Memoria Explicativa Agua Consumo Humano Particular

15
 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS. SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR PROYECTO PISCICULTURA CARÉN ALTO. PROPIETARIO:  J ORGE ALEJ AN DRO NÚÑEZ CAMPOS Y COMPAÑÍA . Diciembre, 2008.

Transcript of Memoria Explicativa Agua Consumo Humano Particular

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 1/15

 

MEMORIA EXPLICATIVA Y ESPECIFICACIONESTÉCNICAS.

SISTEMA DE AGUA CONSUMO HUMANO PARTICULARPROYECTO PISCICULTURA CARÉN ALTO.

PROPIETARIO:

 J ORGE ALEJ ANDRO NÚÑEZ CAMPOS Y COMPAÑÍA.

Diciembre, 2008.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 2/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

1

 1. IDENTIFICACIÓN.

Nombre Propietario: J orge Alejandro Núñez Campos y Compañía.Ubicación del Sistema: Rol Avalúo 310-60, Sector Carén Alto, Km 18 Ruta Melipeuco -

Icalma, Provincia de Cautín, Melipeuco.R.U.T. Empresa Propietaria: 76.840.380 – 5 Teléfono - Fax: 045-736363Comuna: MelipeucoProvincia: CautínRegión: Novena

2. CARACTERÍSTICAS DEL PROYECTO

Las presentes especificaciones establecen las condiciones generales bajo las cuales se

ejecutará el SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR de la propiedadperteneciente al predio del Proyecto Piscicultura Carén Alto, ubicada en Sector CarénAlto, Km 18 Ruta Melipeuco - Icalma, Provincia de Cautín, Melipeuco.

Las instalaciones deberán cumplir con lo establecido en el Reglamento de InstalacionesDomiciliarias de Agua Potable y Alcantarillado (RIDAA); con las Normas del InstitutoNacional de Normalización a que haya lugar y con la “Ordenanza General de Urbanismo yconstrucción”.

La fuente de abastecimiento de Agua Potable será un pozo de 1.2m de diámetro y 6,5metros de profundidad, ubicado en el predio de la empresa acuícola.

Estas especificaciones complementan los planos correspondientes al proyecto de aguaconsumo humano particular. En general los planos presentan la ubicación definitiva de lastuberías e instalaciones.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 3/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

2

3. FUENTE DE ABASTECIMIENTO

El proyecto de agua consumo humano particular consiste en la captación del agua deabastecimiento de un pozo de 6,5 m de profundidad. El pozo tiene 1.2m de diámetro y sucontorno cuenta con hormigón armado para la hermeticidad o sello sanitario. El sello

presentará un espesor de 10cm con doble malla ACMA C92 y una geometría cuadrada de4.2m por 4.2m. En el fondo del pozo se considera una capa de gravilla o arena gruesacon 0.3m de altura la cual impide el paso del material fino.

En la bocatoma se instala filtro físico para la separación de sólidos gruesos, si existiesen.El agua se traslada por tubo de PVC a un estanque Infraplast de polietileno de 650lt (VerAnexo 1) ubicado en la losa de hormigón a un costado del pozo.

La elevación es por bomba de agua con corte automático por flotación. Esta bombaotorgará la energía para el tramo de bocatoma en el fondo del pozo al estanque. Losdatos de la bomba de elevación son los siguientes:

Marca: Pedrollo.Caudal máximo: 90lt/min.Potencia máxima: 1.0Hp.Altura máxima de elevación: 36m

Antes del empalme al estanque, el agua llegará clorada mediante una bomba inyectora decloro o clorador automático (Ver Anexo 3. Prospecto de Clorador Automático). Delestanque de acumulación se distribuirá el agua potable a la edificación mediante unasegunda bomba cuyas características son las siguientes:

Marca: Pedrollo.Caudal máximo: 120lt/min.

Potencia máxima: 1.5Hp.Altura máxima de elevación: 38m

La impulsión de esta segunda bomba se obtiene del sistema AUTOPRESS, equipoadosado a la bomba y de marca Koslan para una presión máxima de 10 bar (100 metroscolumna de agua) que sustituye al sistema hidropack (Ver Anexo 2).

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 4/15

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 5/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

4

 e) Sistema de Impulsión

El sistema de impulsión contempla dos bombas centrífugas de agua, como se detallaanteriormente.

