.02 712.3 250.8 2.71 664.5 263.9 2.41

10 795.9 214.4 3.51 778.1 239.3 3.09 743.8 256.1 2.77 687.7 259.9 2.53  

12 837.5 221.3 3.59 814.8 244.8 3.17 775.7 259.5 2.86 697.3 250.4 2.66  

15 901.4 229.5 3.73 871.4 252.6 3.29 824.8 264.5 2.98 712.0 236.4 2.87  

15.5 912.3 231.0 3.75 881.2 253.4 3.32 833.2 265.3 3.00 714.3 234.4 2.90  

4.5 716.8 197.4 3.40 703.7 223.2 2.98 689.0 253.2 2.59 648.0 269.7 2.295 726.6 199.5 3.42 713.2 224.0 3.01 698.1 254.1 2.61 655.2 269.9 2.31

6 746.4 203.3 3.45 732.5 226.1 3.06 716.7 255.9 2.66 670.2 270.3 2.367 766.6 206.9 3.48 752.0 230.6 3.08 734.4 257.2 2.72 685.4 270.6 2.42  

8 787.1 210.6 3.52 771.8 234.9 3.11 751.2 257.5 2.77 700.9 270.9 2.4710 829.4 218.1 3.58 812.6 242.8 3.17 784.2 263.4 2.84 732.5 271.3 2.57  

12 872.2 225.6 3.65 854.6 250.7 3.24 818.1 267.7 2.91 763.7 276.7 2.6315 938.9 233.5 3.81 918.9 263.1 3.33 870.4 273.7 3.03 812.6 282.4 2.75  

15.5 950.3 235.0 3.83 930.0 264.5 3.35 879.1 274.7 3.05 821.0 283.3 2.77

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Tem eratura de Salida del A ua

   L   W   T   °   C

YCIV

0760

YCIV

0800

YCIV

0830

Modelo

YCIV

0590

YCIV

0630

YCIV

0700

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 515.7 144.3 3.37 497.3 158.3 2.98 476.8 172.6 2.63 454.8 187.6 2.325 523.5 145.0 3.40 505.0 159.0 3.01 484.0 173.4 2.66 461.6 188.6 2.34  

6 539.4 146.4 3.48 520.2 160.8 3.07 498.5 175.4 2.71 475.5 190.5 2.397 555.5 147.9 3.55 535.7 162.6 3.13 513.3 177.3 2.76 489.7 192.7 2.43  

8 571.8 149.5 3.61 551.5 164.4 3.19 528.3 179.4 2.81 504.8 195.6 2.47  

10 605.0 153.1 3.74 583.2 168.5 3.29 558.9 183.8 2.90 535.4 202.0 2.54  

12 639.0 157.1 3.85 616.0 172.9 3.39 590.5 188.6 2.99 547.9 194.0 2.70  

15 692.5 163.2 4.03 668.3 179.3 3.55 641.3 196.0 3.13 560.8 180.8 2.96  

15.5 701.7 164.2 4.06 677.2 180.5 3.58 650.4 197.6 3.15 562.9 178.7 3.00  

4.5 556.0 154.2 3.39 539.3 171.0 2.98 520.5 188.3 2.63 500.7 206.3 2.325 564.4 154.7 3.43 547.3 171.6 3.02 528.0 189.1 2.65 508.1 207.5 2.34  

6 581.3 155.9 3.51 563.4 172.9 3.08 543.2 190.7 2.71 522.9 209.8 2.387 598.6 157.1 3.58 579.7 174.4 3.15 558.8 192.3 2.76 535.5 210.4 2.43  

8 616.1 158.5 3.66 596.4 176.0 3.21 574.7 194.1 2.82 541.6 205.5 2.5110 651.9 161.7 3.80 630.4 179.5 3.33 607.1 198.0 2.92 553.5 195.7 2.69  

12 688.9 165.4 3.93 665.8 183.5 3.44 641.1 202.3 3.02 564.2 186.4 2.8715 746.4 172.0 4.10 721.1 190.2 3.60 695.4 210.6 3.15 576.7 173.6 3.14  

15.5 756.1 173.2 4.13 730.6 191.4 3.63 700.4 209.1 3.20 578.7 171.6 3.194.5 598.5 169.9 3.31 586.8 191.7 2.90 567.7 212.6 2.54 535.0 228.3 2.24

5 606.7 171.6 3.32 594.8 192.4 2.92 574.8 213.0 2.57 541.2 228.7 2.26  6 623.3 174.9 3.35 611.0 194.7 2.97 589.2 213.8 2.62 553.7 229.5 2.307 640.1 177.9 3.39 627.3 198.8 2.99 603.7 214.6 2.68 566.4 230.2 2.35  

8 657.3 181.0 3.42 643.9 202.4 3.02 618.4 216.1 2.72 579.3 230.8 2.40  

10 692.0 187.3 3.49 677.5 208.8 3.08 648.0 222.0 2.78 602.3 230.0 2.50  

12 727.8 193.2 3.56 709.2 213.4 3.16 678.7 226.7 2.86 611.0 222.4 2.62  

15 783.5 199.7 3.72 758.3 219.9 3.28 722.1 232.8 2.96 624.5 210.7 2.82  

15.5 793.0 201.0 3.74 766.7 220.5 3.31 729.4 233.7 2.98 626.5 208.8 2.85  

4.5 646.7 188.1 3.25 633.5 214.0 2.82 612.6 239.7 2.44 570.3 251.4 2.175 655.4 189.9 3.26 642.0 214.5 2.85 619.6 239.7 2.47 576.7 251.7 2.20  

6 673.1 193.0 3.30 659.2 217.3 2.89 633.9 239.7 2.53 589.7 252.0 2.247 691.2 196.1 3.34 676.5 221.4 2.91 648.3 239.6 2.59 602.7 252.3 2.29  

8 709.6 199.3 3.37 694.1 225.0 2.94 662.7 240.6 2.63 616.2 252.3 2.3410 747.3 206.0 3.44 730.5 231.8 3.01 691.3 245.0 2.70 643.7 253.1 2.44  

12 786.3 212.2 3.52 767.3 238.6 3.07 721.0 247.9 2.78 669.1 256.1 2.5115 847.3 220.0 3.67 816.1 242.8 3.22 766.4 252.3 2.91 683.0 240.9 2.71

15.5 857.6 221.4 3.69 824.5 243.0 3.25 774.1 253.0 2.93 685.2 238.7 2.744.5 688.6 194.8 3.33 675.6 221.4 2.89 654.9 247.6 2.52 614.9 263.0 2.24

5 697.9 196.9 3.34 684.7 222.0 2.92 662.9 248.0 2.55 621.8 263.2 2.26  

6 716.8 200.3 3.38 702.9 224.5 2.97 679.2 248.7 2.60 635.7 263.6 2.317 736.1 203.6 3.41 721.4 228.8 2.99 695.7 249.4 2.66 650.0 263.8 2.36  

8 755.7 207.1 3.45 740.2 232.7 3.02 712.3 250.8 2.71 664.5 263.9 2.41

10 795.9 214.4 3.51 778.1 239.3 3.09 743.8 256.1 2.77 687.7 259.9 2.53  

12 837.5 221.3 3.59 814.8 244.8 3.17 775.7 259.5 2.86 697.3 250.4 2.66  

15 901.4 229.5 3.73 871.4 252.6 3.29 824.8 264.5 2.98 712.0 236.4 2.87  

15.5 912.3 231.0 3.75 881.2 253.4 3.32 833.2 265.3 3.00 714.3 234.4 2.90  

4.5 716.8 197.4 3.40 703.7 223.2 2.98 689.0 253.2 2.59 648.0 269.7 2.295 726.6 199.5 3.42 713.2 224.0 3.01 698.1 254.1 2.61 655.2 269.9 2.31

6 746.4 203.3 3.45 732.5 226.1 3.06 716.7 255.9 2.66 670.2 270.3 2.367 766.6 206.9 3.48 752.0 230.6 3.08 734.4 257.2 2.72 685.4 270.6 2.42  

8 787.1 210.6 3.52 771.8 234.9 3.11 751.2 257.5 2.77 700.9 270.9 2.4710 829.4 218.1 3.58 812.6 242.8 3.17 784.2 263.4 2.84 732.5 271.3 2.57  

12 872.2 225.6 3.65 854.6 250.7 3.24 818.1 267.7 2.91 763.7 276.7 2.6315 938.9 233.5 3.81 918.9 263.1 3.33 870.4 273.7 3.03 812.6 282.4 2.75  

15.5 950.3 235.0 3.83 930.0 264.5 3.35 879.1 274.7 3.05 821.0 283.3 2.77

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Tem eratura de Salida del A ua

   L   W   T   °   C

YCIV

0760

YCIV

0800

YCIV

0830

Modelo

YCIV

0590

YCIV

0630

YCIV

0700

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 41/72

 

41

Form No. 201.26 EG 04 (ES 02/10)

Modelos de Alto Rendimiento (HE LS) con Ventiladores de Dos Velocidades (Velocidad Alta Inhibida) - CapacidadesFrigorí ficas (Continuación)

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 792.8 232.2 3.23 776.9 260.1 2.84 753.3 289.2 2.49 710.9 310.1 2.205 803.4 234.8 3.24 787.3 261.2 2.87 762.7 290.1 2.51 718.1 309.9 2.22  

6 825.1 239.4 3.27 808.2 265.3 2.90 781.9 291.9 2.56 725.9 304.4 2.297 847.2 244.1 3.29 829.4 271.1 2.92 800.0 293.2 2.61 733.5 298.5 2.35  

8 869.6 248.9 3.32 850.2 275.9 2.94 818.3 295.6 2.65 740.9 292.0 2.43  

10 915.5 258.5 3.37 892.1 284.4 3.00 854.7 303.7 2.70 753.7 278.8 2.58  

12 963.0 267.1 3.44 935.3 292.9 3.06 892.1 310.3 2.76 761.4 268.3 2.71

15 1036.8 277.2 3.57 1002.1 304.8 3.15 943.4 314.0 2.88 773.3 254.1 2.89  

15.5 1049.8 278.4 3.60 1013.4 305.9 3.18 946.7 310.2 2.93 775.5 251.9 2.93  

4.5 899.7 255.7 3.32 879.7 290.1 2.88 852.3 325.5 2.50 791.1 344.7 2.205 912.0 258.4 3.33 891.8 291.1 2.91 862.7 325.9 2.53 800.2 345.3 2.22  

6 937.2 263.1 3.36 916.2 293.7 2.96 882.7 326.6 2.58 818.5 346.2 2.267 962.7 267.8 3.40 940.8 299.6 2.99 903.2 327.2 2.64 837.3 347.1 2.31

8 988.8 272.4 3.44 965.9 305.3 3.01 923.8 328.1 2.69 856.1 347.8 2.3610 1042.2 282.0 3.50 1017.6 315.3 3.08 964.5 335.7 2.75 894.9 349.4 2.45  

12 1097.4 291.3 3.58 1071.1 325.7 3.14 1006.5 341.5 2.82 933.6 356.5 2.5115  1183.7 301.9 3.7 1143.5 335.3 3.3 1071.4 349.8 2.93 959.6 340.9 2.7  

15.5 1198.5 303.8 3.8 1155.3 335.9 3.3 1082.1 351.2 2.95 962.8 337.9 2.74.5 958.0 269.8 3.35 937.9 308.3 2.89 911.5 349.0 2.49 847.8 366.2 2.21

5 971.1 272.5 3.36 950.6 309.2 2.92 922.1 349.0 2.52 857.3 366.6 2.24  

6 997.7 277.2 3.40 976.5 311.3 2.98 943.5 349.0 2.58 876.8 367.1 2.297 1024.9 281.8 3.44 1002.5 317.1 3.01 965.2 348.9 2.64 896.7 367.5 2.34  

8 1052.6 286.4 3.47 1029.0 322.9 3.03 987.3 348.8 2.70 916.9 367.6 2.39  

10 1109.4 296.1 3.55 1083.8 332.7 3.10 1030.4 355.6 2.77 958.1 367.6 2.49  

12 1168.1 306.0 3.62 1140.6 343.0 3.17 1075.5 360.3 2.85 999.4 373.6 2.56  

15 1260.5 317.2 3.78 1220.4 354.1 3.29 1144.5 366.9 2.99 1040.8 365.2 2.73  

15.5 1276.3 319.4 3.80 1233.1 354.4 3.32 1156.2 368.0 3.01 1044.1 361.9 2.76  

4.5 1041.7 298.4 3.30 1020.8 338.2 2.87 984.7 375.4 2.51 920.9 396.5 2.225 1055.8 301.6 3.31 1034.5 339.3 2.90 996.4 375.9 2.53 931.1 396.9 2.25  

6 1084.5 306.7 3.34 1062.1 343.7 2.94 1020.2 376.7 2.59 951.7 397.5 2.297 1113.8 312.0 3.38 1090.1 350.4 2.96 1044.4 377.5 2.64 972.9 397.9 2.34  

8 1143.6 317.4 3.41 1118.7 356.4 2.99 1068.6 379.7 2.69 994.4 398.2 2.3910  1204.7 328.8 3.5 1175.2 366.4 3.1 1115.2 387.4 2.75 1029.6 393.0 2.5  

12 1268.3 338.9 3.56 1229.0 373.8 3.14 1162.9 392.7 2.83 1043.7 379.1 2.6315 1368.0 352.0 3.70 1313.0 383.9 3.27 1236.5 400.2 2.96 1065.5 357.5 2.84  

15.5 1385.1 354.4 3.72 1327.4 384.8 3.30 1249.1 401.5 2.98 1068.9 354.4 2.874.5 1178.8 337.5 3.30 1152.4 378.6 2.89 1116.2 422.2 2.53 1056.3 456.0 2.22

5 1195.0 341.5 3.31 1168.2 380.3 2.92 1130.5 423.4 2.55 1068.7 457.0 2.24  

6 1227.8 348.8 3.33 1200.0 384.8 2.97 1159.2 425.9 2.60 1094.0 458.9 2.297 1261.3 355.8 3.36 1232.2 393.4 2.98 1188.5 428.4 2.65 1120.0 460.7 2.33  

8 1295.1 363.2 3.38 1265.0 401.7 3.00 1218.0 431.5 2.70 1144.1 460.6 2.38  

10 1364.8 377.8 3.43 1330.9 416.3 3.05 1275.1 444.8 2.74 1165.4 439.4 2.54  

12 1436.7 391.9 3.49 1395.6 428.7 3.11 1333.5 455.4 2.81 1178.5 423.5 2.66  

15 1549.3 407.0 3.63 1495.6 447.1 3.20 1423.6 471.3 2.90 1197.4 400.9 2.85  

15.5 1568.4 409.4 3.65 1512.9 449.0 3.23 1439.0 473.9 2.91 1200.6 397.5 2.88  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.

EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Tem eratura de Salida del A ua

Modelo

   L   W   T   °   C

YCIV

1380

YCIV

0930

YCIV

1220

YCIV

1050

YCIV

1120

 

Temperatura de Entrada del Aire en la Batería Condensadora °C

25 30 35 40

kWo kWci EER kWo kWci EER kWo kWci EER kWo kWci EER

4.5 792.8 232.2 3.23 776.9 260.1 2.84 753.3 289.2 2.49 710.9 310.1 2.205 803.4 234.8 3.24 787.3 261.2 2.87 762.7 290.1 2.51 718.1 309.9 2.22  

6 825.1 239.4 3.27 808.2 265.3 2.90 781.9 291.9 2.56 725.9 304.4 2.297 847.2 244.1 3.29 829.4 271.1 2.92 800.0 293.2 2.61 733.5 298.5 2.35  

8 869.6 248.9 3.32 850.2 275.9 2.94 818.3 295.6 2.65 740.9 292.0 2.43  

10 915.5 258.5 3.37 892.1 284.4 3.00 854.7 303.7 2.70 753.7 278.8 2.58  

12 963.0 267.1 3.44 935.3 292.9 3.06 892.1 310.3 2.76 761.4 268.3 2.71

15 1036.8 277.2 3.57 1002.1 304.8 3.15 943.4 314.0 2.88 773.3 254.1 2.89  

15.5 1049.8 278.4 3.60 1013.4 305.9 3.18 946.7 310.2 2.93 775.5 251.9 2.93  

4.5 899.7 255.7 3.32 879.7 290.1 2.88 852.3 325.5 2.50 791.1 344.7 2.205 912.0 258.4 3.33 891.8 291.1 2.91 862.7 325.9 2.53 800.2 345.3 2.22  

6 937.2 263.1 3.36 916.2 293.7 2.96 882.7 326.6 2.58 818.5 346.2 2.267 962.7 267.8 3.40 940.8 299.6 2.99 903.2 327.2 2.64 837.3 347.1 2.31

8 988.8 272.4 3.44 965.9 305.3 3.01 923.8 328.1 2.69 856.1 347.8 2.3610 1042.2 282.0 3.50 1017.6 315.3 3.08 964.5 335.7 2.75 894.9 349.4 2.45  

12 1097.4 291.3 3.58 1071.1 325.7 3.14 1006.5 341.5 2.82 933.6 356.5 2.5115  1183.7 301.9 3.7 1143.5 335.3 3.3 1071.4 349.8 2.93 959.6 340.9 2.7  

15.5 1198.5 303.8 3.8 1155.3 335.9 3.3 1082.1 351.2 2.95 962.8 337.9 2.74.5 958.0 269.8 3.35 937.9 308.3 2.89 911.5 349.0 2.49 847.8 366.2 2.21

5 971.1 272.5 3.36 950.6 309.2 2.92 922.1 349.0 2.52 857.3 366.6 2.24  

6 997.7 277.2 3.40 976.5 311.3 2.98 943.5 349.0 2.58 876.8 367.1 2.297 1024.9 281.8 3.44 1002.5 317.1 3.01 965.2 348.9 2.64 896.7 367.5 2.34  

8 1052.6 286.4 3.47 1029.0 322.9 3.03 987.3 348.8 2.70 916.9 367.6 2.39  

10 1109.4 296.1 3.55 1083.8 332.7 3.10 1030.4 355.6 2.77 958.1 367.6 2.49  

12 1168.1 306.0 3.62 1140.6 343.0 3.17 1075.5 360.3 2.85 999.4 373.6 2.56  

15 1260.5 317.2 3.78 1220.4 354.1 3.29 1144.5 366.9 2.99 1040.8 365.2 2.73  

15.5 1276.3 319.4 3.80 1233.1 354.4 3.32 1156.2 368.0 3.01 1044.1 361.9 2.76  

4.5 1041.7 298.4 3.30 1020.8 338.2 2.87 984.7 375.4 2.51 920.9 396.5 2.225 1055.8 301.6 3.31 1034.5 339.3 2.90 996.4 375.9 2.53 931.1 396.9 2.25  

6 1084.5 306.7 3.34 1062.1 343.7 2.94 1020.2 376.7 2.59 951.7 397.5 2.297 1113.8 312.0 3.38 1090.1 350.4 2.96 1044.4 377.5 2.64 972.9 397.9 2.34  

8 1143.6 317.4 3.41 1118.7 356.4 2.99 1068.6 379.7 2.69 994.4 398.2 2.3910  1204.7 328.8 3.5 1175.2 366.4 3.1 1115.2 387.4 2.75 1029.6 393.0 2.5  

12 1268.3 338.9 3.56 1229.0 373.8 3.14 1162.9 392.7 2.83 1043.7 379.1 2.6315 1368.0 352.0 3.70 1313.0 383.9 3.27 1236.5 400.2 2.96 1065.5 357.5 2.84  

15.5 1385.1 354.4 3.72 1327.4 384.8 3.30 1249.1 401.5 2.98 1068.9 354.4 2.874.5 1178.8 337.5 3.30 1152.4 378.6 2.89 1116.2 422.2 2.53 1056.3 456.0 2.22

5 1195.0 341.5 3.31 1168.2 380.3 2.92 1130.5 423.4 2.55 1068.7 457.0 2.24  

6 1227.8 348.8 3.33 1200.0 384.8 2.97 1159.2 425.9 2.60 1094.0 458.9 2.297 1261.3 355.8 3.36 1232.2 393.4 2.98 1188.5 428.4 2.65 1120.0 460.7 2.33  

8 1295.1 363.2 3.38 1265.0 401.7 3.00 1218.0 431.5 2.70 1144.1 460.6 2.38  

10 1364.8 377.8 3.43 1330.9 416.3 3.05 1275.1 444.8 2.74 1165.4 439.4 2.54  

12 1436.7 391.9 3.49 1395.6 428.7 3.11 1333.5 455.4 2.81 1178.5 423.5 2.66  

15 1549.3 407.0 3.63 1495.6 447.1 3.20 1423.6 471.3 2.90 1197.4 400.9 2.85  

15.5 1568.4 409.4 3.65 1512.9 449.0 3.23 1439.0 473.9 2.91 1200.6 397.5 2.88  

Notas:

kWo = Capacidad frigorífica a plena carga. kWci = kW de potencia absorbida de todos los compresores.

EER = Coef. de Rendimiento Energético (incluye compresores y ventiladores).Datos en base a una diferencia de temperatura del líquido frío de 5°C.LWT = Tem eratura de Salida del A ua

Modelo

   L   W   T   °   C

YCIV

1380

YCIV

0930

YCIV

1220

YCIV

1050

YCIV

1120

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 42/72

 

42

Form No. 201.26 EG 04 (ES 02/10)

MODELOS ESTÁNDAR/ALTO RENDIMIENTO (SE & SERS/HE & HERS) - DATOS ACÚSTICOSPotencia Acústica d Plantas de Rendimiento Estándar (SE) SPL Potencia Acústica d Plantas de Rendimiento Estándar (SE RS) SPL

Mod. SWL Niveles Banda - Frecuencia Hz a Mod. SWL Niveles Banda - Frecuencia Hz a

YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m

LWA 102 75 82 93 95 96 97.4 87 77 LWA 100 73 80 91 93 94 95.4 85 75LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1LWA 103 76 83 94 96 97 98.4 88 78 LWA 99 72 79 90 92 93 94.4 84 74LW 108 102 99.1 103 99.2 97 97.2 87 79.1 LW 104 98.2 95.1 98.6 95.2 93 93.2 83 75.1LWA 104 77 84 95 97 99 99.4 89 79 LWA 100 73 80 91 93 95 95.4 85 75LW 109 103 100 104 100 99 98.2 88 80.1 LW 105 99.2 96.1 99.6 96.2 95 94.2 84 76.1LWA 103 76 83 94 96 97 98.4 88 78 LWA 99 72 79 90 92 93 94.4 84 74LW 108 102 99.1 103 99.2 97 97.2 87 79.1 LW 104 98.2 95.1 98.6 95.2 93 93.2 83 75.1LWA 106 79 86 97 99 100 101 91 81 LWA 102 75 82 93 95 96 97.4 87 77LW 111 105 102 106 102 100 100 90 82.1 LW 107 101 98.1 102 98.2 96 96.2 86 78.1LWA 105 77 85 96 98 99 100 90 80 LWA 101 73 81 92 94 95 96.4 86 76LW 110 103 101 105 101 99 99.2 89 81.1 LW 106 99.2 97.1 101 97.2 95 95.2 85 77.1LWA 105 78 85 96 98 99 100 90 80 LWA 101 74 81 92 94 95 96.4 86 76LW 110 104 101 105 101 99 99.2 89 81.1 LW 106 100 97.1 101 97.2 95 95.2 85 77.1LWA 107 59.6 73.7 82.2 101 98.5 104 95 86.4 LWA 103 56 70 78 97 94 100 91 82LW 108 85.8 89.8 90.8 104 98.5 103 94 87.5 LW 104 82 86 87 100 94 99 90 84LWA 109 60.6 74.7 83.2 103 99.8 106 96.8 86.7 LWA 105 57 71 79 99 96 102 93 83LW 109 86.8 90.8 91.8 106 99.8 105 95.8 87.8 LW 105 83 87 88 102 96 101 92 84LWA 109 58.9 75.7 78.2 106 100 105 97.1 88.5 LWA 105 55 72 74 102 96 101 93 85LW 111 85.1 91.8 86.8 109 100 104 96.1 89.6 LW 107 81 88 83 105 96 100 92 86LWA 110 59.6 76.7 79.2 107 102 103 97.8 90.7 LWA 106 56 73 75 103 98 99 94 87LW 111 85.8 92.8 87.8 110 102 102 96.8 91.8 LW 107 82 89 84 106 98 98 93 88

Los modelos X llevan ventiladores de velocidad normal, sin cubierta del compresor. Los modelos RS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada.

Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

SWL = Nive l de po tencia acúst ica ; Lw = Po tencia acúst ica SWL = Nivel de potencia acúst ica; Lw = Potencia acúst ica

Potencia Acústica d High Efficiency Chillers (HE) SPL Potencia Acústica d High Efficiency Chillers (HE RS) SPL

Mod. SWL Niveles Banda - Frecuencia Hz a Mod. SWL Niveles Banda - Frecuencia Hz a

YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m

LWA 100 73 80 91 93 94 95.4 85 75 LWA 97 70 77 88 90 91 92.4 82 72LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1 LW 102 96.2 93.1 96.6 93.2 91 91.2 81 73.1LWA 102 75 82 93 95 96 97.4 87 77 LWA 98 71 78 89 91 92 93.4 83 73LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 103 97.2 94.1 97.6 94.2 92 92.2 82 74.1LWA 102 75 82 93 95 96 97.4 87 77 LWA 98 71 78 89 92 93 93.4 83 73LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 103 97.2 94.1 97.6 95.2 93 92.2 82 74.1LWA 104 77 84 95 97 98 99.4 89 79 LWA 100 73 80 91 93 94 95.4 85 75LW 109 103 100 104 100 98 98.2 88 80.1 LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1LWA 102 75 81.9 93 95.4 95.8 97.4 86.8 77 LWA 99 70.8 78.9 89.4 91.8 93 94.2 84 73.9LW 107 101 98 102 98.6 95.8 96.2 85.8 78.1 LW 103 97 95 98 95 93 93 83 75LWA 106 79 86 97 98 100 101 91 81 LWA 102 75 82 93 94 96 97.4 87 77LW 111 105 102 106 101 100 100 90 82.1 LW 107 101 98.1 102 97.2 96 96.2 86 78.1

LWA 105 78 85 96 97 99 100 90 80 LWA 100 74 81 92 92 94 96.4 86 76LW 110 104 101 105 100 99 99.2 89 81.1 LW 106 100 97.1 101 95.2 94 95.2 85 77.1LWA 104 59.6 71.7 86.2 98.8 99.5 99.6 92 86.4 LWA 102 56 68 82 95 95 98 90 82LW 106 85.8 87.8 94.8 102 99.5 98.4 91 87.5 LW 102 82 84 91 98 95 97 89 84LWA 105 59.6 71.7 86.2 99.6 99.8 101 92.8 85.7 LWA 102 56 68 82 95 95 98 91 82LW 106 85.8 87.8 94.8 103 99.8 99.8 91.8 86.8 LW 102 82 84 91 98 95 97 90 83LWA 106 59.6 73.7 82.2 102 98.8 103 93.8 85.7 LWA 104 56 70 78 98 95 101 92 82LW 108 85.8 89.8 90.8 105 98.8 102 92.8 86.8 LW 104 82 86 87 101 95 100 91 83LWA 107 59.9 74.7 83.2 103 102 101 94.1 90.5 LWA 104 56 71 79 98 98 99 91 87LW 108 86.1 90.8 91.8 106 102 100 93.1 91.6 LW 104 82 87 88 101 98 98 90 88

Los modelos X llevan ventiladores de velocidad normal, sin cubierta del compresor. Los modelos RS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada.

Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

SWL = Nive l de po tencia acúst ica ; Lw = Po tencia acúst ica SWL = Nivel de potencia acúst ica; Lw = Potencia acúst ica

67.4

66.4

67.55

66.27

72.3

73.5

74.0

67.27

65.96

68.6

70.8

70.4

65.76

69.27

68.15

68.96

68.15

69.4

70.4

71.55

70.27

71.59

67.55

68.64

69.9373.93

75.95

76.12

76.41

67.4

69.27

69.27

71.95

72.1

72.41

64.4

65.27

71.27

69.17

72.96

71.96

0600

0650

0720

0770

0840

0920

1000

0840

0920

1000

73.27

72.15

72.15

0600

0650

0720

0770

1050

1120

1070

1180

1340

1500

1180

1340

1500

1070

1050

1120

1380

0590

0630

0700

0760

0800

0830

0930

1220

1380

1220

0590

0630

0700

0760

0800

0830

0930

 

Potencia Acústica d Plantas de Rendimiento Estándar (SE) SPL Potencia Acústica d Plantas de Rendimiento Estándar (SE RS) SPL

Mod. SWL Niveles Banda - Frecuencia Hz a Mod. SWL Niveles Banda - Frecuencia Hz a

YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m

LWA 102 75 82 93 95 96 97.4 87 77 LWA 100 73 80 91 93 94 95.4 85 75LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1LWA 103 76 83 94 96 97 98.4 88 78 LWA 99 72 79 90 92 93 94.4 84 74LW 108 102 99.1 103 99.2 97 97.2 87 79.1 LW 104 98.2 95.1 98.6 95.2 93 93.2 83 75.1LWA 104 77 84 95 97 99 99.4 89 79 LWA 100 73 80 91 93 95 95.4 85 75LW 109 103 100 104 100 99 98.2 88 80.1 LW 105 99.2 96.1 99.6 96.2 95 94.2 84 76.1LWA 103 76 83 94 96 97 98.4 88 78 LWA 99 72 79 90 92 93 94.4 84 74LW 108 102 99.1 103 99.2 97 97.2 87 79.1 LW 104 98.2 95.1 98.6 95.2 93 93.2 83 75.1LWA 106 79 86 97 99 100 101 91 81 LWA 102 75 82 93 95 96 97.4 87 77LW 111 105 102 106 102 100 100 90 82.1 LW 107 101 98.1 102 98.2 96 96.2 86 78.1LWA 105 77 85 96 98 99 100 90 80 LWA 101 73 81 92 94 95 96.4 86 76LW 110 103 101 105 101 99 99.2 89 81.1 LW 106 99.2 97.1 101 97.2 95 95.2 85 77.1LWA 105 78 85 96 98 99 100 90 80 LWA 101 74 81 92 94 95 96.4 86 76LW 110 104 101 105 101 99 99.2 89 81.1 LW 106 100 97.1 101 97.2 95 95.2 85 77.1LWA 107 59.6 73.7 82.2 101 98.5 104 95 86.4 LWA 103 56 70 78 97 94 100 91 82LW 108 85.8 89.8 90.8 104 98.5 103 94 87.5 LW 104 82 86 87 100 94 99 90 84LWA 109 60.6 74.7 83.2 103 99.8 106 96.8 86.7 LWA 105 57 71 79 99 96 102 93 83LW 109 86.8 90.8 91.8 106 99.8 105 95.8 87.8 LW 105 83 87 88 102 96 101 92 84LWA 109 58.9 75.7 78.2 106 100 105 97.1 88.5 LWA 105 55 72 74 102 96 101 93 85LW 111 85.1 91.8 86.8 109 100 104 96.1 89.6 LW 107 81 88 83 105 96 100 92 86LWA 110 59.6 76.7 79.2 107 102 103 97.8 90.7 LWA 106 56 73 75 103 98 99 94 87LW 111 85.8 92.8 87.8 110 102 102 96.8 91.8 LW 107 82 89 84 106 98 98 93 88

Los modelos X llevan ventiladores de velocidad normal, sin cubierta del compresor. Los modelos RS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada.

Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

SWL = Nive l de po tencia acúst ica ; Lw = Po tencia acúst ica SWL = Nivel de potencia acúst ica; Lw = Potencia acúst ica

Potencia Acústica d High Efficiency Chillers (HE) SPL Potencia Acústica d High Efficiency Chillers (HE RS) SPL

Mod. SWL Niveles Banda - Frecuencia Hz a Mod. SWL Niveles Banda - Frecuencia Hz a

YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m YCIV Madia 63 125 250 500 1000 2000 4000 8000 10 m

LWA 100 73 80 91 93 94 95.4 85 75 LWA 97 70 77 88 90 91 92.4 82 72LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1 LW 102 96.2 93.1 96.6 93.2 91 91.2 81 73.1LWA 102 75 82 93 95 96 97.4 87 77 LWA 98 71 78 89 91 92 93.4 83 73LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 103 97.2 94.1 97.6 94.2 92 92.2 82 74.1LWA 102 75 82 93 95 96 97.4 87 77 LWA 98 71 78 89 92 93 93.4 83 73LW 107 101 98.1 102 98.2 96 96.2 86 78.1 LW 103 97.2 94.1 97.6 95.2 93 92.2 82 74.1LWA 104 77 84 95 97 98 99.4 89 79 LWA 100 73 80 91 93 94 95.4 85 75LW 109 103 100 104 100 98 98.2 88 80.1 LW 105 99.2 96.1 99.6 96.2 94 94.2 84 76.1LWA 102 75 81.9 93 95.4 95.8 97.4 86.8 77 LWA 99 70.8 78.9 89.4 91.8 93 94.2 84 73.9LW 107 101 98 102 98.6 95.8 96.2 85.8 78.1 LW 103 97 95 98 95 93 93 83 75LWA 106 79 86 97 98 100 101 91 81 LWA 102 75 82 93 94 96 97.4 87 77LW 111 105 102 106 101 100 100 90 82.1 LW 107 101 98.1 102 97.2 96 96.2 86 78.1

LWA 105 78 85 96 97 99 100 90 80 LWA 100 74 81 92 92 94 96.4 86 76LW 110 104 101 105 100 99 99.2 89 81.1 LW 106 100 97.1 101 95.2 94 95.2 85 77.1LWA 104 59.6 71.7 86.2 98.8 99.5 99.6 92 86.4 LWA 102 56 68 82 95 95 98 90 82LW 106 85.8 87.8 94.8 102 99.5 98.4 91 87.5 LW 102 82 84 91 98 95 97 89 84LWA 105 59.6 71.7 86.2 99.6 99.8 101 92.8 85.7 LWA 102 56 68 82 95 95 98 91 82LW 106 85.8 87.8 94.8 103 99.8 99.8 91.8 86.8 LW 102 82 84 91 98 95 97 90 83LWA 106 59.6 73.7 82.2 102 98.8 103 93.8 85.7 LWA 104 56 70 78 98 95 101 92 82LW 108 85.8 89.8 90.8 105 98.8 102 92.8 86.8 LW 104 82 86 87 101 95 100 91 83LWA 107 59.9 74.7 83.2 103 102 101 94.1 90.5 LWA 104 56 71 79 98 98 99 91 87LW 108 86.1 90.8 91.8 106 102 100 93.1 91.6 LW 104 82 87 88 101 98 98 90 88

Los modelos X llevan ventiladores de velocidad normal, sin cubierta del compresor. Los modelos RS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada.

Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

SWL = Nive l de po tencia acúst ica ; Lw = Po tencia acúst ica SWL = Nivel de potencia acúst ica; Lw = Potencia acúst ica

67.4

66.4

67.55

66.27

72.3

73.5

74.0

67.27

65.96

68.6

70.8

70.4

65.76

69.27

68.15

68.96

68.15

69.4

70.4

71.55

70.27

71.59

67.55

68.64

69.9373.93

75.95

76.12

76.41

67.4

69.27

69.27

71.95

72.1

72.41

64.4

65.27

71.27

69.17

72.96

71.96

0600

0650

0720

0770

0840

0920

1000

0840

0920

1000

73.27

72.15

72.15

0600

0650

0720

0770

1050

1120

1070

1180

1340

1500

1180

1340

1500

1070

1050

1120

1380

0590

0630

0700

0760

0800

0830

0930

1220

1380

1220

0590

0630

0700

0760

0800

0830

0930

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 43/72

 

43

Form No. 201.26 EG 04 (ES 02/10)

MODELOS ESTÁNDAR/ALTO RENDIMIENTO (SELS/HELS) - DATOS ACÚSTICOSPlantas de Rendimiento Estándar (SE LS) SPL Plantas de Alto Rendimiento (HE LS) SPL

Mod. Vel. de SWL Niveles Banda - Frecuencia Hz a Mod. Vel. de SWL Niveles Banda - Frecuencia Hz a

YCIV Vent. Madia 63 125 250 500 1000 2000 4000 8000 10 m YCIV Vent. Madia 63 125 250 500 1000 2000 4000 8000 10 m

LWA 98 77 81 89 93 91 91.7 84.7 74.8 LWA 95 78 81.1 87 91 90 86 80.7 72.8LW 106 103 97.1 97.6 96.2 91 90.5 83.7 75.9 LW 106 104 97.2 95.6 94.2 90 84.8 79.7 73.9LWA 91 68.8 76 79.4 86 86 83.4 78.9 70.8 LWA 89 70 75 78.4 85 84 80.5 75.9 69.8LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 98 96.2 91.1 87 88.2 84 79.3 74.9 70.9LWA 94 75.3 79.1 85.6 89 87 87.7 80.7 70.8 LWA 96 78.3 82.1 88.6 92 90 88.3 81.7 73.8LW 104 102 95.2 94.2 92.2 87 86.5 79.7 71.9 LW 107 105 98.2 97.2 95.2 90 87.1 80.7 74.9LWA 91 68.8 76 79.4 86 86 83.4 78.9 70.8 LWA 90 69.8 74.9 78.4 85 86 81.5 76.9 70.8LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 98 96 91 87 88.2 86 80.3 75.9 71.9

LWA 95 76.3 80.1 86.6 90 88 88.7 81.7 71.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8LW 105 103 96.2 95.2 93.2 88 87.5 80.7 72.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9LWA 92 69.8 77 80.4 87 87 84.4 79.9 71.8 LWA 91 69.8 77 80.4 87 86 82.5 77.9 71.8LW 99 96 93.1 89 90.2 87 83.2 78.9 72.9 LW 99 96 93.1 89 90.2 86 81.3 76.9 72.9LWA 94 75.3 79.1 85.6 89 87 87.7 80.7 70.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8LW 104 102 95.2 94.2 92.2 87 86.5 79.7 71.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9LWA 91 68.8 76 79.4 86 86 83.4 78.9 70.8 LWA 91 71 77 80.4 87 87 82 77.9 71.8LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 100 97.2 93.1 89 90.2 87 80.8 76.9 72.9LWA 96 77.3 81.1 87.6 91 89 89.7 82.7 72.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8LW 106 104 97.2 96.2 94.2 89 88.5 81.7 73.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9LWA 93 70.8 78 81.4 88 88 85.4 80.9 72.8 LWA 91 71 77 80.4 87 87 82 77.9 71.8LW 100 97 94.1 90 91.2 88 84.2 79.9 73.9 LW 100 97.2 93.1 89 90.2 87 80.8 76.9 72.9LWA 96 77.3 81.1 87.6 91 89 89.7 82.7 72.8 LWA 95 77.3 81.1 87.6 91 89 87.3 80.7 72.8LW 106 104 97.2 96.2 94.2 89 88.5 81.7 73.9 LW 106 104 97.2 96.2 94.2 89 86.1 79.7 73.9LWA 94 71.8 79 82.4 89 89 86.4 81.9 73.8 LWA 92 72 78 81.4 88 88 83 78.9 72.8LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 101 98.2 94.1 90 91.2 88 81.8 77.9 73.9LWA 96 77.3 81.1 87 90 90.8 88.4 82.7 72.8 LWA 95 77.3 81.1 87.6 91 89 85 80.7 72.8LW 105 104 97.2 95.6 93.2 90.8 87.2 81.7 73.9 LW 106 104 97.2 96.2 94.2 89 83.8 79.7 73.9LWA 94 71.8 79 82.4 89 89 86.4 81.9 73.8 LWA 92 72 78 81.4 88 88 83 78.9 72.8LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 101 98.2 94.1 90 91.2 88 81.8 77.9 73.9LWA 96 78 82 88 93 90 86 80 75 LWA 96 78 82 88 92 90 86 80 75LW 106 104 98 97 96 90 85 79 76 LW 106 104 98 97 95 90 85 79 76LWA 93 72 79 81 91 85 81 74 69 LWA 92 72 79 82 89 86 80 74 69LW 101 98 95 90 94 85 80 73 70 LW 101 98 95 90 93 86 79 73 70LWA 97 78 82 88 94 90 86 80 75 LWA 97 78 82 89 93 90 86 80 76LW 106 104 98 97 97 90 85 79 76 LW 107 104 99 97 96 90 85 79 77LWA 94 72 79 82 92 86 82 74 69 LWA 93 72 79 82 90 86 81 74 69LW 102 98 95 90 95 86 80 73 70 LW 102 99 95 90 93 86 80 73 70LWA 99 79 83 89 97 91 87 81 76 LWA 97 79 83 89 94 91 87 80 76LW 107 105 99 97 100 91 85 80 77 LW 107 105 99 97 97 91 85 79 77LWA 97 73 80 82 96 87 82 75 70 LWA 94 73 79 82 92 86 82 74 70LW 103 99 96 91 99 87 81 74 71 LW 102 99 95 91 95 86 81 73 71LWA 99 79 83 89 97 91 87 81 76 LWA 98 79 83 89 94 91 87 81 76LW 108 105 99 98 100 91 86 80 77 LW 107 105 99 98 97 91 86 80 77LWA 97 73 80 83 96 87 81 75 70 LWA 94 73 80 83 92 87 81 75 70

LW 103 99 96 91 99 87 80 74 71 LW 102 99 96 91 95 87 80 74 71Los modelos LS llevan ventiladores de dos velocidades y cubierta del compresor insonorizada. Los modelos LS llevan ventiladores de dos velocidades y cubierta del compresor insonorizada.

Datos a velocidad normal de los ventiladores a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Datos a velocidad normal de los ventiladores a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

Datos con velocidad lenta de los ventiladores a 7°C de temp. de salida del agua fría y 25°C de temp. ambiente. Datos con velocidad lenta de los ventiladores a 7°C de temp. de salida del agua fría y 25°C de temp. ambiente.

Mod. SWL Niveles Banda - Frecuencia Hz Mod. SWL Niveles Banda - Frecuencia Hz

YCIV Madia 63 125 250 500 1000 2000 4000 8000 YCIV Madia 63 125 250 500 1000 2000 4000 8000

LWA 95 73.8 81 84.4 89 90 87.4 83.9 75.8 LWA 94 72.8 80 82 89 89 86.4 81 74.8LW 103 100 97.1 93 92.2 90 86.2 82.9 76.9 LW 102 99 96.1 90.6 92.2 89 85.2 80 75.9LWA 91 69.8 76 79 85 86 83.4 79.9 71.8 LWA 95 73.8 81 83 90 90 87.4 82 75.8LW 99 96 92.1 87.6 88.2 86 82.2 78.9 72.9 LW 103 100 97.1 91.6 93.2 90 86.2 81 76.9LWA 93 71.8 78 81 87 88 85.4 81.9 73.8 LWA 91 69.8 77 78 85 86 83.4 79.9 71.8LW 101 98 94.1 89.6 90.2 88 84.2 80.9 74.9 LW 99 96 93.1 86.6 88.2 86 82.2 78.9 72.9LWA 92 70.8 78 80 86 87 85.4 80.9 72.8 LWA 92 69.8 77 80.4 87 87 84.4 79.9 71.8LW 100 97 94.1 88.6 89.2 87 84.2 79.9 73.9 LW 99 96 93.1 89 90.2 87 83.2 78.9 72.9LWA 94 71 79 82.4 89 89 86.4 81.9 73.8 LWA 92 71 77 80.4 87 87 84.4 79.9 71.8LW 101 97.2 95.1 91 92.2 89 85.2 80.9 74.9 LW 100 97.2 93.1 89 90.2 87 83.2 78.9 72.9LWA 94 71.8 79 82.4 89 89 86.4 81.9 73.8 LWA 94 73 79 82.4 89 89 86.4 81.9 73.8LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9LWA 94 73 79 82.4 89 89 86.4 81.9 73.8 LWA 94 73 79 82.4 89 89 86.4 81.9 73.8LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9 LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9LWA 93 72 79 81 91 85 81 74 69 LWA 92 72 79 82 89 86 80 74 69LW 101 98 95 90 94 85 80 73 70 LW 101 98 95 90 93 86 79 73 70LWA 94 72 79 82 92 86 82 74 69 LWA 93 72 79 82 90 86 81 74 69LW 102 98 95 90 95 86 80 73 70 LW 102 99 95 90 93 86 80 73 70LWA 97 73 80 82 96 87 82 75 70 LWA 94 73 79 82 92 86 82 74 70LW 103 99 96 91 99 87 81 74 71 LW 102 99 95 91 95 86 81 73 71LWA 97 73 80 83 96 87 81 75 70 LWA 94 73 80 83 92 87 81 75 70LW 103 99 96 91 99 87 80 74 71 LW 103 99 96 92 95 87 80 74 71

Los modelos LS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada. Los modelos LS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada.

Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

SWL = Niv el de potencia acústica ; Lw = Potencia a cústica SWL = Nive l de potencia acústica; Lw = Potencia a cústica

Standard Efficiency Chillers (SE LS)

Normal Fan Speed InhibitedPotencia Acústica dB

High Efficiency Chillers (HE LS)

Normal Fan Speed Inhibited

60.13

61.21

61.22

0590

0590

Est. 62.95

Lent 56.77

63.5

SPL

a

10 m

SPL

a

10 m

63.6

60.75

63.6

63.87

60.75

65.6

58.34

63.36

60.34

63.24

61.21

61.21

62.36

59.34

63.41

60.13

65.33

58.47

61.49

58.47

61.36

63.04

Est.

Lent

Est.

Est.

Lent

Est.

Lent

Est.

Lent

Est.

Lent

0920

1000

1070

0600

0650

0720

0770

0840

1180

1340

1500

Est.

Lent

Est.

Lent

Est.

Lent

1500

1340

Lent

Est.

1070

1180

0650

0720

0600

Potencia Acústica dB

0630

Est. 63.82

Lent 57.52

0700Est. 61.82

Lent 58.63

0760

Est. 61.82

Lent 58.9

0800

Est. 61.69

Lent 58.77

62.41

Lent 59.77

0830

Est. 62.69

59.77

1050

Est. 63.23

Lent 59.3

Est.

1120

Est. 63.5

Lent 59.7

1220

Est. 64.1

Lent 60.8

61.33

62.38

58.23

60.11 58.08

0760 59.34

65.8

63.5

59.35

64.5

Lent 61.01380

0770

0840

0920

1000

61.44

0630 62.31

1050 59.3

0800 59.22

0830 61.22

0700

1380 61.1

Potencia Acústica dB Potencia Acústica dB

1120 59.7

1220 60.8

0930 61.22

Lent

Est.

Lent

Est.

0930Lent

 

Plantas de Rendimiento Estándar (SE LS) SPL Plantas de Alto Rendimiento (HE LS) SPL

Mod. Vel. de SWL Niveles Banda - Frecuencia Hz a Mod. Vel. de SWL Niveles Banda - Frecuencia Hz a

YCIV Vent. Madia 63 125 250 500 1000 2000 4000 8000 10 m YCIV Vent. Madia 63 125 250 500 1000 2000 4000 8000 10 m

LWA 98 77 81 89 93 91 91.7 84.7 74.8 LWA 95 78 81.1 87 91 90 86 80.7 72.8LW 106 103 97.1 97.6 96.2 91 90.5 83.7 75.9 LW 106 104 97.2 95.6 94.2 90 84.8 79.7 73.9LWA 91 68.8 76 79.4 86 86 83.4 78.9 70.8 LWA 89 70 75 78.4 85 84 80.5 75.9 69.8LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 98 96.2 91.1 87 88.2 84 79.3 74.9 70.9LWA 94 75.3 79.1 85.6 89 87 87.7 80.7 70.8 LWA 96 78.3 82.1 88.6 92 90 88.3 81.7 73.8LW 104 102 95.2 94.2 92.2 87 86.5 79.7 71.9 LW 107 105 98.2 97.2 95.2 90 87.1 80.7 74.9LWA 91 68.8 76 79.4 86 86 83.4 78.9 70.8 LWA 90 69.8 74.9 78.4 85 86 81.5 76.9 70.8LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 98 96 91 87 88.2 86 80.3 75.9 71.9

LWA 95 76.3 80.1 86.6 90 88 88.7 81.7 71.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8LW 105 103 96.2 95.2 93.2 88 87.5 80.7 72.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9LWA 92 69.8 77 80.4 87 87 84.4 79.9 71.8 LWA 91 69.8 77 80.4 87 86 82.5 77.9 71.8LW 99 96 93.1 89 90.2 87 83.2 78.9 72.9 LW 99 96 93.1 89 90.2 86 81.3 76.9 72.9LWA 94 75.3 79.1 85.6 89 87 87.7 80.7 70.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8LW 104 102 95.2 94.2 92.2 87 86.5 79.7 71.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9LWA 91 68.8 76 79.4 86 86 83.4 78.9 70.8 LWA 91 71 77 80.4 87 87 82 77.9 71.8LW 98 95 92.1 88 89.2 86 82.2 77.9 71.9 LW 100 97.2 93.1 89 90.2 87 80.8 76.9 72.9LWA 96 77.3 81.1 87.6 91 89 89.7 82.7 72.8 LWA 94 76.3 80.1 86.6 90 88 86.3 79.7 71.8LW 106 104 97.2 96.2 94.2 89 88.5 81.7 73.9 LW 105 103 96.2 95.2 93.2 88 85.1 78.7 72.9LWA 93 70.8 78 81.4 88 88 85.4 80.9 72.8 LWA 91 71 77 80.4 87 87 82 77.9 71.8LW 100 97 94.1 90 91.2 88 84.2 79.9 73.9 LW 100 97.2 93.1 89 90.2 87 80.8 76.9 72.9LWA 96 77.3 81.1 87.6 91 89 89.7 82.7 72.8 LWA 95 77.3 81.1 87.6 91 89 87.3 80.7 72.8LW 106 104 97.2 96.2 94.2 89 88.5 81.7 73.9 LW 106 104 97.2 96.2 94.2 89 86.1 79.7 73.9LWA 94 71.8 79 82.4 89 89 86.4 81.9 73.8 LWA 92 72 78 81.4 88 88 83 78.9 72.8LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 101 98.2 94.1 90 91.2 88 81.8 77.9 73.9LWA 96 77.3 81.1 87 90 90.8 88.4 82.7 72.8 LWA 95 77.3 81.1 87.6 91 89 85 80.7 72.8LW 105 104 97.2 95.6 93.2 90.8 87.2 81.7 73.9 LW 106 104 97.2 96.2 94.2 89 83.8 79.7 73.9LWA 94 71.8 79 82.4 89 89 86.4 81.9 73.8 LWA 92 72 78 81.4 88 88 83 78.9 72.8LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 101 98.2 94.1 90 91.2 88 81.8 77.9 73.9LWA 96 78 82 88 93 90 86 80 75 LWA 96 78 82 88 92 90 86 80 75LW 106 104 98 97 96 90 85 79 76 LW 106 104 98 97 95 90 85 79 76LWA 93 72 79 81 91 85 81 74 69 LWA 92 72 79 82 89 86 80 74 69LW 101 98 95 90 94 85 80 73 70 LW 101 98 95 90 93 86 79 73 70LWA 97 78 82 88 94 90 86 80 75 LWA 97 78 82 89 93 90 86 80 76LW 106 104 98 97 97 90 85 79 76 LW 107 104 99 97 96 90 85 79 77LWA 94 72 79 82 92 86 82 74 69 LWA 93 72 79 82 90 86 81 74 69LW 102 98 95 90 95 86 80 73 70 LW 102 99 95 90 93 86 80 73 70LWA 99 79 83 89 97 91 87 81 76 LWA 97 79 83 89 94 91 87 80 76LW 107 105 99 97 100 91 85 80 77 LW 107 105 99 97 97 91 85 79 77LWA 97 73 80 82 96 87 82 75 70 LWA 94 73 79 82 92 86 82 74 70LW 103 99 96 91 99 87 81 74 71 LW 102 99 95 91 95 86 81 73 71LWA 99 79 83 89 97 91 87 81 76 LWA 98 79 83 89 94 91 87 81 76LW 108 105 99 98 100 91 86 80 77 LW 107 105 99 98 97 91 86 80 77LWA 97 73 80 83 96 87 81 75 70 LWA 94 73 80 83 92 87 81 75 70

LW 103 99 96 91 99 87 80 74 71 LW 102 99 96 91 95 87 80 74 71Los modelos LS llevan ventiladores de dos velocidades y cubierta del compresor insonorizada. Los modelos LS llevan ventiladores de dos velocidades y cubierta del compresor insonorizada.

Datos a velocidad normal de los ventiladores a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Datos a velocidad normal de los ventiladores a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

Datos con velocidad lenta de los ventiladores a 7°C de temp. de salida del agua fría y 25°C de temp. ambiente. Datos con velocidad lenta de los ventiladores a 7°C de temp. de salida del agua fría y 25°C de temp. ambiente.

Mod. SWL Niveles Banda - Frecuencia Hz Mod. SWL Niveles Banda - Frecuencia Hz

YCIV Madia 63 125 250 500 1000 2000 4000 8000 YCIV Madia 63 125 250 500 1000 2000 4000 8000

LWA 95 73.8 81 84.4 89 90 87.4 83.9 75.8 LWA 94 72.8 80 82 89 89 86.4 81 74.8LW 103 100 97.1 93 92.2 90 86.2 82.9 76.9 LW 102 99 96.1 90.6 92.2 89 85.2 80 75.9LWA 91 69.8 76 79 85 86 83.4 79.9 71.8 LWA 95 73.8 81 83 90 90 87.4 82 75.8LW 99 96 92.1 87.6 88.2 86 82.2 78.9 72.9 LW 103 100 97.1 91.6 93.2 90 86.2 81 76.9LWA 93 71.8 78 81 87 88 85.4 81.9 73.8 LWA 91 69.8 77 78 85 86 83.4 79.9 71.8LW 101 98 94.1 89.6 90.2 88 84.2 80.9 74.9 LW 99 96 93.1 86.6 88.2 86 82.2 78.9 72.9LWA 92 70.8 78 80 86 87 85.4 80.9 72.8 LWA 92 69.8 77 80.4 87 87 84.4 79.9 71.8LW 100 97 94.1 88.6 89.2 87 84.2 79.9 73.9 LW 99 96 93.1 89 90.2 87 83.2 78.9 72.9LWA 94 71 79 82.4 89 89 86.4 81.9 73.8 LWA 92 71 77 80.4 87 87 84.4 79.9 71.8LW 101 97.2 95.1 91 92.2 89 85.2 80.9 74.9 LW 100 97.2 93.1 89 90.2 87 83.2 78.9 72.9LWA 94 71.8 79 82.4 89 89 86.4 81.9 73.8 LWA 94 73 79 82.4 89 89 86.4 81.9 73.8LW 101 98 95.1 91 92.2 89 85.2 80.9 74.9 LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9LWA 94 73 79 82.4 89 89 86.4 81.9 73.8 LWA 94 73 79 82.4 89 89 86.4 81.9 73.8LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9 LW 102 99.2 95.1 91 92.2 89 85.2 80.9 74.9LWA 93 72 79 81 91 85 81 74 69 LWA 92 72 79 82 89 86 80 74 69LW 101 98 95 90 94 85 80 73 70 LW 101 98 95 90 93 86 79 73 70LWA 94 72 79 82 92 86 82 74 69 LWA 93 72 79 82 90 86 81 74 69LW 102 98 95 90 95 86 80 73 70 LW 102 99 95 90 93 86 80 73 70LWA 97 73 80 82 96 87 82 75 70 LWA 94 73 79 82 92 86 82 74 70LW 103 99 96 91 99 87 81 74 71 LW 102 99 95 91 95 86 81 73 71LWA 97 73 80 83 96 87 81 75 70 LWA 94 73 80 83 92 87 81 75 70LW 103 99 96 91 99 87 80 74 71 LW 103 99 96 92 95 87 80 74 71

Los modelos LS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada. Los modelos LS llevan ventiladores de velocidad normal y cubierta del compresor no insonorizada.

Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente. Todos los datos probados a 7°C de temp. de salida del agua fría y 35°C de temp. ambiente.

SWL = Niv el de potencia acústica ; Lw = Potencia a cústica SWL = Nive l de potencia acústica; Lw = Potencia a cústica

Standard Efficiency Chillers (SE LS)

Normal Fan Speed InhibitedPotencia Acústica dB

High Efficiency Chillers (HE LS)

Normal Fan Speed Inhibited

60.13

61.21

61.22

0590

0590

Est. 62.95

Lent 56.77

63.5

SPL

a

10 m

SPL

a

10 m

63.6

60.75

63.6

63.87

60.75

65.6

58.34

63.36

60.34

63.24

61.21

61.21

62.36

59.34

63.41

60.13

65.33

58.47

61.49

58.47

61.36

63.04

Est.

Lent

Est.

Est.

Lent

Est.

Lent

Est.

Lent

Est.

Lent

0920

1000

1070

0600

0650

0720

0770

0840

1180

1340

1500

Est.

Lent

Est.

Lent

Est.

Lent

1500

1340

Lent

Est.

1070

1180

0650

0720

0600

Potencia Acústica dB

0630

Est. 63.82

Lent 57.52

0700Est. 61.82

Lent 58.63

0760

Est. 61.82

Lent 58.9

0800

Est. 61.69

Lent 58.77

62.41

Lent 59.77

0830

Est. 62.69

59.77

1050

Est. 63.23

Lent 59.3

Est.

1120

Est. 63.5

Lent 59.7

1220

Est. 64.1

Lent 60.8

61.33

62.38

58.23

60.11 58.08

0760 59.34

65.8

63.5

59.35

64.5

Lent 61.01380

0770

0840

0920

1000

61.44

0630 62.31

1050 59.3

0800 59.22

0830 61.22

0700

1380 61.1

Potencia Acústica dB Potencia Acústica dB

1120 59.7

1220 60.8

0930 61.22

Lent

Est.

Lent

Est.

