    Power Quality Monitoring

    1

    ALSTOM Power Quality

    Monitoring SolutionsSelling Guide

    APRIL 2000

  • 5/21/2018 BIEL - Original

    2/70

    Power Quality Monitoring

    2

    POWER QUALITY CONCERNS:

    In the upper part of the network, the main

    concern is to improve the grid load flow In the lower part of the network, the main

    concern is to improve the end user Voltage

  • 5/21/2018 BIEL - Original

    3/70

    Power Quality Monitoring

    3

    INTERCONNECTED TRANSMISSIONNETWORK

    SUB TRANSMISSION

    DISTRIBUTION

    SECONDARY DISTRIBUTION

    LV NETWORK

    G

    G

    G

    G

    SECONDARY(RURAL)DISTRIBUTION

    Heavy

    Industry

    MediumIndustry

    Light Industry

    POW GEN

    IPPPOW GEN

    IPP

    RenewableSourcesIPPMunicipal

    CO-GEN

    DOMESTIC

    URBANTRANSFORMERS

    CHEMICALPLANTS

    STEELWORKS

    M722

    M722

    M722

    M723

    M723

    M724

    M723

    M724

    M723

    M722

    M721

    M721

    M723

    M722 M722

    M721

    M724HV Sliding refrequired

    GRID LOAD FLOWIMPROVEMENT

    END USER VOLTAGEIMPROVEMENT

    Range MiCOM M720 : PQ Meters

    Why assessing the level of Power Quality ?

    G

  • 5/21/2018 BIEL - Original

    4/70

    Power Quality Monitoring

    4

    Customer solutions :

    Transmission Utility

    Distribution Utility

    Industries

    Generation, IPP

  • 5/21/2018 BIEL - Original

    5/70

    Power Quality Monitoring

    5

    Power Quality MonitoringinTRANSMISSION

  • 5/21/2018 BIEL - Original

    6/70

    Power Quality Monitoring

    6

    Transmission Utility : Customer questions:

    How can I monitor the legal and contractual interfaces

    inside my network ? Do I need and how can I build-up Power Quality

    contracts ?

    How to optimise the network planning improving asset

    management ?

  • 5/21/2018 BIEL - Original

    7/70

    Power Quality Monitoring

    7

    Transmission Utility : Monitoring the legal and

    contractual interfaces : how PQM can help ?

    by monitoring a set of parameters versus PQ standards,

    including the sliding HV reference : V,V dips andInterruptions, FRQ, Unbalance, Harmonics to evaluate

    the propagation of bad quality over the transmission

    network

    by producing advanced PQ reports in a user-friendly way, accessible to financial deciders, and to produce

    evidence to the customers that the promised Power

    Quality level is met

  • 5/21/2018 BIEL - Original

    8/70

    Power Quality Monitoring

    8

    Transmission Utility : build-up power quality

    contracts : how PQM can help ?

    by assessing how far is the actual level of Power Quality

    from the to be defined standards to evaluate the riskswhile building legal contractual agreements

    by monitoring the set of PQ parameters with fully

    configurable limits to sharpen the knowledge of PQ, to

    eliminate PQ pollution at the source by knowing the level of Power Quality time and space

    related, to take planning action to reach the level of PQ

    at whatever time and location

    by getting advanced reports on PQ data producingcontractual evidences

  • 5/21/2018 BIEL - Original

    9/70

    Power Quality Monitoring

    9

    Transmission Utility : optimise the networkplanning through better asset management :

    how PQM can help ? by getting the relevant PQ data to improve the technical

    and financial management of the network by increasing the relevance of the renovation by knowing

    the PQ level at critical locations (common coupling

    points)

    by getting in an efficient way advanced PQ reports, timeand space related to build-up ROI analysis

    by knowing the convergence to the PQ standards to

    avoid over-quality and consequently over investment

  • 5/21/2018 BIEL - Original

    10/70

    Power Quality Monitoring

    10

    Transmission Utility : optimise the networkplanning through better asset management :

    how PQM can help ? by allowing calculation of potential penalties according to

    the type of investment and therefore optimise thefinancial management of my network

    by using the PQM data to mitigate PQ sags/Interruptions

    and consequently decrease the loss of income due to the

    undelivered energy

  • 5/21/2018 BIEL - Original

    11/70

    Power Quality Monitoring

    11

    Transmission Utility : Power Quality

    Monitoring solutions : Which product to

    choose in PCB range ?

