Efectos de ondas distorsionadas en transformadores de medida
Transcript of Efectos de ondas distorsionadas en transformadores de medida
![Page 1: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/1.jpg)
Efectos de ondas distorsionadas
en transformadores de medida
Ing. Alejandro Santos
Laboratorio UTE
Uruguay
![Page 2: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/2.jpg)
Equipo de Investigacion del Laboratorio de UTE
• Daniel Slomovitz
• Leonardo Trigo
• Gonzalo Aristoy
• Marcelo Brhem
• Alejandro Santos
• Personal de los diferentes departamentos del Laboratorio de UTE
![Page 3: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/3.jpg)
INTRODUCCIÓN
• Causas que llevan a desarrollar un sistema de medida para altas frecuencias.
– Cargas no lineales
– Generación distribuida
• Aerogeneradores
• Células Fotovoltaicas
• Acumuladores de Energía
– Desarrollo de redes inteligentes
![Page 4: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/4.jpg)
INTRODUCCIÓN
• Se crean regulaciones para cuantificar el contenido de armónicos en las redes.
• Esta cuantificación se realiza a través de transformadores de medida (normalmente calibrados a frecuencia industrial 50 Hz, 60 Hz)
• Requerimientos adicionales fueron agregados a la normativa vigente (IEC/TR 61869-103)
• En las redes actuales gran numero de transformadores deben ser verificados
![Page 5: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/5.jpg)
IEEE 519 es la norma que establece los limites del contenido de armónico en redes.
Redes entre 120V y 69kV Redes entre 69kV y 161kV
![Page 6: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/6.jpg)
IEEE 519
• Limites bajos se aplican a armónicos de orden superior en redes de alta tensión y bajas corrientes de corto circuito.
• La incertidumbre del sistema de medida propuesto debe ser bajo (0.04% o menor de
acuerdo a las tablas vistas anteriormente)
• Armónicos pares tienen limites aun menores
• Se requiere un sistema de alta precisión
![Page 7: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/7.jpg)
INTRODUCCIÓN
• Muchos trabajos proponen estudios a diferentes frecuencias que la nominal, pero están basados en respuesta en frecuencia en ensayos realizados a diferentes condiciones a las nominales.
• Si la excitación del núcleo, es diferente en los test que la de trabajo, el comportamiento del transformador puede ser diferente debido a su comportamiento no lineal
![Page 8: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/8.jpg)
INTRODUCCIÓN
• En este trabajo una fuente de potencia de onda programable es propuesta, para estudiar los CT VT y CVT bajo condiciones similares a las existentes en las redes
![Page 9: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/9.jpg)
Fuente de potencia onda distorsionada
![Page 10: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/10.jpg)
Fuente de potencia onda distorsionada
![Page 11: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/11.jpg)
Fuente de potencia onda distorsionada
• La fuente está compuesta por:
• Generador programable
• Un amplificador de potencia
![Page 12: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/12.jpg)
Generador programable
• Existen muchos generadores de onda arbitrarias comerciales ,pero no se encontraron que fueran capaces de gran flexibilidad (arbitraria amplitud y fase de
armónicos)
• Se selecciono por esto tarjetas multifunción programables capaces de generar cualquier onda que se seleccione
![Page 13: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/13.jpg)
Amplificador de potencia
• La potencia de ensayo es fundamentalmente la de la inductancia de perdidas del circuito de alta corriente ( aprox 10 kVA fp 0.7 para 1000A de
corriente primaria).
• El principal componente es un amplificador de audio de 50 kW de potencia
• Se sustituyo la batería por un rectificador
• Se colocaron filtros para eliminar ruido HF del amplificador
![Page 14: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/14.jpg)
Transductor de Tensión Rama de AT
• Capacitor AT HIGHVOLT MCP100 100pF
• Valor certificado de calibración 100,091pF
• Temp. Range 5….40°C
• coef. Var. 26ppm°C
![Page 15: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/15.jpg)
Transductor de Tensión Rama de BT
![Page 16: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/16.jpg)
Sistema de medida de transformadores de tensión
![Page 17: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/17.jpg)
Sistema de medida de transformadores de tensión
Las tensiones del primario y el secundario del transformador bajo ensayoson rediucidas por un divisores de tensión. La tension primaria es reducidapor un divisor capacitivo formado por un capacitor patron de AT 100-pF-SF6 en serie con una red de capacitores de baja tensión.