0930Lent

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 44/72

 

44

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE RENDIMIENTO ESTÁNDAR (SE) - DATOS FÍSICOS

Refrigerante R134a YCIV YCIV YCIV YCIV YCIV YCIV

0600 0650 0720 0770 0840 0920

Cantidad de Circuitos Frigoríficos 2 2 2 2 2 2Carga de Refrig Circuito 1/Circuito 2 kg 74/74 77/77 84/77 87/80 87/87 105/89Carga de Aceite Circuito 1/Circuito 2 kg 19/19 19/19 19/19 19/19 19/19 19/19Compresor Cantidad 2 2 2 2 2 2

Volumen de agua litros 253.6 359.6 359.6 529.9 529.9 529.9

Conexiones hidráulicas pulg 8 10 10 10 10 10Condensador Superf. frontal de la batería (Total) m

2 21.8 21.8 24.5 24.5 27.2 30refrigerado Número de hileras de tubos 3 3 3 3 3 3por aire Número de aletas por metro 669 669 669 669 669 669

Nº de Ventil. (Circuito 1/Ct 2) 4/4 4/4 5/4 5/4 5/5 6/5Ventil. Normales Mod. SE&SE RS:Caudal de aire total m

3 /s 48.8 48.8 54.9 54.9 61.0 67.1

Ventiladores de Mod.LS:Caudal total aire a vel. Normal m3 /s 48.8 48.8 54.9 54.9 61.0 67.1

Dos Velocidades Mod.LS:Caudal total aire a baja vel. m3 /s 36.6 36.6 41.2 41.2 45.8 50.3

Longitud mm 5848 5848 6966 6966 6966 8083Dimensiones Anchura mm 2241 2241 2241 2241 2241 2241

Altura mm 2384 2384 2384 2384 2384 2384Peso al embarque mod. SE kg 5216 5619 5818 6295 6524 6692

Mod. SE: Peso en funcionamiento kg 5470 5979 6178 6825 6940 7222Peso extra modelos RS kg 260 260 260 260 260 260Peso extra modelos LS kg 325 325 325 325 325 325Peso extra aletas de cobre kg 725 725 910 910 910 1085

Refrigerante R134a YCIV YCIV YCIV YCIV YCIV

1000 1070 1180 1340 1500

Cantidad de Circuitos Frigoríficos 2 3 3 3 3

Carga de RefrigCircuito 1/Circuito 2

Circuito 3kg

105/105 84/77/ 77

84/84/ 77

84/84/ 105

105/105 /105

Carga de AceiteCircuito 1/Circuito 2

Circuito 3

kg 19/1919/15/ 

15

19/19/ 

15

19/19/ 

19

19/19/ 

19Compresor Cantidad 2 3 3 3 3Volumen de agua litros 529.9 764.6 893.3 893.3 893.3Conexiones hidráulicas pulg 10 10 10 10 10

Condensador Superf. frontal de la batería (Total) m2 32.7 35 38 44 49

refrigerado Número de hileras de tubos 3 3 3 3 3por aire Número de aletas por metro 669 669 669 669 669

Nº de Ventil. (Circuito 1/Ct 2) 6/6 5/4/4 5/5/4 5/5/6 6/6/6Ventil. Normales Mod. SE&SE RS:Caudal de aire total m

3 /s 73.2 79.3 85.4 97.6 109.8

Ventiladores de Mod.LS:Caudal total aire a vel. Normal m3 /s 73.2 79.3 85.4 97.6 109.8

Dos Velocidades Mod.LS:Caudal total aire a baja vel. m3 /s 54.9 59.5 64.1 73.2 82.4

Longitud mm 8083 9581 9581 10699 11816Dimensiones Anchura mm 2241 2241 2241 2241 2241

Altura mm 2384 2384 2384 2384 2384Peso al embarque mod. SE kg 6768 9633 10137 10638 11075Mod. SE: Peso en funcionamiento kg 7298 10437 11077 11577 12014Peso extra modelos RS kg 260 520 520 520 520Peso extra modelos LS kg 325 640 640 640 640Peso extra aletas de cobre kg 1085 1179 1270 1451 1632

Evaporador

Peso

Plantas de Rendimiento Estándar

Plantas de Rendimiento Estándar

Evaporador

Peso

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 45/72

 

45

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE ALTO RENDIMIENTO (HE) - DATOS FÍSICOS

Refrigerante R134a YCIV YCIV YCIV YCIV YCIV YCIV

0590 0630 0700 0760 0800 0830

Cantidad de Circuitos Frigoríficos 2 2 2 2 2 2Carga de Refrig Circuito 1/Circuito 2 kg 77/77 84/77 84/84 87/87 102/87 102/102Carga de Aceite Circuito 1/Circuito 2 kg 19/19 19/19 19/19 19/19 19/19 19/19Compresor Cantidad 2 2 2 2 2 2

Volumen de agua litros 359.6 359.6 359.6 416.4 416.4 416.4Conexiones hidráulicas pulg 10 10 10 10 10 10

Condensador Superf. frontal de la batería (Total) m2 21.8 24.5 27.2 27.2 30 32.7

refrigerado Número de hileras de tubos 3 3 3 3 3 3por aire Número de aletas por metro 669 669 669 669 669 669

Nº de Ventil. (Circuito 1/Ct 2) 4/4 5/4 5/5 5/5 6/5 6/6Ventil. Normales Mod. HE&HE RS:Caudal de aire total m

3 /s 48.8 54.9 61.0 61.0 67.1 73.2

Ventiladores de Mod.LS:Caudal total aire a vel. Normal m3 /s 48.8 54.9 61.0 61.0 67.1 73.2

Dos Velocidades Mod.LS:Caudal total aire a baja vel. m3 /s 36.6 41.2 45.8 45.8 50.3 54.9

Longitud mm 5848 6966 6966 6966 8083 8083Dimensiones Anchura mm 2241 2241 2241 2241 2241 2241

Altura mm 2384 2384 2384 2384 2384 2384Peso al embarque mod. HE kg 5708 5801 5993 6080 6342 6410Mod. HE: Peso en funcionamiento kg 5962 6161 6353 7404 6758 6826Peso extra modelos RS kg 260 260 260 260 260 260Peso extra modelos LS kg 325 325 325 325 325 325Peso extra aletas de cobre kg 725 910 910 910 1085 1085

Refrigerante R134a YCIV YCIV YCIV YCIV YCIV

0930 1050 1120 1220 1380

Cantidad de Circuitos Frigoríficos 2 3 3 3 3

Carga de RefrigCircuito 1/Circuito 2

Circuito 3kg

105/105 84/84/ 77

84/84/ 105

84/84/ 105

105/105 /105

Carga de Aceite

Circuito 1/Circuito 2

Circuito 3 kg 19/19

19/19/ 

15

19/19/ 

19

19/19/ 

19

19/19/ 

19Compresor Cantidad 2 3 3 3 3

Volumen de agua litros 529.9 764.6 764.6 893.3 893.3Conexiones hidráulicas pulg 10 10 10 10 10

Condensador Superf. frontal de la batería (Total) m2 32.7 38 44 44 49

refrigerado Número de hileras de tubos 3 3 3 3 3por aire Número de aletas por metro 669 669 669 669 669

Nº de Ventil. (Circuito 1/Ct 2) 6/6 5/5/4 5/5/6 5/5/6 6/6/6Ventil. Normales Mod. HE&HE RS:Caudal de aire total m

3 /s 73.2 85.4 97.6 97.6 109.8

Ventiladores de Mod.LS:Caudal total aire a vel. Normal m3 /s 73.2 85.4 97.6 97.6 109.8

Dos Velocidades Mod.LS:Caudal total aire a baja vel. m3 /s 54.9 64.1 73.2 73.2 82.4

Longitud mm 8083 9581 10699 10699 11816

Dimensiones Anchura mm 2241 2241 2241 2241 2241Altura mm 2384 2384 2384 2384 2384Peso al embarque mod. HE kg 6760 9755 10112 10623 11059Mod. HE: Peso en funcionamiento kg 7290 10559 10916 11562 11999Peso extra modelos RS kg 260 520 520 520 520Peso extra modelos LS kg 325 640 640 640 640Peso extra aletas de cobre kg 1085 1270 1360 1451 1632

Evaporador

Peso

Plantas Enfriadoras de Alto Rendimiento

Plantas Enfriadoras de Alto Rendimiento

Evaporador

Peso

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 46/72

 

46

Form No. 201.26 EG 04 (ES 02/10)

MODELOS DE RENDIMIENTO ESTÁNDAR (SE) - CARACTERÍSTICAS ELÉCTRICAS

MODELOS DE ALTO RENDIMIENTO (HE) - CARACTERÍSTICAS ELÉCTRICAS

YCIV Intensidad Nominal(1)

Intensidad

Máxima(2)

Modelo Vent Estn Vent 2 Velo Vent. Alta Pres Est Vent Estn Vent 2 Velo Vent. Alta Pres Est Todos los Ven

0600 313 334 362 173 184 198 3930650 343 360 392 220 230 245 3870720 367 394 423 228 216 259 4380770 400 411 462 228 231 259 446

0840 419 450 481 227 242 258 4850920 461 496 536 268 286 305 5401000 491 524 553 266 283 303 5981070 543 576 630 416 439 472 6151180 595 632 682 420 442 476 6721340 669 718 774 475 508 543 7811500 724 775 799 512 549 587 897

(1) Intensidad Nominal (Amps) a 35oC de temp. ambiente y 7oC de temp. de salida del agua enfriada 400V.c.a.(2) La Intensidad Máxima es el consumo máximo (Amps) antes de que el compresor

descargue y es la condición que debe utilizarse para el dimensionado de los cables eléctricos.

Intensidad de Arranque Típica de los Compresores (4 primeros segundos al arranque):Tensión Nominal Intensidad de Arranque Típica por Compresor380-400/50/3 17A

Intensidad Instantáneo Máxima

La intensidad de arranque del circuito frigorífico es menor que la intensidad nominal, debido aluso de tecnología de Variador de Velocidad.

YCIV Intensidad Nominal(1)

Intensidad

Máxima(2)

Modelo Vent Estn Vent 2 Velo Vent. Alta Pres Est Vent Estn Vent 2 Velo Vent. Alta Pres Est Todos los Ven

0590 289 306 338 161 170 186 3630630 311 323 373 179 186 210 3850700 342 361 404 218 232 249 4150760 371 398 433 203 216 234 4490800 390 411 465 219 231 256 4680830 397 424 472 216 229 253 4910930 445 471 513 269 286 306 5371050 509 545 596 388 411 450 6241120 539 572 632 376 401 438 6591220 588 631 693 414 443 476 7021380 640 679 715 490 521 565 803

(1) Intensidad Nominal (Amps) a 35oC de temp. ambiente y 7oC de temp. de salida del agua enfriada 400V.c.a.(2) La Intensidad Máxima es el consumo máximo (Amps) antes de que el compresor

descargue y es la condición que debe utilizarse para el dimensionado de los cables eléctricos.

Intensidad de Arranque Típica de los Compresores (4 primeros segundos al arranque):Tensión Nominal Intensidad de Arranque Típica por Compresor

380-400/50/3 17A

Intensidad Instantáneo Máxima

La intensidad de arranque del circuito frigorífico es menor que la intensidad nominal, debido aluso de tecnología de Variador de Velocidad.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 47/72

 

47

Form No. 201.26 EG 04 (ES 02/10)

CARACTERÍSTICAS ELÉCTRICAS (RENDIMIENTO ESTÁNDAR - 2 CIRCUITOS)

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

0600 400 50 144 4 3.1 18.0 152 4 1.9/3.8 4.5/10.30650 400 50 191 4 3.1 18.0 198 4 1.9/3.8 4.5/10.30720 400 50 195 5 3.1 18.0 180 5 1.9/3.8 4.5/10.30770 400 50 174 5 3.1 18.0 178 5 1.9/3.8 4.5/10.30840 400 50 194 5 3.1 18.0 206 5 1.9/3.8 4.5/10.30920 400 50 232 6 3.1 18.0 246 6 1.9/3.8 4.5/10.31000 400 50 230 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Nominal

Amps(3)

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

0600 400 50 144 4 3.1 18.0 152 4 1.9/3.8 4.5/10.3

0650 400 50 127 4 3.1 18.0 132 4 1.9/3.8 4.5/10.30720 400 50 144 4 3.1 18.0 180 4 1.9/3.8 4.5/10.30770 400 50 195 4 3.1 18.0 195 4 1.9/3.8 4.5/10.30840 400 50 194 5 3.1 18.0 206 5 1.9/3.8 4.5/10.30920 400 50 192 5 3.1 18.0 204 5 1.9/3.8 4.5/10.31000 400 50 230 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

Modelo Control

Intensidad No

Disrupt por

Cortoc (KA)

YCIV KVA(4) a 400 V.c.a.

Bornes/ 

Fases(1)

0600 2.4 65KA 20650 2.4 65KA 20720 2.4 65KA 20770 2.4 65KA 20840 2.4 65KA 20920 2.4 65KA 31000 2.4 65KA 3

1. Todos los equipos se suministran de serie con un solo punto de conexión eléctrica.

3. Intensidad Nominal (Amps) a 35ºC de temp. ambiente y 7ºC de temp. de salida del agua enfriada, 400 V.c.a.

4. El Control KVA incluye controles de funcionamiento y resistencias calefactoras del evaporador.

Intensidad de Arranque Típica de los Compresores (4 primeros segundos al arranque):Tensión Nominal Intensidad de Arranque Típica por Compresor

380-400/50/3 17A6. Gama de Utilización del Voltaje:

Tensión Nominal Gama de Utilización380-415/50/3 360-440

7. Los valores indicados son para velocidad Lenta (estrella) y Rápida (triángulo) respectivamente.

485540598

5. La intensidad de arranque del circuito frigorífico es menor que la intensidad nominal, debido al uso detecnología de Variador de Velocidad.

Modelo Nº./Valores Nominales Ventiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Circuito Frigorífico Nº 1

Modelo Nº./Valores Nominales

Circuito Frigorífico Nº 2

Ventiladores Cond. de 2

Velocidades

Ventiladores Cond. Estándar &

UQ

Cableado en Obra & Protección

Intensidad a Plena

Carga de Vent.

Estándar, UQ o de 2

Velocidades(2)

393387

70 - 240 mm²70 - 240 mm²

2. La Intensidad a Plena Carga es el consumo máximo de corriente antes de que el compresordescargue y es la condición que debe utilizarse para el dimensionado de los cables eléctricos.

Condiciones 7ºC de temp. de salida del agua enfriada, temp. de entrada en el condensador enaumento, bajo nivel sonoro estándar, Ventiladores supersilenciosos o de 2 velocidades, 400 V.c.a.

Multiplicar corriente por 1,02 para el funcionamiento a 360 V.c.a. Tamaño según EN60204.

95 - 195 mm²

Gama Sección Cable

70 - 240 mm²70 - 240 mm²70 - 240 mm²95 - 195 mm²

438446

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 48/72

 

48

Form No. 201.26 EG 04 (ES 02/10)

CARACTERÍSTICAS ELÉCTRICAS (RENDIMIENTO ESTÁNDAR - 3 CIRCUITOS)

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

1070 400 50 175 5 3.1 18.0 186 5 1.9/3.8 4.5/10.31180 400 50 177 5 3.1 18.0 188 5 1.9/3.8 4.5/10.3

1340 400 50 192 5 3.1 18.0 204 5 1.9/3.8 4.5/10.31500 400 50 229 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

1070 400 50 196 4 3.1 18.0 202 4 1.9/3.8 4.5/10.31180 400 50 177 5 3.1 18.0 188 5 1.9/3.8 4.5/10.31340 400 50 192 5 3.1 18.0 204 5 1.9/3.8 4.5/10.31500 400 50 229 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

1070 400 50 129 4 3.1 18.0 135 4 1.9/3.8 4.5/10.31180 400 50 198 4 3.1 18.0 203 4 1.9/3.8 4.5/10.31340 400 50 232 6 3.1 18.0 245 6 1.9/3.8 4.5/10.31500 400 50 229 6 3.1 18.0 243 6 1.9/3.8 4.5/10.3

Modelo Control

Intensidad No

Disrupt por

Cortoc (KA)

YCIV KVA(4) a 400 V.c.a.

Bornes/ 

Fases(1)

1070 2.4 65KA 41180 2.4 65KA 41340 2.4 65KA 41500 2.4 65KA 4

1. Todos los equipos se suministran de serie con un solo punto de conexión eléctrica.

3. Intensidad Nominal (Amps) a 35ºC de temp. ambiente y 7ºC de temp. de salida del agua enfriada, 400 V.c.a.

4. El Control KVA incluye controles de funcionamiento y resistencias calefactoras del evaporador.

Intensidad de Arranque Típica de los Compresores (4 primeros segundos al arranque):Tensión Nominal Intensidad de Arranque Típica por Compresor

380-400/50/3 17A6. Gama de Utilización del Voltaje:

Tensión Nominal Gama de Utilización380-415/50/3 360-440

7. Los valores indicados son para velocidad Lenta (estrella) y Rápida (triángulo) respectivamente.

120 - 240 mm²120 - 240 mm²

Cableado en Obra & Protección

Gama Sección CableIntensidad a Plena

Carga de Vent.