    to monitor the legal and contractual interfaces

    (deregulation) -> MiCOM M723

    to build-up Power Quality contracts -> MiCOM M724

    to optimise the network planning with the asset

    management approach -> MiCOM M724

    and QR Manager analysis software

  • 5/21/2018 BIEL - Original

    12/70

    Power Quality Monitoring

    12

    Power Quality MonitoringinDISTRIBUTION

  • 5/21/2018 BIEL - Original

    13/70

    Power Quality Monitoring

    13

    Distribution Utility : Customer questions:

    How can I monitor the legal and contractual interfaces ?

    How can I improve the reliability and the availability of thepower delivered to the customers at lower costs ?

    How being able to propose premium power contracts ?

    How to optimise the network planning improving asset

    management ?

  • 5/21/2018 BIEL - Original

    14/70

    Power Quality Monitoring

    14

    Distribution Utility : monitor the legal and

    contractual interfaces : how PQM can help ?

    by monitoring a set of parameters versus PQ standards

    including Flicker, Inter-harmonics and signalling Voltage by getting efficiently periodic PQ reports

    by comparing the actual level of Power Quality versus

    other utilities, to make sure to keep a good benchmark

    position by monitoring carefully the Power Quality coming from

    IPPs

  • 5/21/2018 BIEL - Original

    15/70

    Power Quality Monitoring

    15

    Distribution Utility : improve the reliability andthe availability of the power delivered to the

    customers at lower costs : how PQM can help ?

    by getting fast and accurate information on Power Qualitydisruption

    by assessing accurately the actual level of Power

    Quality to avoid penalties

    by monitoring the disturbances created by pollutingcustomers (Industries), and claim penalties

    by linking the kwh purchase rate from IPPs to the Power

    Quality level

  • 5/21/2018 BIEL - Original

    16/70

    Power Quality Monitoring

    16

    Distribution utility : being able to propose

    premium power contracts : how PQM can

    help ? by investigating the actual level of Power Quality to know

    where the Quality is harmed and take action by assessing the Power Quality with fully configurable

    limits, to get some sections to a top quality power

    by building up an offer of targeted quality to sensitive

    customers by having a powerful and automatic reports generation

    facility

  • 5/21/2018 BIEL - Original

    17/70

    Power Quality Monitoring

    17

    Distribution utility : optimise the network

    planning improving asset management : how

    PQM can help ? by investing in a relevant way with best ROI possible,

    related to penalties involved by decreasing the loss of income due to the undelivered

    energy

    by avoiding over-quality for everyone, keeping the best

    quality for premium power contracts by recovering the incoming penalties, and avoiding the

    out-coming penalties

    by managing efficiently the power flow to buy

    continuously the best value for money power

  • 5/21/2018 BIEL - Original

    18/70

    Power Quality Monitoring

    18

    Distribution Utility : Power Quality

    Monitoring solutions : Which product to

    choose in PCB range ?

    to monitor the legal and contractual interfaces(deregulation) -> MiCOM M721

    to improve the reliability and the availability of the power

    delivered to the customers at lower costs

    -> MiCOM M722 to be able to propose premium power contracts

    to optimise the network planning with the asset

    management approach -> MiCOM M722

    and QR Manager analysis software

  • 5/21/2018 BIEL - Original

    19/70

    Power Quality Monitoring

    19

    Power Quality MonitoringinINDUSTRIES

  • 5/21/2018 BIEL - Original

    20/70

    Power Quality Monitoring

    20

    Industry :

    Power Quality Monitoring : Customers

    questions

    How can I check that the committed power quality isreached ?

    How can I keep the continuity of the process ?

    How can I decrease my energy bill ?

    How can I avoid penalties (minimise pollution to the grid)

    ?

    How can I optimise the plant ?