La tensión secundaria es reducida por un divisor resistivo construido con resistencias de alta estabilidad térmica (Vishay).
Las salidas de los divisores de tensión son enviadas a conversoresanalógicos digital (ADC) de las tarjetas DAQ 6211.
Ambos canales son digitalizados en forma sincrónica, para permitir la medida de fase entre ellos. Los datos son enviados al PC para suprocesamiento..
![Page 18: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/18.jpg)
Transformadores de Tension
![Page 19: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/19.jpg)
Transformadores de tension
• Diferentes tipos de transformadores de tensión existentes en la red fueron analizados
• En redes de AT principalmente son de dos tipos :
– Transformadores Inductivos IVT
– Transformadores capacitivos CVT
![Page 20: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/20.jpg)
Transformadores Inductivos
![Page 21: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/21.jpg)
Modelo de transformador de tensión inductivo
Z1 y Z2 son impedancias de bobinado primario y secundario
ZM es la rama de magnetización, modelada por una resistencia en paralelo con un inductor no lineal
El comportamiento de este inductor se tiene en cuenta modificando su valor en función del voltaje aplicado
A bajas frecuencias, los errores en IVT se deben a caídas de tensión en la impedancia serie Z1 y Z2.
PRUEBAS
Realizamos dos pruebas diferentes. Pruebas de bajo voltaje hasta 20 kHz y pruebas de voltaje nominal de hasta 3 kHz
![Page 22: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/22.jpg)
Ensayos a BT
Las ensayos se realizaron con un equipo SFRA, con voltajes de alrededor de 10 V. Las Figuras 2 a 4 muestran el comportamiento de la respuesta de frecuencia de diferentes IVT utilizados en redes de alta tensión.
Todas las curvas muestran un comportamiento similar de hasta 2 kHz, correspondiente al 40 ° armónico
La variación de relación a 2 kHz alcanza valores de hasta 20% para el IVT de 150 kV
![Page 23: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/23.jpg)
Ensayos a Tensión nominal
Estas pruebas se realizaron a 53 Hz de frecuencia fundamental, para evitar la influencia del ruido de la red eléctrica.
La tensión a frecuencia fundamental se estableció entre 80% y 100% del valor nominal
Se realizó una primera prueba añadiendo a la frecuencia fundamental tonos únicos desde el componente 3 ° (159 Hz) hasta el 49 ° (2597 Hz). La amplitud de los componentes armónicos se estableció alrededor del 10%.
En esta condición, los errores del transformador se midieron para fundamental y cada armónico.
![Page 24: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/24.jpg)
Ensayos a tensión nominal
Se realizó un segundo ensayo aplicando fundamental y todos los armónicos juntos . De nuevo, se midió el error del transformador en el componente fundamental y en cada componente armónico . Las figuras 5 a 8 muestran el error de relación y el desplazamiento de fase con tonos únicos y con alta distorsión (todos los componentes armónicos al mismo tiempo).
No se detectaron diferencias entre ambas pruebas, lo que concuerda con un comportamiento lineal de las IVT probadas . Las formas de estas curvas son muy similares a las obtenidas de las pruebas de bajo voltaje, pero las diferencias de relación no permiten el uso de pruebas de bajo voltaje para la corrección de errores. Si se pretende usar factores correctivos, se deben realizar pruebas con voltaje nominal.
![Page 25: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/25.jpg)
Transformadores de Tensión Capacitivos
![Page 26: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/26.jpg)
Transformadores de Tensión Capacitivos
![Page 27: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/27.jpg)
Modelo TVC
R1 ,L1Resistencia e inductancia correspondiente al primario. Las correspondiente al secundario R2 y L2. Rt y Lt son resistencia e inductancia del reactor de sintonización.La impedancia de magnetización está representada por la resistencia Rm en paralelo con inductancia Lm. Las pérdidas de la sección del condensador están representadas por Rc1 y Rc2.La inductancia en serie total incluye la inductancia de fuga L1 + L2 y la sintonizacióninductancia Lt.
![Page 28: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/28.jpg)
Dependencia de la Frecuencia
• En los CVT, la resonancia debe producirse entre la reactancia capacitiva y la inductiva a la frecuencia nominal.
• No se espera que los CVT tenga la misma precisión para las frecuencias que se desvían de la nominal.