Estándar, UQ o de 2

Velocidades(2)

615672

Modelo Nº./Valores

NominalesVentiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Circuito Frigorífico Nº 1

Modelo Nº./Valores

Nominales

Modelo Nº./Valores

Nominales

Circuito Frigorífico Nº 2

Ventiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Ventiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Circuito Frigorífico Nº 3

2. La Intensidad a Plena Carga es el consumo máximo de corriente antes de que el compresordescargue y es la condición que debe utilizarse para el dimensionado de los cables eléctricos.

Condiciones 7ºC de temp. de salida del agua enfriada, temp. de entrada en el condensador en

aumento, bajo nivel sonoro estándar, Ventiladores supersilenciosos o de 2 velocidades, 400 V.c.a.Multiplicar corriente por 1,02 para el funcionamiento a 360 V.c.a. Tamaño según EN60204.

5. La intensidad de arranque del circuito frigorífico es menor que la intensidad nominal, debido al uso detecnología de Variador de Velocidad.

120 - 240 mm²120 - 240 mm²

781897

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 49/72

 

49

Form No. 201.26 EG 04 (ES 02/10)

CARACTERÍSTICAS ELÉCTRICAS (ALTO RENDIMIENTO - 2 CIRCUITOS)

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

0590 400 50 132 4 3.1 18.0 138 4 1.9/3.8 4.5/10.30630 400 50 134 5 3.1 18.0 139 5 1.9/3.8 4.5/10.3

0700 400 50 185 5 3.1 18.0 196 5 1.9/3.8 4.5/10.30760 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.30800 400 50 170 6 3.1 18.0 178 6 1.9/3.8 4.5/10.30830 400 50 180 6 3.1 18.0 189 6 1.9/3.8 4.5/10.30930 400 50 233 6 3.1 18.0 246 6 1.9/3.8 4.5/10.3

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

0590 400 50 132 4 3.1 18.0 138 4 1.9/3.8 4.5/10.30630 400 50 146 4 3.1 18.0 154 4 1.9/3.8 4.5/10.30700 400 50 126 5 3.1 18.0 131 5 1.9/3.8 4.5/10.30760 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.30800 400 50 183 5 3.1 18.0 195 5 1.9/3.8 4.5/10.30830 400 50 180 6 3.1 18.0 189 6 1.9/3.8 4.5/10.30930 400 50 178 6 3.1 18.0 187 6 1.9/3.8 4.5/10.3

Modelo Control

Intensidad No

Disrupt por

Cortoc (KA)

YCIV KVA(4) a 400 V.c.a.

Bornes/ 

Fases(1)

0590 2.4 65KA 20630 2.4 65KA 20700 2.4 65KA 20760 2.4 65KA 20800 2.4 65KA 20830 2.4 65KA 20930 2.4 65KA 3

1. Todos los equipos se suministran de serie con un solo punto de conexión eléctrica.

3. Intensidad Nominal (Amps) a 35ºC de temp. ambiente y 7ºC de temp. de salida del agua enfriada, 400 V.c.a.

4. El Control KVA incluye controles de funcionamiento y resistencias calefactoras del evaporador.

Intensidad de Arranque Típica de los Compresores (4 primeros segundos al arranque):Tensión Nominal Intensidad de Arranque Típica por Compresor

380-400/50/3 17A6. Gama de Utilización del Voltaje:

Tensión Nominal Gama de Utilización380-415/50/3 360-440

7. Los valores indicados son para velocidad Lenta (estrella) y Rápida (triángulo) respectivamente.

2. La Intensidad a Plena Carga es el consumo máximo de corriente antes de que el compresordescargue y es la condición que debe utilizarse para el dimensionado de los cables eléctricos.

Condiciones 7ºC de temp. de salida del agua enfriada, temp. de entrada en el condensador enaumento, bajo nivel sonoro estándar, Ventiladores supersilenciosos o de 2 velocidades, 400 V.c.a.

Multiplicar corriente por 1,02 para el funcionamiento a 360 V.c.a. Tamaño según EN60204.

70 - 240 mm²

363385415449468491537

70 - 240 mm²

70 - 240 mm²70 - 240 mm²

95 - 195 mm²

Intensidad a Plena

Carga de Vent.

Estándar, UQ o de 2

Velocidades(2)

Gama Sección Cable

70 - 240 mm²

70 - 240 mm²

5. La intensidad de arranque del circuito frigorífico es menor que la intensidad nominal, debido al uso detecnología de Variador de Velocidad.

Modelo Nº./Valores Nominales

Circuito Frigorífico Nº 1

Ventiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Modelo Nº./Valores Nominales

Circuito Frigorífico Nº 2

Ventiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Cableado en Obra & Protección

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 50/72

 

50

Form No. 201.26 EG 04 (ES 02/10)

CARACTERÍSTICAS ELÉCTRICAS (ALTO RENDIMIENTO - 3 CIRCUITOS)

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

1050 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.3

1120 400 50 164 5 3.1 18.0 173 5 1.9/3.8 4.5/10.31220 400 50 183 5 3.1 18.0 194 5 1.9/3.8 4.5/10.31380 400 50 218 6 3.1 18.0 229 6 1.9/3.8 4.5/10.3

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

1050 400 50 170 5 3.1 18.0 180 5 1.9/3.8 4.5/10.31120 400 50 164 5 3.1 18.0 173 5 1.9/3.8 4.5/10.31220 400 50 183 5 3.1 18.0 194 5 1.9/3.8 4.5/10.31380 400 50 218 6 3.1 18.0 229 6 1.9/3.8 4.5/10.3

Compresor

(Ventil Estnd &

UQ)

Compresor

(Ventil de 2

Velocidades)

YCIV Voltios(6) Frecuen

Intensidad

Nominal(3) Cantidad.

FLA

(EA)

LRA

(EA)

Intensidad

Nominal(3) Cantidad.

FLA(7)

(EA)

LRA(7)

(EA)

1050 400 50 126 4 3.1 18.0 132 4 1.9/3.8 4.5/10.31120 400 50 164 5 3.1 18.0 173 5 1.9/3.8 4.5/10.31220 400 50 169 6 3.1 18.0 178 6 1.9/3.8 4.5/10.31380 400 50 167 6 3.1 18.0 175 6 1.9/3.8 4.5/10.3

Modelo Control

Intensidad No

Disrupt porCortoc (KA)

YCIV KVA(4) a 400 V.c.a.

Bornes/ 

Fases(1)

1050 2.4 65KA 41120 2.4 65KA 41220 2.4 65KA 41380 2.4 65KA 4

1. Todos los equipos se suministran de serie con un solo punto de conexión eléctrica.

3. Intensidad Nominal (Amps) a 35ºC de temp. ambiente y 7ºC de temp. de salida del agua enfriada, 400 V.c.a.

4. El Control KVA incluye controles de funcionamiento y resistencias calefactoras del evaporador.

Intensidad de Arranque Típica de los Compresores (4 primeros segundos al arranque):Tensión Nominal Intensidad de Arranque Típica por Compresor

380-400/50/3 17A6. Gama de Utilización del Voltaje:

Tensión Nominal Gama de Utilización380-415/50/3 360-440

7. Los valores indicados son para velocidad Lenta (estrella) y Rápida (triángulo) respectivamente.

Ventiladores Cond. de 2

Velocidades

Modelo Nº./Valores

Nominales

Circuito Frigorífico Nº 3

Ventiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Modelo Nº./Valores

Nominales

Circuito Frigorífico Nº 2

Ventiladores Cond. Estándar &

UQ

Modelo Nº./Valores

Nominales

Circuito Frigorífico Nº 1

Ventiladores Cond. Estándar &

UQ

Ventiladores Cond. de 2

Velocidades

Cableado en Obra & Protección

Intensidad a Plena

Carga de Vent.

Estándar, UQ o de 2

Velocidades(2)

Gama Sección Cable

120 - 240 mm²624

2. La Intensidad a Plena Carga es el consumo máximo de corriente antes de que el compresor

descargue y es la condición que debe utilizarse para el dimensionado de los cables eléctricos.Condiciones 7ºC de temp. de salida del agua enfriada, temp. de entrada en el condensador enaumento, bajo nivel sonoro estándar, Ventiladores supersilenciosos o de 2 velocidades, 400 V.c.a.Multiplicar corriente por 1,02 para el funcionamiento a 360 V.c.a. Tamaño según EN60204.

5. La intensidad de arranque del circuito frigorífico es menor que la intensidad nominal, debido al uso detecnología de Variador de Velocidad.

120 - 240 mm²120 - 240 mm²

659702803 120 - 240 mm²

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 51/72

 

51

Form No. 201.26 EG 04 (ES 02/10)

YCIV0590HE, 0600SE Y 0650SE - DIMENSIONES

     M    o     d    e     l    o

     A

     B

     C

     D

     Y     C     I     V     0     5        9     0     H     E

     2     8     6     5 .        9

     (     1     1     2 .     8

     )

     2     1     4     6 .     3     (     8     4 .     5

     )

     4     8     4 .     5

     (     1        9 .     1

     )

     7     1     4 .     0

     (     2     8 .     1     "

     )

     Y     C     I     V     0     6     0     0     S     E

     2     7        9     6 .        9

     (     1     1     0 .     1

     )

     2     2     8     6

     (        9     0 .     0

     )

     4     4     1 .     6

     (     1     7 .     4

     )

     7     3        9 .     4

     (     2        9 .     1     "

     ) ,

     Y     C     I     V     0     6     5     0     S     E

     2     8     6     5 .        9

     (     1     1     2 .     8

     )

     2     1     4     6 .     3     (     8     4 .     5

     )

     4     8     4 .     5

     (     1        9 .     1

     )

     7     1     4 .     0

     (     2     8 .     1     "

     )

   E   l  p   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o

  r  a   d  o  r  m  a  n  o

   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r

   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s   h   i   d  r   á  u   l   i  c  a  s   d  e   l

  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e   l   d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i  e  s  e

  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s

   d  e  m  a  n  o

   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 52/72

 

52

Form No. 201.26 EG 04 (ES 02/10)

YCIV0630HE, 0720SE Y 0770SE - DIMENSIONES

     M

    o     d    e     l    o

     A

     B

     C

     D

     Y     C     I     V

     0     6     3     0     H     E

     2     8     6     5 .        9

     (     1     1     2 .     8

     )

     2     1     4     6 .     3

     (     8     4 .     5

     )

     4     8     4 .     5

     (     1        9 .     1

     )

     7     1     4 .     0

     (     2     8 .     1

     "     )

     Y     C     I     V

     0     7     2     0     S     E

     2     8     6     5 .        9

     (     1     1     2 .     8

     )

     2     1     4     6 .     3

     (     8     4 .     5

     )

     4     8     4 .     5

     (     1        9 .     1

     )

     7     1     4 .     0

     (     2     8 .     1

     "     )

     Y     C     I     V

     0     7     7     0     S     E

     2     8     7     8 .     6

     (     1     1     3 .     3

     )

     2     0     0        9 .        9

     (     7        9 .     1

     )

     5     3     5 .     3

     (     2     1 .     1

     )

     6     6     0 .     6

     (     2     6 .     0

     "     )

     D

     i    m    e    n    s     i    o    n    e    s

   E   l  p   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o

  r  a   d  o  r  m  a  n  o

   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r

   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s   h   i   d  r   á  u   l   i  c  a  s   d  e   l

  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t

  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e   l   d  e  c  o  n   t  r  o   l .   D  e

  s  e  r   i  e  s  e

  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s

   d  e  m  a  n  o

   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 53/72

 

53

Form No. 201.26 EG 04 (ES 02/10)

YCIV0700HE, 0760HE Y 0840SE - DIMENSIONES

     M    o     d    e     l    o

     A

     B

     C

     D

     Y     C     I     V     0     7     0     0     H     E

     2     8     6     5 .        9

     (     1     1     2 .     8

     )

     2     1     4     6 .     3

     (     8     4 .     5

     )

     4     8     4 .     5

     (     1        9 .     1

     )

     7     1     4 .     0

     (     2     8 .     1

     "     )

     Y     C     I     V     0     7     6     0     H     E

     2     8     5     3 .     3

     (     1     1     2 .     3

     )

     2     1     7     4 .     8

     (     8     5 .     6

     )

     5     1        9 .     4

     (     2     0 .     4

     )

     7     1     4 .     0

     (     2     8 .     1

     "     )

     Y     C     I     V     0     8     4     0     S     E

     2     8     7     8 .     6

     (     1     1     3 .     3

     )

     2     0     0        9 .        9

     (     7        9 .     1

     )

     5     3     5 .     3

     (     2     1 .     1

     )

     6     6     0 .     6

     (     2     6 .     0

     "     )

     D     i    m    e    n    s     i    o    n    e    s

   E   l  p   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o  r  a   d  o  r  m  a  n  o

   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r

   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s   h   i   d  r   á  u   l   i  c  a  s   d  e   l

  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s

   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e   l   d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i  e  s  e

  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s   d  e  m  a  n  o

   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 54/72

 

54

Form No. 201.26 EG 04 (ES 02/10)

YCIV0800HE Y 0920SE - DIMENSIONES

     M    o     d    e     l    o

     A

     B

     C

     D

     Y     C     I     V     0     8     0

     0     H     E

     2     8     5     3 .     3

     (     1     1     2 .     3

     )

     2     1     7     4 .     8

     (     [     8     5 .     6

     )

     5     1        9 .     4

     (     2     0 .     4

     )

     7     1     4 .     0

     (     2     8 .     1

     "     )

     Y     C     I     V     0        9     2

     0     S     E

     2     8     7     8 .     6

     (     1     1     3 .     3

     )

     2     0     0        9 .        9

     (     7        9 .     1

     )

     5     3     5 .     3

     (     2     1 .     1

     )

     6     6     0 .     6

     (     2     6 .     0

     "     )

     D     i    m

    e    n    s     i    o    n    e    s

   E   l  p   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o

  r  a   d  o  r  m  a  n  o

   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r

   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s   h   i   d  r   á  u   l   i  c  a  s   d  e   l

  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t

  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e   l   d  e  c  o  n   t  r  o   l .   D  e

  s  e  r   i  e  s  e

  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s

   d  e  m  a  n  o

   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 55/72

 

55

Form No. 201.26 EG 04 (ES 02/10)

YCIV0830HE, 0930HE Y 1000SE - DIMENSIONES

     M    o     d    e

     l    o

     A

     B

     C

     D

     Y     C     I     V     0     8     3     0     H     E

     2     8     5     3 .     3

     (     1     1     2 .     3

     )

     2     1     7     4 .     8

     (     8     5 .     6

     )

     5     1        9 .     4

     (     2     0 .     4

     )