5. VERIFICACIONES TÉCNICAS

a) Bases de Cálculo

Los requerimientos de agua potable se originan en la losa de mortalidad, EdificaciónPrincipal y Casa J efe de Centro.

Requerimientos Losa de Mortalidad:

• Agua de lavado de bins: 450l/día para lavado.

Edificación Principal:• Población máxima saneada (N): 6 personas residentes y 20 personas no residentes.• Dotación Agua Potable (D): 150l/hab·día y 100l/hab·día respectivamente.• Caudal Máximo Diario (Q): 2900l/día.

Casa J efe de Centro:• Población máxima saneada (N): 6 personas residentes.• Dotación Agua Potable (D): 150l/hab·día.• Caudal Máximo Diario (Q): 900l/día.

El caudal máximo diario (Q) de la Edificación Principal y Casa J efe de Centro se obtuvo apartir de la Ecuación 1.

 D N Q ·= (Ec. 1)

Reemplazando, el caudal máximo diario (Q) será de: 4250l/día.

b) Cálculo de potencias de bombas, pérdidas de carga, gastos y d iámetros.

La presencia de bombas en el sistema de tuberías afecta positivamente las líneas deenergía total y de gradiente hidráulico del flujo, ya que las bombas son maquinas

hidráulicas cuyo objetivo es convertir energía mecánica de rotación en energía cinética opotencial del fluído dentro del sistema, la bomba debe vencer la cabeza estática más lasperdidas menores y las de fricción, de acuerdo a la siguiente expresión:

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 6/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

5

Hm = H T +∑hf +∑hm 

Donde:Hm= Altura Manométrica.H T = Cabeza estática

∑hf = Perdida de energía por fricción. ∑hm= Perdida de energía por singularidades.

Para el cálculo de las perdidas de carga por fricción se empleara la ecuación de Hazen-Williams:

 L J  Hf  ·=  

Donde:

L = Longitud de tubería de impulsión. J = Perdida de Energía unitaria (m/m).

A la vez la energía unitaria se calcula de la siguiente forma:

Donde:

 J : Perdida de carga unitaria (metros/metros de conducción)C: Coeficiente de rugosidad de Hazen-Williams (PVC=150)

Q: Gasto máximo por tramo (método establecido por Reglamento de instalacionesdomiciliarias de agua potable y alcantarillado).

D: Diámetros por cada tramo (m).

Los gastos por artefacto se extraen de Anexo 3 del Reglamento de InstalacionesDomiciliarias de Agua Potable y Alcantarillado. Para obtener el Caudal Máximo Probable(QMP) se emplea la siguiente ecuación:

6891.0·7391.1 QQMP =  

Donde:

QMP: Caudal Máximo Probable (l/min).Q: Gastos por artefacto (l/min).

La velocidad por tramo se calcula a partir de la siguiente ecuación:

2· R

QMPV 

Π=  

869.4852.1

852.1

·

·665.10

 DC 

Q j =

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 7/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

6

 Donde:V: Velocidad en el tramo (m/s).QMP: Caudal Máximo Probable (m3/s).R: Radio de la tubería (m).

Para el tramo de nominado o – A y A - B, desde la bocatoma en el fondo del pozo alestanque, la bomba de elevación considerada en una Pedrollo de 1HP de potencia concapacidad de elevar 36m. Se emplea como altura manométrica 36m para establecer lacabeza estática en cada tramo, la que corresponderá a la presión de salida como seindica en Tabla 1.

Para el resto de los tramos se considera una bomba de impulsión Pedrollo de 1.5HP depotencia con capacidad de elevar 38m. Al igual que el tramo anterior se emplea comoaltura manométrica 38m para establecer la cabeza estática en cada tramo, la quecorresponderá a la presión de salida como se indica en Tabla 1.

Los resultados por tramo se presentan en tabla 1 y en plano anexo.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 8/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

7

Tabla 1. Gastos máximos, diámetros, longitudes, velocidades y pérdidas de carga portramo.