• IEC 60044-5 especifica que para una clase de medición se debe mantener la precisión para una variación de frecuencia entre 99-101% de la frecuencia nominal
• Para la clase de protección entre 96-102%.
• La sensibilidad para las variaciones de frecuencia depende de la capacitancia equivalente y la tensión intermedia.
![Page 29: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/29.jpg)
Diagrama simplificado
Se muestra el modelo más simple para este tipo de VT, C1 y C2 forman un divisor de tensión capacitivo que es seguido por un inductor compensador y un transformador convencional de media tensión.
El inductor está diseñado para resonar con los condensadores a frecuencia nominal.
Pero, en otras frecuencias, la impedancia serie aumenta, por lo que los errores aumentaran tambien.
![Page 30: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/30.jpg)
Errores bajo ondas distorsionadas
Calibration configuration of
CVT
Para la prueba, se utilizó el circuito equivalente, que se muestra.
La terminal baja C2 se desconectó de la tierra y se conectó a la terminal superior de C1.
Esta reconfiguración de la CVT, para fines de calibración, está permitida por la norma [2]. Supone que los condensadores tienen el mismo valor en cualquier voltaje.
Todos los componentes, excepto el divisor capacitivo, se excitan a sus voltajes nominales.
La ventaja de este método es que la fuente de alimentación tiene menor voltaje y potencia que en las pruebas convencionales.
![Page 31: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/31.jpg)
Errores bajo ondas distorsionadas
Se realizaron muchas pruebas en diferentes unidades desde 60 kV hasta 500 kV. Como ejemplo, las figuras 10 y 11 muestran el error de relación y el desplazamiento de fase para una CVT de 150 kV, 200 VA, clase 0.5, a dos voltajes diferentes: 80% y 120% del nominal.
El voltaje aplicado tenía contenidos armónicos que incluyen muchas órdenes desde el 3 ° hasta el 49 °. La amplitud de cada uno fue de alrededor del 10%.
Los resultados muestran que este transformador tiene errores muy grandes en cualquier frecuencia armónica.
Por otro lado, la mayoría de los TT instalados en redes de alta tensión son de este tipo, y no es práctico cambiarlos por otros tipos que permitan la medición de armónicos.
![Page 32: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/32.jpg)
Conclusiones CVT
• Se realizaron muchas pruebas en diferentes unidades desde 60 kV hasta 500 kV. Como ejemplo, las figuras 10 y 11 muestran el error de relación y el desplazamiento de fase para una CVT de 150 kV, 200 VA, clase 0.5, a dos voltajes diferentes: 80% y 120% del nominal.
![Page 33: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/33.jpg)
Conclusiones CVT
• El voltaje aplicado tenía contenido armónico que incluía muchos órdenes desde el 3 ° hasta el 49 °. La amplitud de cada uno fue de alrededor del 10%.
• Los resultados muestran que este transformador tiene errores muy grandes en cualquier frecuencia armónica.
![Page 34: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/34.jpg)
Conclusiones CVT
• Por otro lado, la mayoría de los VT instalados en redes de alta tensión son CVT de este tipo, y no es práctico cambiar por otros tipos que permiten la medición de armónicos.
• El método de ensayo de baja tensión(FRA) es útil para obtener una vista rápida de la respuesta de frecuencia.
![Page 35: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/35.jpg)
Conclusiones CVT
• Para conocer con precisión el valor de los errores, se deben realizar pruebas con voltaje nominal.
• Los errores IVT se pueden compensar utilizando factores correctivos para cada armónico, pero esto no se puede hacer para la CVT. Sus errores son tan grandes que son necesarias otras técnicas de compensación.
![Page 36: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/36.jpg)
Modelado de transformadores capacitivos
• Motivacion: Como vimos los Tvc tienen grandes errores a todas las frecuencias diferentes de la fundamental
• Se tratara de predecir su comportamiento con diferntes ondas distorsionadas
• Un apropiado modelo permitira estimar los errores y ayudar a la compensacion de los mismos
•
![Page 37: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/37.jpg)
Modelado de transformadores capacitivos
• El modelo debera reproducir el error con una onda distorsinada de hasta 8% del valor de cada armonico y hasta el armonico 50 IEC 61869-103 TR
• Ensayos con unidades en servicio serviran para validar el modelo
![Page 38: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/38.jpg)
CVT Models (1)Simplest model -capacitive divider, -inductor for compensation of capacitive reactance-intermediate medium voltage transformer.