     7     1     4 .     0

     (     2     8 .     1

     "     )

     Y     C     I     V     0        9     3     0     H     E

     2     8     7     8 .     6

     (     1     1     3 .     3

     )

     2     0     0        9 .        9

     (     [     7        9 .     1

     )

     5     3     5 .     3

     (     2     1 .     1

     )

     6     6     0 .     6

     (     2     6 .     0

     "     )

     Y     C     I     V     1     0     0     0     S     E

     2     8     7     8 .     6

     (     1     1     3 .     3

     )

     2     0     0        9 .        9

     (     [     7        9 .     1

     )

     5     3     5 .     3

     (     2     1 .     1

     )

     6     6     0 .     6

     (     2     6 .     0

     "     )

     D     i    m    e    n    s     i    o    n    e    s

   E   l  p   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o

  r  a   d  o  r  m  a  n  o

   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r

   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s   h   i   d  r   á  u   l   i  c

  a  s   d  e   l

  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e   l   d  e  c  o  n   t  r  o   l .   D  e

  s  e  r   i  e  s  e

  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s

   d  e  m  a  n  o

   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 56/72

 

56

Form No. 201.26 EG 04 (ES 02/10)

YCIV1050HE - DIMENSIONES

   E   l   p   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o  r  a   d  o

  r  m  a  n  o   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s

   h   i   d  r   á  u   l   i  c  a  s   d  e   l   e  v  a  p  o  r  a   d  o  r  p

  u  e   d  e  n  e  s   t  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l    l  a   d  o

   d  e

   l   p  a  n  e   l    d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i  e  s  e  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n

  e  s   d  e  m  a  n  o   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 57/72

 

57

Form No. 201.26 EG 04 (ES 02/10)

YCIV1070SE - DIMENSIONES

   E   l   p

   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o  r  a   d  o

  r  m  a  n  o   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o

  n  e  x   i  o  n  e  s

   h   i   d

  r   á  u   l   i  c  a  s   d  e   l   e  v  a  p  o  r  a   d  o  r  p

  u  e   d  e  n  e  s   t  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l    l  a   d  o

   d  e

   l   p  a  n  e   l    d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i

  e  s  e  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n

  e  s   d  e  m  a  n  o   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 58/72

 

58

Form No. 201.26 EG 04 (ES 02/10)

YCIV1120HE - DIMENSIONES

   E   l  p   l  a  n  o

  m  u  e  s   t  r  a  e  v  a  p  o  r  a   d  o  r  m  a  n  o   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r   l  a   i  n  s   t  a   l  a

  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s

   h   i   d  r   á  u   l   i  c  a  s   d  e   l  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t  a  r  a   l  a   d  e  r  e  c   h  a  o  a   l  a   i  z  q  u   i  e  r   d

  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e   l   d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i  e  s  e  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s   d  e  m  a  n  o   i  z

  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 59/72

 

59

Form No. 201.26 EG 04 (ES 02/10)

YCIV1180SE - DIMENSIONES

   E

   l   p   l  a  n  o  m  u  e  s   t  r  a  e  v  a  p  o  r  a   d  o  r  m  a  n  o   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a

  c   i   l   i   t  a  r   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o

  n  e  x   i  o  n  e  s

   h

   i   d  r   á  u   l   i  c  a  s   d  e   l   e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t  a  r  a   l  a   d  e  r  e  c   h  a

  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s   t  a  s   d  e  s   d  e  e   l    l  a   d  o

   d

  e   l   p  a  n  e   l    d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i  e  s  e  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s   d  e  m  a  n  o   i  z  q  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 60/72

 

60

Form No. 201.26 EG 04 (ES 02/10)

YCIV12200HE Y 1340SE - DIMENSIONES

   E   l  p   l  a  n  o

  m  u  e  s   t  r  a  e  v  a  p  o  r  a   d  o  r  m  a  n  o   i  z  q

  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s

   h   i   d  r   á  u   l   i  c  a  s   d  e   l  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t

  a  r  a   l  a   d  e  r  e  c   h  a  o  a   l  a   i  z  q  u   i  e  r   d  a

 ,  v   i  s   t  a  s   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e   l   d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i  e  s  e  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s   d  e  m  a  n  o   i  z  q

  u   i  e  r   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 61/72

 

61

Form No. 201.26 EG 04 (ES 02/10)

YCIV1380HE Y 1500SE - DIMENSIONES

   E   l  p   l  a  n  o

  m  u  e  s   t  r  a  e  v  a  p  o  r  a   d  o  r  m  a  n  o   i  z  q  u   i  e  r   d  a .

   P  a  r  a   f  a  c   i   l   i   t  a  r   l  a   i  n  s   t  a   l  a  c   i   ó  n ,

   l  a  s  c  o  n  e  x   i  o  n  e  s

   h   i   d  r   á  u   l   i  c  a  s   d  e   l  e  v  a  p  o  r  a   d  o  r  p  u  e   d  e  n  e  s   t  a  r

  a   l  a   d  e  r  e  c   h  a  o  a   l  a   i  z  q  u   i  e  r   d  a ,  v   i  s

   t  a  s   d  e  s   d  e  e   l   l  a   d  o

   d  e   l  p  a  n  e

   l   d  e  c  o  n   t  r  o   l .   D  e  s  e  r   i  e  s  e  s  u  m   i  n   i  s   t  r  a  n  c  o  n  e  x   i  o  n  e  s   d  e  m  a  n  o   i  z  q  u   i  e  r

   d  a .

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 62/72

 

62

Form No. 201.26 EG 04 (ES 02/10)

ENTRADA CABLES ELÉCTRICOS

   4   4   2

   2   4   4

   1

   4   8

   4   8   4

   P   R   O   F   U   C   N   D

   I   D   A   D

   A   P   E   R   T   U   R   A   1   5   0   m   m

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 63/72

 

63

Form No. 201.26 EG 04 (ES 02/10)

PÉRDIDA DE CARGA LADO AGUA CON DESRECALENTADOR OPCIONAL

10

20

30

40

50

60

160

1 2 3 4 5 6

   P   é  r   d   i   d  a   d  e

   C  a  r  g  a   k   P  a

Caudal de Agua l/s

C

B

A

1.51.25 1.75 2.5 3.5 4.5 5.5

140

120

100

80

70

15

25

Linea Cálculo de Pérdida de Carga

A Pérdida de Carga [kPa] = 11.5132 x (Caudal [l/s]^1.9187)B Pérdida de Carga [kPa] = 6.8514 x (Caudal [l/s]^1.9400)C Pérdida de Carga [kPa] = 5.6073 x (Caudal [l/s]^1.9209)

Línea Modelo

A 0590HE, 0600SE, 0630HE 0650SE0700HE, 0720SE, 0760HE, 0770SE, 0800HE,0830HE, 0840SE,1050HE, 1070SE, 1120HE,1180SE, 1220HE, 1340SE

C 0920SE, 0930HE, 1000SE, 1380HE, 1500SE

No se instalan desrecalentadores en el circuito 3 de los Modelos1050HE, 1070SE, 1120HE, 1180SE, 1220HE, 1340SE, 1380HE, 1500SE

B

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 64/72

 

64

Form No. 201.26 EG 04 (ES 02/10)

CONEXIONES HIDRÁULICAS EN DESRECALENTADOR OPCIONAL

219

ACOPLAMIENTOMACHO DE 2”

850

251

2230

PANEL DECONTROL

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 65/72

 

65

Form No. 201.26 EG 04 (ES 02/10)

ESPECIFICACIONES GUÍA DEL CONSULTOR

PARTE 1 - GENERALIDADES

1.01 ALCANCE

Los requisitos de las Condiciones Generales,Condiciones Suplementarias y Planos son aplicables atodos los trabajos que se citan en este documento.

Proporcionar plantas enfriadoras de líquido refrigeradaspor aire, con compresores de doble tornillo, controladaspor microprocesador, de las capacidades previstas taly como se indica en los planos, incluyendo pero nolimitado a:

Conjunto de planta enfriadora

Carga de refrigerante (excepto aplicaciones conevaporador remoto) y de aceite

Conexiones de alimentación eléctrica y de control

Conexiones de agua fría

Puesta en marcha por el personal del fabricante.

1.02 ASEGURAMIENTO DE LA CALIDAD

Los productos serán diseñados, probados, catalogados,certificados e instalados de conformidad con loscorrespondientes apartados de las siguientes normas ydirectivas:

Las plantas enfriadoras estarán diseñadas de acuerdocon la norma EN ISO 9002 y construidas según losrequisitos de EN ISO 9001 por una empresa acreditaday conforme a las siguientes Directivas Europeas:

Directiva sobre Maquinaria 2006/42/CEE

Directiva sobre Compatibilidad Electromagnética2004/108/CEE

Directiva sobre Recipientes a Presión 97/23/CEE

Norma de Seguridad sobre Refrigeración MecánicaEN378-2 (2008)

Prueba de Fábrica: La planta enfriadora será probada apresión, vaciada y totalmente cargada con refrigerante yaceite y será sometida a una prueba de funcionamientoen fábrica con agua fluyendo a través del evaporador.

El fabricante de la planta enfriadora deberá disponerde una organización de asistencia técnica debidamenteformada y soportada por fábrica.

Garantía: El fabricante garantizará todos los equipos ymateriales que sean de su fabricación contra defectos defabricación y materiales durante un periodo de dieciocho(18) meses a partir de la fecha de disponibilidad.

1.

2.

1.

2.

1.

2.

3.

1.03 SUMINISTRO Y MANIPULACIÓN

El equipo será entregado en obra, completamentemontado y cargado de refrigerante (excepto aplicacionescon evaporador remoto) y aceite por parte delfabricante.

Durante en envío, los componentes vulnerables llevaránuna cubierta protectora. Las boquillas/conexiones y losextremos abiertos irán cubiertos con tapas/proteccionesde plástico.

Tanto la planta enfriadora como sus accesorios iránprotegidos contra la intemperie y la suciedad durante elenvío.

El equipo será almacenado y manipulado de acuerdocon las instrucciones del Fabricante.

PARTE 2 - PRODUCTOS

2.01 GENERALIDADES

Fabricantes: El diseño que muestran los planos estábasado en York International. Se aceptarán equiposalternativos si éstos cumplen con los rendimientos

previstos y con estas especificaciones. Si hubieraequipos fabricados por un fabricante distinto al previsto,entonces el Contratista Mecánico será responsable dela coordinación con el Contratista General y con todoslos Subcontratistas afectados, para garantizar lossuministros apropiados para la instalación del equiposuministrado. Dicha coordinación incluirá, pero no estarálimitada a lo siguiente:

Soportes estructurales para los equipos.

Diámetro de las tuberías y situación de las conexiones/ cabezales.

Requisitos sobre la alimentación eléctrica y cableado/ conductos portacables, así como dimensionado de losprotectores de sobreintensidad.

Impacto del tamaño físico del grupo enfriador sobre eltrazado de la planta.

Consideraciones acústicas del lugar.

El Contratista Mecánico será responsable de todoslos gastos contraídos por el Contratista General,Subcontratistas y Asesores relativos a la modificación delas estipulaciones del edificio para aceptar los equipossuministrados.

Descripción: Instalar y poner en servicio, tal comose indica en los programas y planes, la(s) planta(s)enfriadora(s) refrigerada(s) por aire, con compresorScroll, montada(s) en fábrica, cargada(s) y probada(s),según se especifica en el presente documento. Laplanta enfriadora comprenderá, pero no se limitará a:una instalación completa con no menos de dos circuitosfrigoríficos independientes, compresores semiherméticosde doble tornillo, evaporador multitubular, condensadorrefrigerado por aire, refrigerante R134a, sistema delubricación, cableado de interconexión, controles deseguridad y funcionamiento, incluyendo el control decapacidad, centro de control, componentes de arranquedel motor y dispositivos especiales especificados eneste documento o requeridos para un funcionamientoseguro y automático.

Características de Funcionamiento:

Proporcionar alternativas de control de baja y altatemperatura ambiente, según necesidades, para

1.

2.

3.

4.

1.

1.

2.

1.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 66/72

 

66

Form No. 201.26 EG 04 (ES 02/10)

asegurarse de que la planta enfriadora pueda funcionardesde -18ºC hasta 52ºC de temperatura ambiente.

Proporcionar un sistema de control de capacidad capazde reducir la capacidad del equipo hasta un 10% paraequipos de 2 compresores y 7,5% para equipos de 3compresores de la carga total. El compresor arrancarásin carga.

Envolvente: Los paneles del equipo, elementosestructurales y base estructural gruesa serán de acero

galvanizado. Los paneles del equipo, cuadros eléctricosy base estructural están acabados a base de pintura enpolvo al horno. Todas las superficies pintadas llevaránuna capa de pintura en polvo al horno, las cuales,cuando son sometidas a los ensayos según la normaASTMB117, de 1.000 horas de duración y una prueba deniebla salina al 5%, ofrecen un valor mínimo “6” segúnASTM 1654.

El equipo se enviará en un solo bulto y el instaladordeberá proporcionar las conexiones para las tuberías deentrada y salida del evaporador. En el caso de un modelode planta enfriadora que se envíe en varios bultos, elContratista deberá proporcionar todo el material y coste

de la mano de obra en el lugar de instalación, para quepersonal autorizado de fábrica instale un kit accesoriopara conectar las piezas y todas las tuberías y cableadode interconexión.

2.02 COMPRESORES Y MOTORES

Compresores: Serán del tipo de accionamiento directo,semiherméticos, rotativos de doble tornillo, incluyendo:silenciador, resistencia calefactora “durante periodos deparo” que se activa en función de la temperatura, cajade bornes estanca (contra la intemperie), válvula deservicio de cierre de la descarga y carcasa de fundiciónmecanizada con precisión. La presión de trabajo de

diseño de todo el compresor --desde la aspiración hastala descarga-- será de 24 bar.

Motores: Motor del compresor hermético accesible,refrigerado por el propio gas de aspiración, flujo de gasde aspiración a través de filtro de malla, con proteccióninterna de sobrecarga y externa de sobreintensidad enlas tres fases.

Lubricación: Separadores de aceite externos sin piezasmóviles, con una presión de trabajo de diseño de 24 bar.La presión diferencial del circuito frigorífico proporcionaráun flujo de aceite a través de un filtro intercambiable de0,5 micras, tipo cartucho, interno al compresor. By-pass

delfi

ltro, medios menos restrictivos, o bomba de aceite,no son aceptables.

Control de Capacidad: Los compresores arrancaránen la posición de carga mínima. Proporcionar controlpor microprocesador para controlar la capacidad delcompresor y equilibrar la capacidad del mismo con lacarga frigorífica.

2.03 COMPONENTES DE LOS CIRCUITOSFRIGORÍFICOS

Cada uno de los circuitos frigoríficos comprenderá:Válvula de cierre de la línea de líquido con boca decarga, válvula de seguridad en el lado de baja, filtro

secador con elemento extraíble, mirilla con indicador dehumedad y válvula de expansión electrónica.

El fabricante de la planta enfriadora proporcionaráun circuito independiente para que cada compresorfacilite la máxima redundancia. Si la planta no disponede circuitos independientes para cada compresor, el

2.

