ATS Presentation (Rev.0 J0131)

download ATS Presentation (Rev.0 J0131)

of 13

Transcript of ATS Presentation (Rev.0 J0131)

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    1/13

    Automatic Transformer Switch(31/01/2009)

    1

    energy S.A.L

    ATS (Automatic TransformerSwitch)

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    2/13

    Automatic Transformer Switch(31/01/2009)

    2

    energy S.A.L

    Prepared & Presented by

    Eng. Mohamad Koubeissi (Head of the Design Department)

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    3/13

    Automatic Transformer Switch(31/01/2009)

    3

    energy S.A.L

    - Type and Operation of ATS

    - ATS G/M

    - ATS G1/G2

    - Break

    - ATS G1/G2/M

    - Digital ATS

    - Problems and possible causes

    - Questions

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    4/13

    Automatic Transformer Switch(31/01/2009)

    4

    energy S.A.L

    Type and operation of ATS

    There are 3 types of ATS

    A- ATS G/M: This type is installed when the Mains electricity is available and the Gen-Set works as standby source.

    Operation: ATS monitors the Mains supply. When the Mains fails, the ATS starts, the Gen-Set the load is engaged after warm-up

    period. As soon as the Mains supply is available, the power is switched back after a restoration delay and the Generator shuts down

    after a certain cooling time without being in load.

    B- ATS G1/G2: This type of ATS is installed when the Mains electricity is completely absent and the 2 Gen-Sets work as Main

    source.

    Operation: G1 is running on load and when the time of the Generator on load comes to the end, the stand-by Generator willautomatically starts and after warm-up period takes the load, then the first Generator stops after a certain cooling time and the cycle

    continues according the adjustable cycle time.

    In case the requested Generator fails to start or shuts down due to any fault, the stand-by Generator will automatically start and

    supply load until fixing the problem of the first one.

    C- ATS G1/G2/ M: This type of ATS is installed when the Mains electricity is available but during short time and the 2 Gen-Sets work

    as standby source.

    Operation: The ATS monitors the Mains supply. When the Mains fails, the ATS starts G1 or G2 depending on the cycle timer. Load is

    engaged after warm-up period. As soon as the Mains supply is available, the power is switched back and the Generator shuts downafter a certain cooling time without being in load.

    When the time of the Generator on load comes to the end, the stand-by Generator will automatically starts and after warm-up period

    takes the load, then the first Generator stop after a certain cooling time and the cycle continues according the adjustable cycle time.

    In case the requested Generator fails to start or its contactor fails to engage or shuts down due to any fault, the stand-by Generator

    will automatically start and supply load until fixing the problem of the first one.

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    5/13

    Automatic Transformer Switch(31/01/2009)

    5

    energy S.A.L

    ATS G/M

    Mains contactor

    Gen-Set contactor

    OUV relay

    Timer 24 hours

    Relay 220VAC Timer 220VAC

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    6/13

    Automatic Transformer Switch(31/01/2009)

    6

    energy S.A.L

    ATS G1/G2

    G1 contactor

    G2 contactor

    Timer 24 hours

    Relay 12VDC

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    7/13

    Automatic Transformer Switch(31/01/2009)

    7

    energy S.A.L

    ATS G1/G2/MTimer 24 hours

    Timer 220VAC

    OUV relay

    Mains Contactor

    Common Contactor

    G2 Contactor

    G1 Contactor

    Relay 12VDC

    Relay 220VAC

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    8/13

    Automatic Transformer Switch(31/01/2009)

    8

    energy S.A.L

    ATS G1/G2/M

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    9/13

    Automatic Transformer Switch(31/01/2009)

    9

    energy S.A.L

    ATS G1/G2/M

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    10/13

    Automatic Transformer Switch(31/01/2009)

    10

    energy S.A.L

    ATS G1/G2/M

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    11/13

    Automatic Transformer Switch(31/01/2009)

    11

    energy S.A.L

    Digital ATS G/M, G1/G2, G1/G2/M

    Digital Unit

    Mains Contactor

    Common Contactor

    G2 Contactor

    G1 Contactor

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    12/13

    Automatic Transformer Switch(31/01/2009)

    12

    energy S.A.L

    Major Problems and possible causes

    Mains is available but Gen-Set is running - OUV relay

    Mains is absent but the Gen-Set doesnt start - AUTO mode

    - Relay RE

    Gen-Set is alive but there is no electricity on Load - Mains contactor auxiliary

    - Gen-Set solenoid contactor

    - Contactor line from Gen-Set Panel

    Mains is available but there is no electricity on load - OUV relay

    - Gen-Set contactor auxiliary,

    - Mains solenoid contactor

    ATS G/MProblem cause

    Gen-Sets dont alternate - Relays TS, RTS, RT

    G1or G2 is alive but there is no electricity on load -Contactor auxiliary and solenoid

    - Contactor line from Gen-Set panel

    Fault on G1 but G2 doesnt start - Signal coming from relay RA

    Miss-connection of electrical inter-lock - Electrical interlock connection

    ATS G1/G2Problem cause

    ATS G1/G2/M :Same as G/M + G1/G2

  • 7/30/2019 ATS Presentation (Rev.0 J0131)

    13/13

    Automatic Transformer Switch(31/01/2009)

    13

    energy S.A.L

    Questions ?