Voltage: 60 kV to 500 kV
![Page 39: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/39.jpg)
CVT Models (2)
Complex model with 23 components (Vermeulen, Davel):
![Page 40: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/40.jpg)
CVT Models (2)
Problems:
-Parameters cannot be evaluated directly by external tests.
-Different distorted waveforms may lead to different values of the parameters.
Possible solutions:
- Adjust the parameters according to experimental data.
- Frequency response analysis at very low voltage.
- Disassemble the electromagnetic unit (laboratory cases)
![Page 41: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/41.jpg)
Proposed CVT model
![Page 42: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/42.jpg)
Proposed CVT model
- Fewer parameters than the previous one
- Match the general behavior of the CVT within the frequency range of interest.
- Possible to divide it into blocks for better study
![Page 43: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/43.jpg)
Proposed CVT model Blocks
-Capacitive Divider
-Compensation Inductor
-Intermediate (Medium Voltage) Inductive Transformer
-Block of non-linear elements (R and L)
![Page 44: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/44.jpg)
Proposed CVT model Blocks
-Capacitive Divider:
Assumed as an ideal divider
-Compensation Inductor:
Modeled as: ideal inductor + parallel type capacitance + parallel type resistance
![Page 45: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/45.jpg)
Proposed CVT model Blocks
-Capacitive Divider:
Assumed as an ideal divider
-Compensation Inductor:
Modeled as: ideal inductor + parallel type capacitance + parallel type resistance
![Page 46: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/46.jpg)
Proposed CVT model Blocks
-Medium voltage transformer:
Modeled as: ideal transformer + magnetizing impedance
-Non-linear elements (Anti-ferroresonance):
For this work, only the influence in normal operation will be studied.
![Page 47: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/47.jpg)
Experimental tests
A 500 kV CVT electromagnetic unit was subjected to various tests and later dismantled to study its components
![Page 48: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/48.jpg)
Experimental tests: External tests
External test of the Compensation Inductor
• This type of transformer has external connection between low side of capacitive divider and input of EM unit. Thus, it is possible to test the compensation inductor without disassembling the EM unit.
• To do this, the outputs were short circuited, and an increasing voltage (between 40 and 2300 volts) is applied to the input.
• Voltage, current, power and angle measurements were made using a FLUKE 41 Analyzer, with a Chauvin Arnoux 1000:1 ratio current clamp (with a 100 Ω load)
![Page 49: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/49.jpg)
Experimental tests: External tests
Compensation Inductor test results:
• Inductance and quality factor values had showed no significant variations in all the tested range
• Measured impedance: 23 kΩ
• Measured inductance: 72 H
This data shows that the inductor was designed to work in its linear region (no saturation is reached under normal conditions of use)
For the purpose of modelling, we also need the stray capacitance between turns, but it can not be obtained from external test.
![Page 50: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/50.jpg)
Experimental tests: External tests
Intermediate transformer no-load test
• It is a transformer with primary rated voltage of 11.5 kV , one secondary of 200/3 V and two of 200/√3 V.
• The no-load test result obtained from the side of 200/3 V is shown in the next figure.
![Page 51: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/51.jpg)
Experimental tests: External testsIntermediate transformer no-load test results:
The ratio is linear up to 150% of the rated voltage
![Page 52: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/52.jpg)
Experimental tests after disassemblingCompensation Inductor frequency sweep (using a QUADTECH
7600 impedance analyzer)
fpr= 2.2 kHz
C = 80 pF
![Page 53: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/53.jpg)
Experimental tests after disassembling
Anti-ferroresonance circuit test:
The anti-ferroresonance circuit comprises several coils and resistors connected at the secondary windings
Upper curve: 12Ω resistor in series with coil “A”.
Lower curve: Coil “B” (in parallel wit the previous set)
For nominal conditions the circuit can be modeled as a resistor
![Page 54: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/54.jpg)
FRA test The values of the components of the proposed model were
determined also by a FRA test (before disassembling). Figure shows
the magnitude (upper curve) and the phase shift (below).
![Page 55: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/55.jpg)
Simulation The parameters of the model were adjusted until the simulated curves
fit the experimental ones. Simulatios were done using the MicroCap 11 software.