3.

4.

1.

2.

3.

4.

1.

2.

fabricante proporcionará al propietario un compresor dereserva por cada modelo.

Se proporcionarán líneas de descarga con válvulas deservicio de cierre manual del compresor. La línea deaspiración irá recubierta de material aislante de célulacerrada

2.04 INTERCAMBIADORES DE CALOR

Evaporador:

Evaporador del tipo de expansión directa o multitubulardel tipo inundado, con tubos de cobre de alto rendimiento.Se proporcionarán circuitos frigoríficos independientespor compresor.

La presión de trabajo de diseño del evaporador seráde 10,3 bar en el lado de la carcasa y de 16 bar en ellado de los tubos (lado del refrigerante). El evaporadorestará construido y marcado conforme a la Directivasobre Recipientes a Presión y sometido a una pruebade presión de acuerdo con la Normativa de Seguridadsobre Refrigerantes EN 378.

La carcasa irá cubierta con material aislante flexible de

célula cerrada de 19 mm de espesor. Los colectoresde agua dispondrán de ranuras para acoplamientosmecánicos y serán aislados por el Contratista despuésde instalar las tuberías.

Se suministrarán accesorios de purga y vaciado, así comoresistencias calefactoras controladas termostáticamentepara proporcionar protección hasta -29ºC de temperaturaambiente en los periodos “de inactividad”.

3.

1.

2.

3.

4.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 67/72

 

67

Form No. 201.26 EG 04 (ES 02/10)

Condensador refrigerado por aire:

Baterías: De tubos de cobre sin costura, interiormenteranurados y mecánicamente expansionados en aletasde una aleación de aluminio, con collarín de máximaaltura. Se proporcionará una batería de subenfriamientocomo parte integrante del condensador. La presión detrabajo de diseño será de 24 bar.

Ventiladores: Los ventiladores estarán dinámica yestáticamente equilibrados, con accionamiento directo y

álabes de un material compuesto con refuerzo de fibrade vidrio, resistente a la corrosión, de sección totalmenteperfilada para un bajo nivel de ruido, proporcionandoasí una descarga de aire vertical a través de orificiosalargados. Las protecciones serán de tela metálicagruesa recubierta de PVC.

Motores de los ventiladores: De alto rendimiento,accionamiento directo, trifásicos, aislamiento clase “F”,con protector de sobreintensidad, del tipo totalmentecerrado “Air Over” y cojinetes de bolas con doble selladoy lubricación permanente

2.05 REQUISITOS ELÉCTRICOS

Panel de Potencia y Control:

Armarios metálicos acabados con pintura en polvo,grado de protección IP55, puertas exteriores articuladascon pestillo y junta de estanqueidad, así como puntalescontra el viento para una mayor seguridad durantelas operaciones de reparación o mantenimiento. Seproporcionará la conexión de la alimentación eléctrica,arrancadores de los compresores, contactores delos motores de los ventiladores, protectores desobreintensidad y cableado de fábrica.

El panel incluirá una puerta de acceso a la pantalla decontrol

Conexión Eléctrica de Un Solo Punto(De serie en plantas enfriadoras con 2 y 3 compresores)

Para la planta enfriadora se proporcionará una conexióneléctrica de un solo punto, trifásica y del voltajeprevisto.

En el punto de entrada de la conexión de un solo puntose facilitará un magnetotérmico que proporcione elmedio de desconexión de la corriente y de proteccióncontra cortocircuitos. El magnetotérmico irá equipadode una palanca de accionamiento bloqueable que seextenderá por la puerta del panel de potencia, de forma

que se pueda desconectar la alimentación eléctrica sinnecesidad de abrir ninguna de las puertas del panel.

Transformador de control: El panel de potencia sesuministrará con un transformador de control, montadoy cableado en fábrica, que proporcionará todo el voltajede control del equipo desde la alimentación de reddel mismo. El transformador utilizará la tensión de redprevista en el lado del primario y proporcionará 115 V/1fase en el secundario.

La intensidad de arranque no superará la intensidad aplena carga del compresor.

Los cables vistos tanto del compresor como delmotor del ventilador deberán canalizarse usando tuboportacables.

Factor de Potencia:

Los equipos irán provistos de condensadores decorrección del factor de potencia, según necesidades,

1.

2.

3.

1.

2.

1.

2.

3.

4.

5.

6.

con el fin de mantener un factor de potencia del 95% aplena carga.

El Contratista Instalador será responsable de loscostes adicionales del suministro e instalación decondensadores de corrección del factor de potencia, sino vienen montados y cableados de fábrica.

2.06 CONTROLES

Generalidades:

Proporcionar un control automático del funcionamientode la planta enfriadora, incluyendo el arranque/paro ycarga/descarga de los compresores, temporizadores deantirreciclaje, ventiladores de los condensadores, bombadel evaporador, resistencia calefactora del evaporador,contactos de las alarmas del equipo y contactos de laseñal de funcionamiento.

La planta enfriadora se reamará automáticamente yvolverá al funcionamiento normal después de un falloeléctrico.

El programa operativo del equipo se guardará enla memoria permanente. Los puntos de consigna

programados en obra se guardarán durante cinco añosen la memoria RTC (Reloj de Tiempo Real), soportadapor una pila de litio.

Se suministrarán contactos de alarmas para alertasremotas relativas a cualquier fallo de seguridad delequipo o del circuito.

Pantalla y Teclado:

Se proporcionará una pantalla de cristal líquido de 80caracteres mínimo, que pueda leerse tanto con luz solardirecta como por la noche mediante la retroiluminaciónpor LED. Cada planta enfriadora llevará incorporado un

teclado y una pantalla de lectura.La pantalla y el teclado serán accesibles a través de unapuerta de acceso, sin necesidad de abrir las puertas delarmario principal de control/eléctrico.

La pantalla facilitará, como mínimo, puntos de consigna,estado, características eléctricas, temperaturas,presiones, bloqueos de seguridad y diagnósticos delequipo, sin usar una pantalla codificada.

Valores en unidades del Sistema Métrico (o Británico).

El teclado sellado incluirá un interruptor de Marcha/Parodel equipo.

Puntos de Consigna, Datos y Seguridades

Puntos de Consigna Programables: Idioma de lectura;temperatura de salida del líquido frío: punto de consigna,campo de control; control local o remoto; unidades demedida; compresor principal/secundario; y gama dereajuste máximo del punto de consigna del agua fría.

Datos de Lectura: Temperaturas de retorno y de salidadel líquido frío; temperatura ambiente; identificación delcompresor principal; reloj y programación; (variable)fuera de límites; indicación de entrada remota; reajustedel punto de consigna del líquido frío e historial de las diez

últimas paradas por anomalía. Presiones y temperaturasde aspiración y descarga de los compresores ydel aceite, recalentamiento de la aspiración y de ladescarga, porcentaje respecto a plena carga, horas defuncionamiento, arranques y estado del temporizador deantirreciclaje. Mensajes de estado de anulación manual,desconexión del equipo, funcionamiento del compresor,

1.

2.

3.

4.

1.

2.

3.

4.

5.

1.

2.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 68/72

 

68

Form No. 201.26 EG 04 (ES 02/10)

permiso de funcionamiento, parada controlada adistancia, sin carga frigorífica, parada diaria/de festivos,temporizador de antirreciclaje.

Puntos de Control Predictivo: Los controles del equipoevitarán las paradas de seguridad cuando funcione fuerade los límites de diseño, mediante la optimización de loscontroles de la planta enfriadora y que la producciónde carga frigorífica permanezca en línea y evite que sealcancen los límites de seguridad. El sistema hará unseguimiento de los siguientes parámetros y mantendrá

la máxima producción de frío posible sin detener elequipo: consumo de los motores, presión de aspiracióny presión de descarga.

Seguridades del sistema: Harán que los sistemasindividuales de los compresores realicen paradas conrearme automático; se precisa un rearme manual despuésdel tercer disparo en 90 minutos. Las seguridadescomprenden: Alta presión o temperatura de descarga,baja presión de aspiración, alto / bajo consumo del motor,elevada temperatura del motor, presostato de alta, alta / baja presión diferencial de aceite, elevada temperaturade aceite, bajo recalentamiento de la aspiración,anomalía crítica de algún sensor, alto o bajo consumo

de corriente, pérdida de fase/alimentación monofásica,sobrecarga del devanado del motor y baja tensión.

Seguridades del equipo: Serán de rearme automáticoy harán que los compresores se paren en caso de:Alta o baja temperatura ambiente, baja temperatura desalida del líquido frío, bajo voltaje (caída de tensión) ofuncionamiento del interruptor de flujo. El Contratistasuministrará los interruptores de flujo y el cableadonecesarios de acuerdo con los requisitos del fabricante.

El fabricante suministrará todos los controles no enumeradosanteriormente, que sean necesarios para el funcionamientoautomático de la planta enfriadora. Asimismo, el Contratista

Mecánico proporcionará el cableado de control necesariopara la interconexión de los sensores al sistema de controlde la planta enfriadora.

2.07 ACCESORIOS Y OPCIONES

Algunos accesorios y opciones sustituyen a funcionesde productos estándar. Su representante YORK estaráencantado de ayudarle.

Reducción Acústica

Se facilitarán las siguientes opciones, según necesidades,para satisfacer los datos acústicos previstos en cualquiercondición de carga.

Ventiladores de velocidad normal y cubierta noinsonorizada del compresor (montaje de fábrica)

Ventiladores de dos velocidades y cubierta insonorizadadel compresor (montaje de fábrica)

Niveles de Potencia Acústica

Datos de potencia acústica medidos en la banda de octava,dB según ISO 3744, a 35ºC de temperatura ambiente y 7ºCde temperatura de salida del agua fría.

Se proporcionará una entrada de control opcional para limitar

la emisión acústica de la planta enfriadora en función dela hora del día. Será programable en el panel de la plantao controlable a distancia a través de una señal (de 4-20mA o de 0-10 V.c.c.) desde un sistema BAS (Sistema deAutomatización de Edificios). Las plantas enfriadoras queno dispongan de esta función irán provistas de la necesaria

3.

4.

5.

insonorización, a fin de ajustarse a los datos acústicosprevistos en todos los puntos de carga.

Protección Medioambiental con BateríasCondensadoras:

BATERÍAS CONDENSADORAS DE ALETAS CONPRE-RECUBRIMIENTO - Las baterías condensadorasrefrigeradas por aire están construidas a base de aletasde aluminio recubiertas de pintura epóxida.

ALETAS DE COBRE - Se suministrarán bateríascondensadoras con aletas de cobre en lugar dealuminio.

BATERÍAS CONDENSADORAS CON POST-RECUBRIMIENTO EN BAÑO EPÓXIDO - El equipoestá construido con baterías condensadoras de aletascuradas en baño epóxido.

1.

2.

3.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 69/72

 

69

Form No. 201.26 EG 04 (ES 02/10)

Paneles Protectores de la Planta (montaje de fábrica):

Paneles de Rejilla (sólo baterías condensadoras): Deacero pintado, a juego con los paneles del equipo,situados sobre las caras externas de la bateríacondensadora.

Paneles Metálicos (todo el equipo) - Protecciones detela metálica gruesa soldada y recubierta para resistirla corrosión, proteger las baterías condensadoras deeventuales daños y restringir el acceso no autorizado a

los componentes internos.Paneles de Rejilla (todo el equipo): De acero pintado,a juego con los paneles del equipo, para proteger lasbaterías condensadoras de eventuales daños, ocultarvisualmente los componentes internos y evitar el accesono autorizado a los mismos.

Paneles de Rejilla/Metálicos: Paneles de rejilla de acerosobre las caras externas de las baterías condensadoras,pintados a juego con los paneles del equipo. De telametálica gruesa, soldada, recubiertos para resistir lacorrosión y colocados alrededor de la base de la máquinapara restringir el acceso no autorizado.

Opciones del Evaporador:

Proporcionar material aislante de 38 mm en lugar de 19mm.

Proporcionar Accesorio de Bridas con Resalto para loscolectores del evaporador:

Bridas para soldar, de 10,3 bar.

Contrabridas para soldar, de 10,3 bar.

Bridas para soldar, de 20,7 bar.

Contrabridas para soldar, de 20,7 bar.

Bridas Victaulic™ de 10,3 bar (kit de obra, brida a juegopara tubería a suministrar por el Contratista).

Interruptor de Flujo (montaje en obra):

Resistente al vapor, de 10,3 bar ó 20,7 bar, de -28,9ºC a121,1ºC.

Interfaz con Sistema de Automatización de Edificios:

Planta enfriadora que admita una entrada de 4 a 20mA o de 0 a 10 V.c.c. para reajustar la temperatura desalida del líquido frío, o intensidad a plena carga en %

(limitación de la corriente). (montaje de fábrica)Se proveerá a la planta enfriadora de una microinterfazde redes para conectarse a otros sistemas que puedancompartir datos a través de BACNet™ (montaje defábrica).

1.

2.

3.

4.

1.

2.

3.

4.

5.

6.

7.

1.

2.

Montaje Antivibratorio (montaje en obra):

Soportes antivibratorios de neopreno - Soportesantivibratorios de muelle con flexión de 1”: Soportesregulables de muelle y tipo jaula, para montar debajo delas viguetas de la base del equipo.

Soportes antivibratorios de 2” contra seísmos - Soportesregulables que incorporen una robusta carcasa de acerosoldada, con topes limitadores verticales y horizontales.Las carcasas estarán diseñadas para soportar una

fuerza acelerada mínima de 1,0 gr en todas direcciones,hasta 50 mm.

Válvula de Servicio de Cierre

Se proporcionará una válvula de servicio de cierre en laaspiración para cada uno de los compresores. (montaje defábrica)

PARTE 3 - EJECUCIÓN

3.01 INSTALACIÓN

Generalidades: Montar e instalar de conformidad conlos requisitos del Fabricante, planos del proyecto y

documentos contractuales.

Emplazamiento: Situar la planta enfriadora según seindica en los planos, incluyendo los espacios necesariospara la limpieza y trabajos de mantenimiento, conformea las instrucciones del Fabricante. Regular y nivelar laplanta enfriadora sobre la estructura de soportación.

Componentes: El Contratista Instalador proporcionará einstalará todos los dispositivos auxiliares y accesoriospara una planta enfriadora totalmente operativa.

Parte Eléctrica: Coordinar las necesidades y conexioneseléctricas de todas las alimentaciones de energía con el

Contratista Eléctrico.Controles: Coordinar todas las necesidades y conexionesde control con el Contratista de Controles.

Acabado: El Contratista Instalador retocará las zonasdañadas y erosionadas, con pintura igual a la delacabado de fábrica.

1.

2.

1.

2.

3.

4.

5.

6.

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 70/72

 

70

Form No. 201.26 EG 04 (ES 02/10)

NOTAS

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 71/72

5/12/2018 YCIV_0210 - slidepdf.com

http://slidepdf.com/reader/full/yciv0210 72/72

 

FORM 201.26 EG 04 (ES 0210) Sujeto a modificación sin previoavisoRevision 4 RESERVADOSTODOSLOSDERECHOS