SEPAM - Protection Relays
Series 20 - 40
PT. Wilmar Gresik, 24 April 2012
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 2/26
2
Sepam series 20:
simple solutionsfor usual applications
Sepam series 40:high-performing solutions
for demanding applications
Sepam series 80:
intelligent solutions
for custom applications
Sepam – Protection Relays
A Range of Solution for All Applications
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 3/26
3
Sepam – Protection Relay
Standard Applications
For industrial and
service sector site
networks
For public distribution
networks
For all voltage levels
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 4/264
Sepam – Substation Application
Series 20 / Type : S20
Substation incomer and
feeder applications
Protection functions:
50/51, phase over
current 50N/51N, earth fault
46, negative
sequence / unbalance
Logic discrimination
4-cycle recloser
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 5/265
● Parallel incomers or closed
ring networks
● Isolated or compensatedneutral networks
● Protection functions:● 50/51,50N/51N,46,50BF● 67N/67NC,
directional earth fault● 67, directional phase
overcurrent● 32P, reverse power
● I, U, P, E metering
Sepam – Substation Application
Series 40 / Type : S40 / S41 / S42
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 6/266
Protection functions:
50/51, 50N/51N and46
49RMS, thermal
overload 38/49T, temperature
monitoring (8
sensors)
Processing of faults
detected by transformer
Buchholz or thermostat
(MES module required)
Sepam – Transformer Protection
Series 20 / Type : T20
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 7/267
● Parallel transformers
● Isolated or compensatedneutral networks
● Protection functions:
● 50/51,50N/51N, 46,50BF● 49RMS and 38/49T● 67N/67NC, directional
earth fault● 67, directional phase
overcurrent
● I, U, P, E metering
Sepam – Transformer Protection
Series 40 / Type : T40 / 42
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 8/26
8
Protection functions:
50/51, 50N/51N, 46
49RMS
38/49T
Specific functions:
37, phase undercurrent 48/51LR, excessive
starting time and
locked rotor
66, starts per hour specific motor-related
function (MES114)
Sepam – Motor Protection
Series 20 / Type : M20
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 9/26
9
● Isolated or compensated
neutral networks
● All the M20 protectionfunctions, plus:● 67N/67NC, directional
earth fault● 32P, reverse power ● 27/59, 81L/81H, …
● Automatic load shedding
● I, U, P, E metering
Sepam – Motor Protection
Series 40 / Type : M41
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 10/26
10
● Protection functions:● 50/51, 50N/51N,46,50BF● 49RMS and 38/49T● 27/59, 81L/81H, …
● Specific functions:● 50V/51V, voltage restraint
overcurrent● 32P, 32Q/40, directional
active and reactiveoverpower
● I, U, P, E measurements
Sepam – Generator Protection
Series 40 / Type : G40
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 11/26
11
Voltage protection functions:
27/59, phase-to-phase
under/overvoltage
81L/81H,
under/overfrequency
59N, neutral voltage
displacement
27D/47, positive sequence
undervoltage and phase
rotation direction
27R, remanent undervoltage
27S, 3 phase-to-phase
undervoltages V1,V2,V3
Sepam – Busbar Protection
Series 20 / Type : B21
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 12/26
12
Voltage protectionfunctions:
27/59, 27S, 59N 81L/81H 27D/47, 27R
Loss of mains protection
81R, rate of change offrequency (ROCOF)fast, reliable detection
of loss of mainsfor substations with
generators in parallelwith the main network
Sepam – Busbar Protection
Series 20 / Type : B22
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 13/26
13
Selection criteria series 20 series 40
Measurements I U U I and U I and U I et U
Specific protection Loss of mains Directional Directional
functions (ROCOF) earth fault earth fault &
phase O/C
Applications series 20 series 40
Substation S20 S40 S41 S42
Transformer T20 T40 T42
Motor M20 M41
Generator G40
Busbar B21 B22
Sepam – Protection Relay
Selection Guide
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 14/26
14
User Machine Interfaces
Logic inputs / outputs
Communication
Temperature acquisition
Analog output
Sepam – Protection Relay
Basic Unit and Optional Module
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 15/26
15
To manage your installation
locally!
The keypad and display are used to set the Sepam parameters and protection
functions and to display measurements and alarms.
The advanced UMI does not give access to the matrix (use SFT2841).
Sepam – Protection Relay
Advanced User Machine Interface
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 16/26
16
To make the most of your
Sepam !
The SFT2841 tool may be used to set parameters and protection functions and
«customize» Sepam. It provides the alarm history, disturbance records and
parameter down and uploading.
Sepam – Protection Relay
SFT2841 Configuration Software
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 17/26
17
4 logic outputs as a
standard feature
a choice of 2 additional
input/output modules:
MES108: 4 logic
inputs/4 logic outputs
MES114: 10 logic
inputs/4 logic outputs
To enhance the
monitoring/control functions
Sepam – Protection Relay
MES – Additional Input/Output
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 18/26
18
Modbus/Jbus protocol
Measurement readouts
TS status readouts
Logic input status readouts
TC remote control orders
Remote settingsControl of the optional MSA114 analog
output
Disturbance recording OPG readouts
Sepam – Protection Relay
Communication Functions
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 19/26
19
Modbus communication
protocol
ACE949-2: RS485 2-wirecommunication interface with
distributed supply
2 wires for the RS485
signal2 wires to supply the
ACE949-2
Auxiliary supply for the
ACE949-2 provided by the ACE909-2 interface or the
ACE919 or a 12 or 24 V DC
external power supply
Sepam – Protection Relay
Communication Interface
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 20/26
20
Modbus communication
protocol
ACE959: RS485 4-wirecommunication interface with
distributed supply
4 wires for the RS485
signal2 wires to supply the
ACE959
Auxiliary supply for the
ACE959 provided by a 12 or 24V DC external power supply
Sepam – Protection Relay
Communication Interface
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 21/26
21
Note : 1 module for Sepam series 20
1 to 2 modules for Sepam series 40
Measurementof 8 or 16 temperatures
By Pt100, Ni100 or Ni120temperature sensors
For better motor, generatorandtransformerprotection!
Sepam – Protection Relay
Temperature Acquisition
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 22/26
22
A choice of formats
(4-20mA, 0-10mA or
0-20mA)
For remote analog
measurements!
Sepam – Protection Relay
Analogue Output
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 23/26
23
Sepam – Protection Relay
A Complete Solution
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 24/26
24
Same cutout as Sepam 1000
Compact, reduced depth (< 100mm)
Universal power supply48 to 250 V DC and 110 to 240 V AC
and 24 V DC power supply
Universal logic inputs
24 to 250 V DC
Engraved terminal identification
Immunity to 10V/m radiated fields
Disconnectable I/O module
Prewired remote modules
Extended temperature range: -25°C to 70°C
<100mm
Sepam – Protection Relay
Easy To Install – Series 20
8/19/2019 Sepam-Basic Presentation 240412
http://slidepdf.com/reader/full/sepam-basic-presentation-240412 25/26
25
● Base unit:
●new basic board
●3 resident voltage channels (3 internal transformers)
● the same size as Sepam 1000+ series 20
(same cutout dimensions and same depth)
● Auxiliary power supply:
●universal: 24 V DC to 250 V DC and 100 V AC to
240 V AC
power line disturbance withstand: 20 ms
●consumption < 15W