• Results:
Magnitude
Phase shift
![Page 56: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/56.jpg)
Tests vs. simulation
• There is good coincidence up to 2-3 kHz in FRA test. At frequencies greater than 5 kHz, there are clearly major differences.
• On the other hand, differences between the model components values determined by FRA with those values measured by specific tests are:
39% for the compensation inductor
-80% for the magnetizing impedance of the transformer
![Page 57: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/57.jpg)
Future works
• The large differences found corroborate that low voltages tests are not suitable for CVT modeling. So, for better parameter determination, voltages in the order of nominal ones will be used in future tests.
• Also, some parameters can be obtained from the information provided by the manufacturer
• The following step is to develop a compensating device to reduce the CVT's errors
![Page 58: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/58.jpg)
Conclusions
• CVT's models were analyzed from the simplest one to a 23 component model.
• An 8 parameters model was proposed as it can be well adjusted to represent the real behavior within the frequency range of interest and all parameters can be determined from conventional tests.
• A 500 kV CVT was dismantled and its components were measured separately to validate the model.
![Page 59: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/59.jpg)
Transformadores de corriente bajo ondas distorsionadas
Se realizaron varios tipos de ensayos para estudiar el comportamiento de los TC
Ensayos con generadores de onda programables a corrientes diferentes de la nominal
Ensayos con el equipamiento antes descripto a valores nominales de corriente
![Page 60: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/60.jpg)
Circuito de ensayo Los ensayos realizados se basaron en un sistema patrón de calidad de onda [4],[5] compuesto por dos digitalizadores Agilent 3458, un generador de onda distorsionada Fluke 6100, y una PC con software para el análisis de los datos. Adicionalmente se utilizaron dos resistores shunt como transductores de corriente a tensión.
![Page 61: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/61.jpg)
Transformadores de corriente bajo ondas distorsionadas
Los ensayos realizados se pueden dividir en tres tipos
Ensayos de tonos puros (se exita el TC con solo una frecuencia)
Ensayo de fundamental y un armonico
Ensayo de fundamental y varios armonicos .
Para todos estos ensayos se calcula el error
![Page 62: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/62.jpg)
Calculo del error
Para cada una de las
frecuencias se calcula el error
del transformador bajo la
definición clásica de error [7].
En (1) se puede observar
dicha definición, donde el
parámetro k es la relación
nominal entre primario y
secundario. Y los subíndices
p y s denotan primario y
secundario respectivamente.
![Page 63: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/63.jpg)
Transformadores de corriente bajo ondas distorsionadas
El segundo tipo de ensayo
realizado es superponer una
onda a la de frecuencia
fundamental múltiplo de la
fundamental. Se observa que
el error es definido en base
al propio armónico y no
interviene la fundamental.
![Page 64: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/64.jpg)
Transformadores de corriente bajo ondas distorsionadas
Por último, se realizan
ensayos superponiendo
todos los armónicos y la
fundamental a la vez,
manteniendo la misma
definición de error que en
(2) para cada uno de los
armónicos
![Page 65: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/65.jpg)
Transformadores de corriente bajo ondas distorsionadas
Adicionalmente a los
ensayos antes descriptos, se
realizó un ensayo de vacío
visto desde el secundario
con el fin de medir el valor
de la impedancia
magnetizante y a partir de
ella estimar los errores del
transformador a distintas
frecuencias.
![Page 66: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/66.jpg)
Transformadores de corriente bajo ondas distorsionadas
La Fig. 3 muestra el
valor del módulo y la Fig.
4 el valor del ángulo de
dicha impedancia.
![Page 67: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/67.jpg)
Transformadores de corriente bajo ondas distorsionadas
Los errores a
diferentes frecuencias se
estimaron utilizando el
modelo de transformador
que se observa en la Fig. 5
![Page 68: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/68.jpg)
Transformadores de corriente bajo ondas distorsionadas
La Tabla 1 muestra los
errores calculados a partir
del modelado. En las
columnas 2 y 3 se
observan los errores
estimados, y en las 4 y 5
los errores medidos según
el primer método para los
armónicos analizados.
Tabla I.
Error Estimado Error medido f (Hz) ε(ppm) δ (μrad) ε (ppm) δ (μrad)
53 -382 732 -281 588 106 -297 431 -130 619
159 -266 323 -117 420
212 -248 262 -110 316 265 -237 228 -102 258
371 -220 184 -95 183
477 -207 160 -91 141 583 -198 146 -89 110
689 -190 136 -87 88
![Page 69: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/69.jpg)
Transformadores de corriente bajo ondas distorsionadas
En la Tabla II se comparan
los errores del
transformador cuando se
lo somete a tonos puros
versus cuando se lo
somete a todos los
armónicos a la misma vez.