  • 5/21/2018 BIEL - Original

    21/70

    Power Quality Monitoring

    21

    Industry : check that the committed power quality

    is reached : how PQM can help ?

    by continuously monitoring the level of Power Quality

    by processing the necessary statistics , generating thePower Quality index stated in the contract

    by getting periodically (typical every week) a reports on

    the contractual PQ indices

    by making the PQ data accessible to financial people

  • 5/21/2018 BIEL - Original

    22/70

    Power Quality Monitoring

    22

    Industry : keep the continuity of my process :

    how PQM can help ? by getting specific contractual agreement with the utilities

    by monitoring the level of Power Quality delivered to their

    plant by minimising the effect of the variations of the electrical

    supply

    by correlating the Power Quality disruptions with the

    failures in the process

  • 5/21/2018 BIEL - Original

    23/70

    Power Quality Monitoring

    23

    Industry : decrease the energy bill : how PQM

    can help ? by monitoring accurately the Power Quality parameters

    linked to possible penalties

    by optimising the energy cost allocations throughout theplant

    by getting a deep knowledge of the power flow on the

    plant in order to better negotiate with the utilities

    by grouping some loads to optimise the costs by getting a cheaper own-generation capability

    by billing in the best way the energy sold by the plant

  • 5/21/2018 BIEL - Original

    24/70

    Power Quality Monitoring

    24

    Industry : avoid penalties (minimise pollution to

    the grid) : how PQM can help ? by monitoring continuously the disturbing loads to know

    their influence on the level of Power Quality emitted to

    outside (arc furnaces etc )

    by placing well-dimensioned relevant corrective devices ,

    thus avoiding penalties

    by getting accurately, statistics on Power Quality data,

    with thresholds crossing

  • 5/21/2018 BIEL - Original

    25/70

    Power Quality Monitoring

    25

    Industry : optimise the plant : how PQM can

    help ? by identifying the sensitive loads, and increase their

    immunity (rather than rise up the power quality level

    everywhere)

    by measuring the Power Quality throughout the plant and

    build up a risk management plan

    by performing a Power Quality level survey , time and

    topology related

    by getting quickly, well designed Power Quality reports

  • 5/21/2018 BIEL - Original

    26/70

    Power Quality Monitoring

    26

    Industry : Power Quality Monitoring

    solutions : Which product to choose in PCB

    range ? to check that the committed power quality is reached

    -> MiCOM M721 to keep the continuity of the process -> MiCOM M722

    to decrease the energy bill -> MiCOM M722

    to avoid penalties (minimise pollution to the grid)

    -> MiCOM M722(memory for long duration data logging) -> MiCOM M724

    to optimise the plant -> MiCOM M724

    and QR Manager analysis software

  • 5/21/2018 BIEL - Original

    27/70

    Power Quality Monitoring

    27

    Low

    Melting ovenCement ovenTansportArc Furnace

    Food processing

    PaperGlassCarmanufacturer

    Metal assemblyMech. ExtrusionIndustrial gasesFiber production

    ElectrolysisGrinding

    High

    Low

    AVAI

    LABIL

    ITY

    Steel rollingAluminiumRolling

    RefiningChemicals/plastics

    Medium High

    Q U A L I T Y(Impact of aninterruption)

    (Impact of a dip)

    IMPACT : in major industries

  • 5/21/2018 BIEL - Original

    28/70

    Power Quality Monitoring

    28

    AirportDips Interruptions Swell Hi Inter- Hi Flicker Unbalance K-Factor

    Telecom.

    Cyclo-converterElectronicEquipt

    Car Industry

    Oil & Gas

    Railways

    Variablespeed drive

    X X X X X X -

    X X

    -

    - - - - - -

    X X X XX - - -

    X X X XX X- -

    X X X X X XX -

    X X X X X -- -

    - X XX - - - -

    X X X XX X- -

    Transformer X X XX-- X

    Type of Power Quality disruption

  • 5/21/2018 BIEL - Original

    29/70

    Power Quality Monitoring

    29

    Interruptions

    Example of cost per PQ event :

    Semi-conductor Industry

    Level of Voltage 20 kV

    Interr. Rate 1.0 /mnth

    Loss / event 52 MUS$ /event

    Cost per month 52 MUS$

    Cost per year 630 MUS$

    Example : process is lasting 70 days with 300 steps in the process, in an oven :700 Wafers x 150 microchips x 500 US$ each

    -> loss = 700 x 150 x 500 = 52 M$ !!