QI QMP L (m) Vel (m/s) J (Unit) J x L Acum Terr o Art Pi

0 A 322 93.00 32 10.40 1.92728496 0.118241065 1.23 1.22971 10.4 36.00 24.37

A B 322 93.00 32 2.00 1.92728496 0.118241065 0.24 1.46619 0 36.00 34.53B C 322 93.00 32 109.00 1.92728496 0.118241065 12.89 12.88828 0 38.00 25.11

C D 302 88.98 32 1.22 1.843975878 0.108949981 0.13 13.02120 0 38.00 24.98

D E 252 78.55 32 4.00 1.627749474 0.086478596 0.35 13.36711 0 38.00 24.63

E F 206 68.36 32 0.20 1.416668876 0.066864785 0.01 13.38048 0 38.00 24.62

F G 150 54.94 32 3.00 1.138484016 0.044603193 0.13 13.51429 0 38.00 24.49

G H 78 35.01 32 84.00 0.725478994 0.019360906 1.63 15.14061 0 38.00 22.86

H I 28 17.28 25 2.90 0.586730939 0.017421963 0.05 15.19113 0 38.00 22.81

I J 16 11.75 25 0.65 0.398989503 0.008529601 0.01 15.19668 0 38.00 22.80

 J K 6 5.98 25 1.30 0.20296746 0.002439506 0.00 15.19985 0 38.00 22.80

K L 6 5.98 25 0.60 0.20296746 0.002439506 0.00 15.20131 0 38.00 22.80

C M 50 25.77 25 85.00 0.874908469 0.036514289 3.10 3.10371 0 38.00 34.90

E N 46 24.33 20 0.28 1.290710486 0.097297852 0.03 0.02724 0 38.00 37.97

N Ñ 8 7.29 20 0.33 0.386671111 0.010437707 0.00 0.03069 0 38.00 37.97

Ñ O 8 7.29 20 1.20 0.386671111 0.010437707 0.01 0.04321 0 38.00 37.96

Ñ P 8 7.29 20 0.65 0.386671111 0.010437707 0.01 0.05000 0 38.00 37.95

P Q 8 7.29 20 1.20 0.386671111 0.010437707 0.01 0.06252 0 38.00 37.94

N R 30 18.12 20 3.10 0.961405657 0.056388612 0.17 0.23733 0 38.00 37.76R S 10 8.50 20 1.80 0.450943796 0.013876596 0.02 0.26231 0 38.00 37.74

R T 20 13.70 20 0.36 0.727046497 0.033609451 0.01 0.27440 0 38.00 37.73

 T U 10 8.50 20 0.80 0.450943796 0.013876596 0.01 0.28551 0 38.00 37.71

 T V 10 8.50 20 1.80 0.450943796 0.013876596 0.02 0.31048 0 38.00 37.69

F a 56 27.86 20 0.28 1.478082877 0.125063447 0.04 0.03502 0 38.00 37.96

a b 16 11.75 20 0.40 0.623421099 0.025280379 0.01 0.04513 0 38.00 37.95

b c 8 7.29 20 1.20 0.386671111 0.010437707 0.01 0.05766 0 38.00 37.94

b d 8 7.29 20 1.85 0.386671111 0.010437707 0.02 0.07696 0 38.00 37.92

a e 40 22.10 20 3.00 1.172200646 0.081402898 0.24 0.32117 0 38.00 37.68

e f 10 8.50 20 1.80 0.450943796 0.013876596 0.02 0.34615 0 38.00 37.65

e g 30 18.12 20 0.55 0.961405657 0.056388612 0.03 0.37717 0 38.00 37.62

g h 10 8.50 20 1.80 0.450943796 0.013876596 0.02 0.40214 0 38.00 37.60

g i 20 13.70 20 1.10 0.727046497 0.033609451 0.04 0.43911 0 38.00 37.56

i j 10 8.50 20 0.80 0.450943796 0.013876596 0.01 0.45021 0 38.00 37.55

i k 10 8.50 20 1.53 0.450943796 0.013876596 0.02 0.47145 0 38.00 37.53

g l 72 33.13 20 11.00 1.757560323 0.172354254 1.90 1.89590 0 38.00 36.10

l m 12 9.64 20 1.10 0.511312268 0.017511974 0.02 1.91516 0 38.00 36.08l n 60 29.22 20 9.65 1.550052626 0.136574575 1.32 3.23310 0 38.00 34.77