Tabla II.
Error tonos puros Error al mismo tiempo.
f (Hz) Amplitud ε(ppm) δ (μrad) ε (ppm) δ (μrad)
53 8 A -274 606 -311 589
159 1 A -116 420 -155 -380
265 1 A -102 258 -148 -201
371 1 A -95 183 -100 -137
477 1 A -91 141 -81 -102
583 1 A -89 110 -69 -78
689 1 A -87 88 -64 -59
795 1 A -84 71 -51 -24
1113 1 A -80 34 -46 -1
![Page 70: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/70.jpg)
Conclusiones de ensayo onda distorsionada en BT
Se observa que existe una gran diferencia en el
error en fase del transformador entre aplicar
una onda de manera independiente (tono puro)
a cuando está sometido a múltiples ondas
sumadas.
![Page 71: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/71.jpg)
Conclusiones de ensayo onda distorsionada en BT
Las diferencias son apreciables en el error en
fase para todos los armónicos. En cambio los
errores en modulo no tienen grandes
diferencias. En el caso de la fundamental los
errores no tienen gran diferencia entre estar
aplicado como tono puro, que acompañado de
distorsión.
![Page 72: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/72.jpg)
Conclusiones de ensayo onda distorsionada en BT
Se puede concluir que el mismo tiene un
comportamiento no lineal y no es válida la
hipótesis de superposición. Esto es coherente
con publicaciones que concluyen no
linealidad, aunque no concuerda con otra
publicaciones donde se proponen barridos en
frecuencia como método para evaluar el
comportamiento frente a ondas distorsionadas
con múltiples armónicos.
![Page 73: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/73.jpg)
Transformadores de corriente bajo ondas distorsionadas a valores
nominales
Como ya habiamos dicho la idea es poder determinar el error del TC bajo ondas distorsionadas a valores nominales similares a los que se ve sometido en las instalaciones yver su variacion respecto al error a frecuencia nominal. La idea es medir el error a cada armonico y cuando muchos a la vez estan presentes.
![Page 74: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/74.jpg)
Fuente onda distorsionada
![Page 75: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/75.jpg)
Transductores corriente tensión
• Para bajas corrientes shunts patrones fueron utilizados ( pero no es posible usarlos por encima
de 10 A)
• Para corrientes superiores a 10 A bobinas de Rogowsky se usarán( Se estudió la respuesta en
frecuencia de los transductores ).
![Page 76: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/76.jpg)
![Page 77: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/77.jpg)
Transductores corriente/tension
![Page 78: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/78.jpg)
Transductores corriente /tension
![Page 79: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/79.jpg)
Transductores corriente/tension
![Page 80: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/80.jpg)
Transductores corriente /tension
![Page 81: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/81.jpg)
![Page 82: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/82.jpg)
CT 150 kV 400-200/5A cl 0.5
FECHA: 13/12/2016 Se prueba devanado de medida HB, BT, 400/5, cl. 0,5, 30 VA, laboratorio No 45512