  • 5/21/2018 BIEL - Original

    30/70

    Power Quality Monitoring

    30

    Power Quality MonitoringinOIL & GAS APPLICATION

  • 5/21/2018 BIEL - Original

    31/70

    Power Quality Monitoring

    31

    Different level are present depending of the

    size of the plant :

    Main arrival from public utility

    Co-generation at sub-transmission or distribution

    level

    Back-up network at low voltage level

    (emergency)

    MV loads (motors , crackers etc )

    LV loads (motors, pumps, etc )

    OIL & GAS PLANT :

  • 5/21/2018 BIEL - Original

    32/70

    Power Quality Monitoring

    32

    OIL & GAS Plant :

    SUB TRANSMISSION

    DISTRIBUTION

    SECONDARY

    DISTRIBUTION

    LVNETWORK

    G

    G

    CO-GENERATION

    INTERCONNECTED TRANSMISSION NETWORK

    LV LOADS

    G

    EmergencyCO-GENERATION

    11KV110KV

    N x 40 MW

    11KV

    36.6KV

    N x 20 MW

    1000 kW

    CO-GENERATION

    HV Arrival (Utility)

    Big Oil &Gas Plant

    Middle sizeOil & GasPlant

  • 5/21/2018 BIEL - Original

    33/70

    Power Quality Monitoring

    33

    Different parameters are to be monitored :

    Monitoring of the main HV arrival from the utility

    Monitoring of the correct coupling/Islanding of the

    Co-generation devices

    Technological monitoring of the Co-generation

    turbines

    Monitoring (M) and Power Quality Monitoring(PQM)

    Power flow (Import/export) monitoring at the

    interconnection public network/oil & gas plant

    OIL & GAS PLANT :

  • 5/21/2018 BIEL - Original

    34/70

    Power Quality Monitoring

    34

    Different parameters are to be monitored :

    Monitoring of the harmonic pollution of the power

    throughout the plant (Variable speed motors,

    transformer saturation, etc )

    Monitoring of operation during

    connection/disconnection of loads

    Unbalance rate of the network (phase to phasefaults, Fuse blowing , Unbalanced load)

    Billing optimisation (peak hours management)

    OIL & GAS PLANT :

    Q

  • 5/21/2018 BIEL - Original

    35/70

    Power Quality Monitoring

    35

    Phenomena to be monitored :

    SUB TRANSMISSION

    DISTRIBUTION

    SECONDARY

    DISTRIBUTION

    LVNETWORK

    INTERCONNECTED TRANSMISSIONNETWORK

    LV LOADS

    G

    EmergencyCO-GENERATION

    11KV110KV

    N x 40 MW

    11KV

    36.6KV

    N x 20 MW

    1000 kW

    CO-GENERATION

    Network phase changing

    Reclosing

    Motor Starting

    Voltage Current

    Motor Starting

    Source coupling

    VariableSpeedMotor

    CO-GENERATION

    G

    GBig Oil &Gas Plant

    Middle sizeOil & GasPlant

    P Q lit M it i

  • 5/21/2018 BIEL - Original

    36/70

    Power Quality Monitoring

    36

    MONITORING AND POWER QUALITY MONITORING

    SUB TRANSMISSION

    DISTRIBUTION

    SECONDARY

    DISTRIBUTION

    LV NETWORK

    INTERCONNECTED TRANSMISSION NETWORK

    LV LOADS

    G

    11KV110KV

    N x 40 MW

    11KV

    36.6KV

    N x 20 MW

    1000 kW

    CO-GENERATION

    Reclosing CO-GENERATION

    G

    G

    MiCOM M723

    EmergencyCO-GENERATION

    M / PQM

    MiCOM M722

    M / PQM

    MiCOM M723

    MiCOM M722

    MiCOM M721MiCOM M722

    M / PQM

    M / PQM

    M / PQM

    M / PQM

    M / PQM

    MiCOM M724Portable

    Big Oil &Gas Plant

    Middle sizeOil & GasPlant

    P Q lit M it i

  • 5/21/2018 BIEL - Original

    37/70

    Power Quality Monitoring

    37

    Power Quality MonitoringinGENERATION & IPPs

    P Q lit M it i

  • 5/21/2018 BIEL - Original

    38/70

    Power Quality Monitoring

    38

    Generation and IPP : Customers questions

    How can I get evidence that the level of Power Quality is

    according the requirements How can I secure the invoicing of different Quality of