n o 18 12.74 20 0.55 0.676130769 0.0293809 0.02 3.24926 0 38.00 34.75

o p 10 8.50 20 0.80 0.450943796 0.013876596 0.01 3.26037 0 38.00 34.74

o q 8 7.29 20 2.10 0.386671111 0.010437707 0.02 3.28228 0 38.00 34.72

n r 60 29.22 20 4.85 1.550052626 0.136574575 0.66 3.94467 0 38.00 34.06

r s 24 15.54 20 0.45 0.824377221 0.042414423 0.02 3.96376 0 38.00 34.04

s t 12 9.64 20 1.10 0.511312268 0.017511974 0.02 3.98302 0 38.00 34.02

s u 12 9.64 20 1.40 0.511312268 0.017511974 0.02 4.00754 0 38.00 33.99

r v 36 20.55 20 1.83 1.090110367 0.071161248 0.13 4.13776 0 38.00 33.86

v w 18 12.74 20 0.35 0.676130769 0.0293809 0.01 4.14805 0 38.00 33.85

w x 8 7.29 20 2.10 0.386671111 0.010437707 0.02 4.16997 0 38.00 33.83

w y 10 8.50 20 1.92 0.450943796 0.013876596 0.03 4.19661 0 38.00 33.80

v 1 18 12.74 20 9.42 0.676130769 0.0293809 0.28 4.47338 2.5 38.00 31.03

1 2 8 7.29 20 1.20 0.386671111 0.010437707 0.01 4.48590 2.5 38.00 31.01

2 3 10 8.50 20 1.50 0.450943796 0.013876596 0.02 4.50672 2.5 38.00 30.99

H 5 20 13.70 32 1.00 0.284002538 0.003408798 0.003 15.14402 0 38.00 22.86

I 4 12 9.64 25 2.60 0.327239852 0.005908541 0.02 15.20649 0 38.00 22.79

Cota, mPerdida de Carga, mTramo Ø

Presíon

[mca]

Longitud [m]Gasto

Maximo [L/m]

 

La nomenclatura de los tramos se presenta en Plano Anexo.

La pérdida de carga máxima acumulada será de 15.2 m.c.a., por ende la presión de aguaen la salida más desfavorable será de 22.8 m.c.a. Dado que el mínimo normado para saliren una llave domiciliaria es de 5mca, se verifica técnicamente que el sistema funciona conuna óptima presión para la bomba instalada.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 9/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

8

c) Verificación de la Potencia de la Bomba.

Para el cálculo de la potencia de la bomba se emplea la siguiente ecuación:

e H QMPgP m··· ρ 

=  

Donde:P: Potencia de la bomba. ρ  : Densidad del agua (1000 kg/m3).

e: Eficiencia en base a 1.QMP: Caudal máximo probable (m3/s).Hm: Altura Manométrica total(m).

Para la bomba de elevación, los valores son los siguientes: ρ  : Densidad del agua (1000 kg/m3).e: 0.8.QMP: 93l/s (0.00155m3/s).Hm: 10.43m.

Para la bomba de impulsión, los valores son los siguientes: ρ  : Densidad del agua (1000 kg/m3).

e: 0.8.QMP: 93l/s (0.00155m3/s).Hm: 2.58m.

Empleando la ecuación de potencia (P), los resultados son los siguientes:

Potencia P, de la bomba de elevación: 198.2 W, equivalente a 0.26HP.Potencia P, de la bomba de impulsión: 49.03 W, equivalente a 0.056HP.

Las bombas centrífugas de elevación e impulsión se encuentran sobredimensionadaspara asegurar un caudal instantáneo de 93 l/min con una presión de salida en toda la redsobre los 5 m.c.a.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 10/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

9

6. ESPECIFICACIONES TECNICAS

 Todas las instalaciones se ejecutan conforme a:

• Planos del Proyecto.• Especificaciones Técnicas del proyecto.• Recomendaciones Instalación de cañerías hidráulicas de PVC.• Instrucción Prueba de Presión.• Instrucciones prueba de conjunto de impermeabilidad de redes de agua potable.

a) Normas y/o Reglamentos 

Las obras en referencia, en lo relacionado a la red de agua potable, se ejecutarán déacuerdo con:

a) Planos adjuntos.b) Especificaciones Técnicas.c) Reglamento de Instalaciones Domiciliarias de Agua Potable y Alcantarillado

(RIDAA).d) Manual de Normas Técnicas para la realización de las instalaciones domiciliarias

de agua potable y alcantarillado, aprobado por DS del MOP Nº 70, del 23 de Enerode 1981.

e) Normas del Instituto Nacional de Normalización (I.N.N.), en especial en lo que serefiere a:

- 349 OF. 55: Prescripciones de seguridad en excavaciones.- 436 OF.51: Prescripciones generales acerca de la prevención de accidentes del

trabajo.

- 438 OF.51: Protecciones de uso personal.