Hz 53 159 265 583 1537 2597
N° 1 3 5 11 29 49
Carga I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad)
30 VA 5,00 -0,0600 -0,0015
30 VA 3 -0,1200 -0,0052
0,50 -0,1200 -0,0035
30 VA 5,00 -0,0500 -0,0020 9 -0,7500 -0,0040
30 VA 3,00 -0,1200 -0,0060 9 -1 -4,4e-3
0,50 -0,1250 -0,0038 -0,2800 0,0003
30 VA 5,00 -0,1200 -0,0030 10 -0,3000 -0,0020
30 VA 3,00 -0,1600 -0,0048 10 -0,2400 -0,0004
0,50 -0,1400 -0,0032 0,0200 0,0000
30 VA 3,00 -0,1300 -0,0050 10 -0,1600 0,0015
30 VA 0,50 -0,1400 -0,0030 10 0,0500 0,0008
30 VA 3,00 -0,1400 -0,0050 8 -0,0500 0,0003
30 VA 0,50 -0,1200 -0,0027 8 0,0200 0,0003
30 VA 3,00 -0,1200 -0,0055 6 -0,0400 -0,0010
30 VA 0,50 -0,1400 -0,0030 6 -0,1000 -0,0008
2,00 -0,13 -0,0018 9 -0,28 0,0002 10,0000 -0,0900 0,0000 10,0000 0,0100 0,0003 8,0000 0,0700 -0,0003 0,0900 -0,0013
0,50 -0,2200 -0,0035 -0,2600 0,0012 -0,0600 0,0007 -0,0500 0,0005 -0,0300 0,0003 -0,0500 -0,0013
![Page 83: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/83.jpg)
CT 150 kV 400-200/5A cl 0.5
FECHA: 14/12/2016 Se prueba devanado de medida HB, BT, 400/5, cl. 0,5, 30 VA, laboratorio No 45512
Hz 53 159 265 583 1537 2597se desmagnetizo y se repitio
N° 1 3 5 11 29 49
Carga I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad)
30 VA 5,00 0,1400 0,0004
30 VA 2 0,1300 -0,0022
0,50 0,0400 -0,0037
30 VA 5,00 0,1700 0,0004 9 0,2100 -0,0010
30 VA 2,00 0,1500 -0,0021 9 0,044 -3,5e-4
0,50 0,0700 -0,0036 0,0200 0,0007
30 VA 5,00 0,1900 0,0006 9,8 0,2200 -0,0002
30 VA 2,00 0,1700 -0,0022 10 0,2800 0,0002
0,50 0,0600 -0,0037 0,3300 0,0004
30 VA 2,00 0,1700 -0,0016 10 0,3200 0,0001
30 VA 0,50 0,0800 -0,0035 10 0,3000 0,0007
30 VA 2,00 0,1700 -0,0018 8 0,3300 -0,0008
30 VA 0,50 0,0800 -0,0033 8 0,2500 -0,0002
30 VA 2,00 0,1600 -0,0019 6 0,2800 -0,0021
30 VA 0,50 0,0800 -0,0031 6 0,1400 -0,0018
2,00 0,15 -0,0019 9 0,02 0,0010 10,0 0,1700 -0,0001 10,0 0,2800 0,0000 8,0 0,3200 -0,0008 6,0 0,3000 -0,0020
0,50 0,0600 -0,0031 -0,0200 0,0016 0,2200 0,0007 0,2500 0,0006 0,2200 0,0000 0,1600 -0,0013
![Page 84: Efectos de ondas distorsionadas en transformadores de medida](https://reader036.fdocuments.ec/reader036/viewer/2022071506/62cfbc464e4cb965df11e47c/html5/thumbnails/84.jpg)
H&B 600/5Acl.0,2
FECHA: 05/12/2016 Se prueba devanado de medida HB, BT, 600/5, cl. 0,2, 10 VA, laboratorio No 45512
Hz 53 159 265 583 1537 2597
N° 1 3 5 11 29 49
Carga I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad) I e(%) d(rad)
10 VA 5,00 -0,1000 -0,0029
10 VA 0,50 -0,1800 -0,0057
Carga
10 VA 5,00 -0,1100 -0,0030 9 0,0300 0,0068
10 VA 0,50 -0,1800 -0,0560 9 0,31 2,7e-3
Carga
10 VA 5,00 -0,1100 -0,0030 10 0,1400 0,0023
10 VA 0,50 -0,1600 -0,0046 10 0,1800 0,0016
Carga
10 VA 5,00 -0,1000 -0,0029 9 0,1600 0,0004
10 VA 0,50 -0,1100 -0,0049 9 0,0700 0,0011
Carga
10 VA 5,00 -0,1000 -0,0030 8 0,2000 -0,0012
10 VA 0,50 -0,1400 -0,0042 8 0,0200 -0,0008
Carga
10 VA 5,00 -0,1000 -0,0030 6 0,1900 0,0029
10 VA 0,50 -0,1200 -0,0042 6 -0,1400 -0,0029
Carga
10 VA 5,00 -0,1 -0,0030 9 -0,02 0,0075 10,0000 0,1500 0,0027 9,0000 0,1900 0,0004 8,0000 0,2100 -0,0012 6,0000 0,2100 -0,0029
10 VA 0,50 -0,1200 -0,0043 9 0,17 ####### 10 0,15 ####### 9 0,11 ####### 8 0,09 -1,30E-03 6 -0,02 -0,0033