    Supply of the power generated according to their rates

    How can I get technological data about the generating

    devices

    P Q lit M it i

  • 5/21/2018 BIEL - Original

    39/70

    Power Quality Monitoring

    39

    Generation and IPP : get evidence that thelevel of Power Quality is according the

    requirements : how PQM can help ?

    by monitoring continuously the level of Power Qualityaccording the contractual commitment

    by keeping the history of the monitored data over an

    invoicing period

    by producing advanced PQ reports showing evidence ofthe fulfilling of the commitments

    P Q lit M it i

  • 5/21/2018 BIEL - Original

    40/70

    Power Quality Monitoring

    40

    Generation and IPP : secure the invoicing ofdifferent Quality of Supply of the power generatedaccording to their rates:

    how PQM can help ?

    by having the monitored data , periodically reported to

    financial people

    by monitoring the power generated according more than

    one Power Quality profile by having selected targeted reports according the

    different rates

    P Q lit M it i

  • 5/21/2018 BIEL - Original

    41/70

    Power Quality Monitoring

    41

    Generation and IPP : get technological data

    about the generating devices :

    how PQM can help ? by monitoring a set of parameters linked to the

    technology of the generating devices (inter-harmonics,unbalance, flicker etc )

    by producing advanced PQ information to technical

    specialists for analysis and corrective and preventive

    maintenance

    Po er Q alit Monitoring

  • 5/21/2018 BIEL - Original

    42/70

    Power Quality Monitoring

    42

    Generation and IPP : Power Quality

    Monitoring solutions : Which product tochoose in PCB range ? to get evidence that the level of Power Quality is

    according the requirements-> MiCOM M722

    IPPs -> MiCOM M721

    to secure the invoicing of different Quality of Supply of

    the power generated according to their rates-> MiCOM M722

    to get technological data about the generating devices

    -> MiCOM M724

    and QR Manager analysis software

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    43/70

    Power Quality Monitoring

    43

    Power QualityMonitoring Solutions :M720 + QR Manager

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    44/70

    Power Quality Monitoring

    44

    FLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKERFLICKER

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    45/70

    Power Quality Monitoring

    45

    ALSTOM Power Quality Monitoring

    Solutions :

    MiCOM M720 : a comprehensive range of Power Quality

    Meters QR Manager : advanced analysis software with

    automatic PQ report generation

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    46/70

    Power Quality Monitoring

    46

    Medidor de calidad de potencia ALSTOM

    Soluciones:

    MICOM M720 : amplia gama de medidores de calidad de

    potencia

    ADMINISTRADOR QR: software de anlisis avanzado

    con generador automtico de PQ.