No se podrá efectuar ninguna modificación al proyecto ni ejecutar obra extraordinaria sinautorización del propietario o proyectista.

b) Construcción de las Obras 

Será de cargo del Contratista el suministro de todos los elementos para construir oinstalar, mano de obra, transporte y medios necesarios para la correcta ejecución deestas obras.

En general, la ejecución de las obras deberá ceñirse a los planos, respetando diámetros,pendientes y artefactos.

c) Planos 

Los planos, materia de este proyecto, tienen un carácter de definitivos.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 11/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

10

d) Pruebas Parciales y Finales Las pruebas de las instalaciones serán de entera responsabilidad del contratista.

Las pruebas parciales no liberan al Contratista de la obligación de efectuar reparacionesde las redes si se produjeran desperfectos antes de la recepción final de las instalaciones.

El sistema de tuberías de las instalaciones de impulsión y distribución de agua potabledeberán ser sometidos a un conjunto de pruebas y verificaciones, que se indican acontinuación, tales que aseguren su impermeabilidad, buena ejecución y funcionamientosatisfactorio:

Prueba Hidráuli caSe efectuará una prueba de presión hidráulica de 1,6 m de presión sobre la boca deadmisión más alta durante un periodo mínimo de 15 minutos sin que se produzca ningunafiltración. Durante esta prueba de presión deberá efectuarse una revisión de las junturasmediante una inspección visual para verificar que no filtren.

Prueba de bolaRealizada la prueba anterior, las tuberías horizontales se someterán a una prueba debola, cuyo objeto es verificar la existencia de costras en las junturas u otro impedimentointerior. La bola con que debe efectuarse las pruebas tendrá una tolerancia máxima de 3mm con respecto al diámetro de la tubería verificada.

e) Red de tuberías de Aguas Todos los trabajos para las distintas redes de distribución se ejecutarán de acuerdo atrazado indicado en el plano respectivo. Se realizarán de manera que la totalidad de latubería y los registros de inspección se apoyen en toda su extensión o superficie sobreterreno firme y regular o a través de soportes metálicos si pasa por cielo a una distancia

no menor de 1,2m uno de otro. Se debe consultar todos aquellos elementos de fitting enPVC necesarios para asegurar un óptimo funcionamiento del sistema.

Dadas las características del proyecto, el representante legal de la empresa asume laresponsabilidad del buen funcionamiento del sistema de agua consumo humano particularde la casa habitación.

Este documento ha sido elaborado a petición de la empresa particular para serpresentado al Servicio de Salud IX Región de la Araucanía, Oficina Cunco, para suaprobación bajo el ítem Sistema de Agua Consumo Humano Particular.

CHRISTIAN HERRERA CÁRDENASINGENIERO PROYECTISTA

INGENIERO AMBIENTAL - INGENIERO CIVIL INDUSTRIALRUT: 10.056.935-3

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 12/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

11

1. Especificaciones estanque de agua.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 13/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

12

 

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 14/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

13

 ANEXO 2. Espec if icaciones s is tema AUTOPRESS.

7/28/2019 Memoria Explicativa Agua Consumo Humano Particular

http://slidepdf.com/reader/full/memoria-explicativa-agua-consumo-humano-particular 15/15

 MEMORIA EXPLICATIVA Y ESPECIFICACIONES TÉCNICAS SISTEMA DE AGUA CONSUMO HUMANO PARTICULAR

14

 ANEXO 3. Prospecto Clorador Automát ico.

Dosificadoras Blackstone

Versatilidad de Diseño 

Las bombas Dosificadoras Blackstone han sido diseñadas para satisfacer lasnecesidades de la industria.

Para acomodarse a las diversas aplicaciones, las bombas dosificadoras pueden sermontadas en cualquier lugar en su planta con una base ancha y lisa.

La parte trasera de la carcasa de la bomba tiene orificios para facilitar un montajevertical.

Con el conjunto de la válvula de la bomba y los controles de la unidad situados en laparte frontal de la bomba no hay problemas con la instalación o ajustes de caudal.

Manejo Sencillo

Las bombas Dosificadoras Blackstone están equipadas con un solo control para salidade bomba.

El control de caudal externo (potenciómetro) le permite ajustar el porcentaje de 0 al100% de su capacidad. Esta característica elimina la necesidad de preocuparse delongitudes de carrera y selecciones de potencia.

Un LED indicador se ilumina cada vez que comienza un recorrido. Esto permite alusuario calcular la cadena de impulsos a distancia.