Datos Genericos Calculo Cortos

13
VALORES CABLES TÍPICOS VOLTALENE 12/20kV C(µF/km) Y(S/km) 12/20kV 95 0.221 0.0000694 95 120 0.241 0.0000757 120 150 0.256 0.0000804 150 185 0.283 0.0000889 185 240 0.318 0.0000999 240 300 0.343 0.0001078 300 400 0.375 0.0001178 400 500 0.417 0.0001310 500 630 0.0000000 630 18/30kV C(µF/km) Y(S/km) 18/30kV 95 0.169 0.0000531 95 120 0.183 0.0000575 120 150 0.194 0.0000609 150 185 0.213 0.0000669 185 240 0.237 0.0000745 240 300 0.254 0.0000798 300 400 0.276 0.0000867 400 500 0.306 0.0000961 500 630 0.0000000 630 **VALORES PRISMYAN CABLES MEJICO RHZ1-OL 18/30 kV R(105ºC) Ω/km L( 60Hz) Ω/km C μF/ km EPR (105ºC) 1250 kCM AL 0.069 0.124 0.329 EPR (105ºC) 1000 kCM AL 0.082 0.128 0.305 EPR (105ºC) 500 kCM AL 0.153 0.141 0.224 EPR (105ºC) 350 kCM AL 0.221 0.149 0.200 EPR (105ºC) 250 kCM AL 0.311 0.155 0.180 EPR (105ºC) 3/0 AWG AL 0.461 0.165 0.156 EPR (105ºC) 1/0 AWG AL 0.736 0.178 0.138 CABLES POLONIA XRUHAKXS 12/20 kV - XRUHKXS 12/20 kV Conductor 630 CU 0.043 0.094 0.440 500 CU 0.053 0.097 0.400 400 CU 0.066 0.100 0.360 300 CU 0.083 0.107 0.320 240 CU 0.101 0.110 0.300 185 CU 0.131 0.116 0.270 150 CU 0.163 0.116 0.250 120 CU 0.198 0.122 0.230 95 CU 0.249 0.129 0.220 70 CU 0.345 0.135 0.200 Sección (mm2) R (W/km) L (W/km) C (mF/km)

description

Datos Genericos Calculo Cortos

Transcript of Datos Genericos Calculo Cortos

Calculo Admitancia EtapVALORES CABLES TPICOSVOLTALENEEPROTENAX12/20kVC(F/km)Y(S/km)12/20kVC(F/km)Y(S/km)950.2210.0000694950.2880.00010341200.2410.00007571200.3150.00009901500.2560.00008041500.3360.00010561850.2830.00008891850.3660.00011502400.3180.00009992400.4210.00013233000.3430.00010783000.4550.00014294000.3750.00011784000.4990.00015685000.4170.00013105000.5560.00017476300.00000006300.000000018/30kVC(F/km)Y(S/km)18/30kVC(F/km)Y(S/km)950.1690.0000531950.2070.00006501200.1830.00005751200.2320.00007291500.1940.00006091500.2530.00007951850.2130.00006691850.2810.00008832400.2370.00007452400.3120.00009803000.2540.00007983000.340.00010684000.2760.00008674000.3660.00011505000.3060.00009615000.4090.00012856300.00000006300.0000000**VALORES PRISMYANCABLES MEJICORHZ1-OL 18/30 kVR(105C) /kmL( 60Hz) /kmC F/ kmY(S/km)EPR (105C) 1250 kCM AL0.0690.1240.3290.0001033586EPR (105C) 1000 kCM AL0.0820.1280.3050.0000958188EPR (105C) 500 kCM AL0.1530.1410.2240.0000703718EPR (105C) 350 kCM AL0.2210.1490.2000.000062832EPR (105C) 250 kCM AL0.3110.1550.1800.0000565488EPR (105C) 3/0 AWG AL0.4610.1650.1560.000049009EPR (105C) 1/0 AWG AL0.7360.1780.1380.0000433541CABLES POLONIAXRUHAKXS 12/20 kV - XRUHKXS 12/20 kVSeccin

(mm2)ConductorR (W/km)L (W/km)C (mF/km)Y(S/km)630CU0.0430.0940.4400.0001382304500CU0.0530.0970.4000.000125664400CU0.0660.1000.3600.0001130976300CU0.0830.1070.3200.0001005312240CU0.1010.1100.3000.000094248185CU0.1310.1160.2700.0000848232150CU0.1630.1160.2500.00007854120CU0.1980.1220.2300.000072256895CU0.2490.1290.2200.000069115270CU0.3450.1350.2000.00006283250CU0.4960.1410.1800.000056548835CU0.6680.1470.1500.000047124630AL0.0680.0940.4400.0001382304500AL0.0850.0970.4000.000125664400AL0.1070.1000.3600.0001130976300AL0.1330.1070.3200.0001005312240AL0.1650.1100.3000.000094248185AL0.2150.1160.2700.0000848232150AL0.2680.1160.2500.00007854120AL0.3280.1220.2300.000072256895AL0.4130.1290.2200.000069115270AL0.5710.1350.2000.00006283250AL0.8250.1410.1800.000056548835AL1.1130.1470.1500.000047124Datos procedentes catalogo Prysmian 2009

Datos Genericos Cortos IMPEDANCIA DE LINEAS Y CONDUCTORESTENSION DE CORTOCIRCUITO PARA TRAFOS MT Y REDES DE DIST.R = /sZt= ( Ucc * U2) / SnIMPEDANCIA TRAFOS*POTENCIA RED*Generalmente Rt