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    47/70

    Power Quality Monitoring

    47

    MiCOM M721

    Standard power quality profile

    MiCOM M722

    Customisable power quality profile - Investigation MiCOM M723

    Standard power quality profile - HV sliding

    reference

    MiCOM M724

    Expert investigation - convergence of the PQ

    parameters to the PQ standards

    MiCOM M720

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    48/70

    Power Quality Monitoring

    48

    MiCOM M721

    Perfiles de calidad normalizados

    MiCOM M722

    Perfiles de calidad configurables - Investigacin MiCOM M723

    Perfiles de calidad normalizados - HV sliding

    reference

    MiCOM M724

    Expert investigation - convergence of the PQ

    parameters to the PQ standards

    MiCOM M720

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    49/70

    Power Quality Monitoring

    49

    POWER QUALITY MONITORINGINTERCONNECTED TRANSMISSIONNETWORK

    SUB TRANSMISSION

    DISTRIBUTION

    SECONDARY DISTRIBUTION

    LV NETWORK

    G

    G

    G

    G

    G

    SECONDARY(RURAL)DISTRIBUTION

    Heavy

    Industry

    Medium

    Industry

    Light Industry

    POW GEN

    IPPPOW GEN

    IPP

    RenewableSourcesIPPMunicipal

    CO-GENDOMESTIC

    URBANTRANSFORMERS

    CHEMICALPLANTS

    STEELWORKS

    M722

    M722

    M722

    M723

    M723

    M724

    M723

    M724

    M723

    M722

    M721

    M721

    M723

    M722 M722

    M721

    M724HV Sliding refrequired

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    50/70

    Power Quality Monitoring

    50

    Medicin de calidad de potenciaRed de transmisin

    SUB-TRANSMISION

    DISTRIBUCION

    DISTRIBUCION

    SECUNDARIA

    RED BAJATENSION

    G

    G

    G

    G

    G

    RED DEDISTRIBUCIONRURAL

    GENERACION

    IPPGENERACION

    IPP

    GeneracinMunicipal

    CO-GENERACIONCONSUMODOMESTICO

    TRANSFORMADORES URBANOS

    INDUSTRIA

    INDUSTRIA

    M722

    M722

    M722

    M723

    M723

    M724

    M723

    M724

    M723

    M722

    M721

    M721

    M723

    M722 M722

    M721

    M724HV Sliding refrequired

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    51/70

    Power Quality Monitoring

    51

    Parameters

    Nb of channels

    Moni

    toring

    :

    Phase Voltage (Va, Vb, Vc)

    Negative Sequence Voltage

    Current (Ia, Ib, Ic)

    Neutral Current

    Active Power (Pa, Pb, Pc, PT)

    Power Factor (Pf1, Pf2, Pf3, PfT)

    Memory

    4 U/ 4 I 4 U/ 4 I 4 U/ 4 I 4 U/ 4 I

    1 Mb 4 Mb 8 Mb 8 Mb

    Line Voltage (Vab, Vbc, Vca)

    Reactive Power (Qa, Qb, Qc, QT)

    Apparent Power (Sa, Sb, Sc, ST)

    Frequency

    * * * *

    * * * *

    * * * *

    * derived quantity

    Harmonics V

    Waveform Capture

    Harmonics I

    Range M721 M722 M723 M724

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    52/70

    Power Quality Monitoring

    52

    Parmetro

    Nmero de canales

    Tensin de Fase (Va, Vb, Vc)

    Tensin de secuencianegativaCorriente: Ia, Ib,

    IcCorriente deneutroPotencia Activa: Pa, Pb, Pc,PT

    Factor de potencia: Pf1, Pf2, Pf3,PfT

    Memoria

    4 U/ 4 I 4 U/ 4 I 4 U/ 4 I 4 U/ 4 I

    1 Mb 4 Mb 8 Mb 8 Mb

    Tensin de lnea: Vab, Vbc,Vca

    Potencia reactiva: Qa, Qb, Qc,QTPotencia Aparente: Sa, Sb, Sc,ST

    Frecuencia

    * * * *

    * * * *

    * * * *

    * Parmetro calculado

    Componente harmnica deV

    Captura de forma de

    onda

    Componente harmnica de I

    M721 M722 M723 M724

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    53/70

    Power Quality Monitoring

    53

    Parameters

    Nb of channels

    Sampling Frequency

    Inter-harmonics

    K-Factor

    Storage T_very_short (3sec)

    4 U/ 4 I 4 U/ 4 I 4 U/ 4 I 4 U/ 4 I

    PQ

    Mo

    nitoring:

    (50) (50) (50) (50)/(100*)

    (2) (4) (8) (8)(Pstimax)(Pst) (Pstimax)(Pst)

    IEC 1000-4-7

    IEC 61000-4-15

    5 120 Hz 5 120 Hz 5 120 Hz 5 120 Hz10 240 Hz *

    HV Sliding reference

    Slow VariationsDips , InterruptionsFrequencyHarmonics, THDRipple clockFlicker

    Unbalance rate

    * option

    EN50160 / IEEE 1159

    Configurable standards

    Range M721 M722 M723 M724

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    54/70

    Power Quality Monitoring

    54

    ParmetroNmero de

    canales

    Frecuencia demuestreo

    Inter-harmonics

    K-Factor

    Storage T_very_short(3sec)

    4 U/ 4 I 4 U/ 4 I 4 U/ 4 I 4 U/ 4 I

    (50) (50) (50) (50)/(100*)

    (2) (4) (8) (8)(Pstimax)(Pst) (Pstimax)(Pst)

    IEC 1000-4-7

    IEC 61000-4-15

    5 120 Hz 5 120 Hz 5 120 Hz 5 120 Hz10 240 Hz *

    HV Slidingreference

    Variacin lentaDips , InterrrupcionesFrecuenciaHarmonicos, THDRipple clockFlicker

    Desbalance fases

    * opcional

    EN50160 / IEEE 1159Configurabl

    e

    M721 M722 M723 M724

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    55/70

    Power Quality Monitoring

    55

    PQM Analysis software : QR Manager:

    95 %

    99 %

    Paramtre 1 - Paramtre 2 - Paramtre 3 - ......- Paramtre N

    Data Analysis : Computation of probability 95% (EN50160), 100% or any

    other desired percentage

    Representation of the PQ data in Time domain

    Representation of the PQ data compared to Power

    Quality patterns (CBEMA, ITIC curves, customised)

    Bar chart 3D for sorting out

    dips and Interruptions

    SARFI indicators

    DISDIP table

    PQ Report generation

    Report

    Generation

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    56/70

    Power Quality Monitoring

    56

    Software de anlisis PQM : Administrador QR:

    95 %

    99 %

    Paramtre 1 - Paramtre 2 - Paramtre 3 - ......- Paramtre N

    Anlisis de datos: Clculo de probabilidad 95% (EN50160)

    100% u otro porcentaje requerido.

    Grfico temporal de los parmetros de calidad. Comparacin grfica de los parmetros medidos

    con modelos normalizados (CBEMA, curvas ITIC,

    personalizado)

    Grfico de barras 3D. Indicadores SARFI

    Tabla DISDIP

    Generacin de reporte.

    ReportGeneration

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    57/70

    Power Quality Monitoring

    57

    Trend

    curves

    viewing

    integrationto the PQ

    report with

    the PQ

    profile

    QR Manager - Report generation

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    58/70

    Power Quality Monitoring

    58

    Curvas de

    tendencias

    Integracin

    del reportePQ con el

    perfil PQ

    Administrador QR - Generacin de Reporte

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    59/70

    Power Quality Monitoring

    59

    x% value

    cumulated

    probability

    integrationto the PQ

    report

    QR Manager - Report generation

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    60/70

    o e Qua ty o to g

    60

    Porcentaje del

    valor

    Probabilidad

    acumulada Integracin al

    reporte PQ

    Administrador QR - Generacin de reporte

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    61/70

    Q y g

    61

    Discrete trend

    curve

    integration to the

    PQ report

    QR Manager - Report generation

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    62/70

    Q y g

    62

    Curvas de

    tendencia

    discreta

    Integracin alreporte PQ

    Administrador QR - Generacin de reporte

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    63/70

    y g

    63

    Swell event

    Points

    representati

    on integration to

    the PQ

    report

    QR Manager - Report generation

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    64/70

    y g

    64

    Zoom

    Representa-

    cin de

    Puntos Integracin

    al reporte

    PQ

    Administrador QR - Generacin de reporte

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    65/70

    y g

    65

    Downtime

    Power Quality

    Regulations

    Integration

    Costs

    Staff Shortages

    Privatisation

    TechnologyManagement

    EvolvingTechnology

    ZA2490

    ELECTRICITY SUPPLY IN A CHANGING

    WORLD

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    66/70

    y g

    66

    Tiempo fuerade servicio

    Calidad de

    Potencia

    Regulaciones

    Integracin

    Costos

    Escasez depersonal

    Privatizacin

    Manejo de laTecnologa

    Tecnologaevolutiva

    ZA2490

    SUMINISTRO DE ENERGIA EN UN MUNDO

    CAMBIANTE

    Power Quality Monitoring

  • 5/21/2018 BIEL - Original

    67/70

    y g

    67

    ENERGY ACTORS

    Customer wants :New servicesAccess to the PQ data,Loyalty

    Pay only for what heZA2491

    PQ ISSUES

    Power Quality Monitoring