852-318 Rele Imagen Termica Digital
-
Upload
enriqueuno -
Category
Documents
-
view
329 -
download
5
Transcript of 852-318 Rele Imagen Termica Digital
-
7/26/2019 852-318 Rele Imagen Termica Digital
1/2
Series
SpecificationInputs3 wire PT100, class BCT's:Fans & Pumps CT's orcontact closureContact rating: 5A(Breaking: 110VDC/0.4A)
0-1 to 0-10A user selectable)
Dimensions:283 (W) X 216 (H) X 143 (D)
Fixing dimensions:242 (W) X 177 (H)
Temperature range: 0-70 Deg
Damp Heat to IEC 68-2-30
Environmental:
Universal, 44-265Vac, 44-260Power consumption:
-
7/26/2019 852-318 Rele Imagen Termica Digital
2/2
Order codes:
852-116 (Wall mounted) 1 winding, 3 Dig i/ps, single PT100 for oil temperature and 6 relays, 2 analogue o/ps
852-216 (Wall mounted) 2 windings, 3 Dig i/ps, single PT100 for oil temperature and 6 relays, 2 analogue o/ps
852-318 (Wall mounted) 3 windings, 3 Dig i/ps, single PT100 for oil temperature and 8 relays, 4 analogue o/ps
Specification:Accuracy, resolution: 12 bit, < 0.5% +/-1 Deg C
Analogue outputs: 0-10, 0-20 & 4-20mA (User selectable) with 12 bit resolution. Maximum loop resistance 800.
CT input: user selectable 1 -10 Amps, +/- 1% @ 20C, (CT = 0.03VA, 1:1000) Overload 75A for 3 secs
Hot Spot Gradient to IEC 354
Relay outputs: 1 off supervisory, plus 6 or 8 (model dependant ) all with N/O or N/C volt free contacts (user selectableby links).
Relay rating: Contact life (for 1.2x10 5 operations): 5A Non inductive (Breaking: 110Vdc/0.4A, for inductive de-rate
using L/R=7msecs, i.e. approx 0.2A@125VDC).
Environmental:Operating temperature range: 0 to70C.
Wall mounted enclosure to IP65, Panel mounted enclosure to IP55. Weight: 1.5 & 1.2Kg
Power supply: Universal input, 44-265 Volts ac, 44-260 Volts dc, power consumption less than 6VA.
EMC: Meets the intent of Directive 89/336 and LVD 73/23/ECC, EN61004-16, EN60255-22-1, IEC255-5, EN55022,
EN50081-2, EN55011, EN6100-4-2,
EN6100-4-5 (surge at 4kV for mains connection and 2kV for signals),
EN6100-4-3 (radiated immunity at 10V/metre),
EN6100-4-4 (fast transients 4kV),EN6100-4-6 (conducted immunity at 10V/metre),
EN6100-4-11, EN6100-4-12 (damped oscillatory wave 2.5kV),
Damp Heat to IEC 68-2-30
Environmental:EN60068-2-2, IEC 255-21-1, IEC 255-21-2 & IEC 68-2-56
Seismic to IEC 255-21-3 (Class 2)
Dimensions: 241 X 185 X 105 DeepFixing dimensions: 3 holes, 198 (W) X 145 (H)
852PlusWall MountedFront View
852PlusWall Mountedside View
1116 214
185
10 105
126
5910
15
96
Dimensions: 283 X 216 X 143 DeepFixing dimensions: 3 holes, 242 (W) X 177 (H)
852Wall Mounted
Front View
852Wall Mounted
side View
1116.5 257
216
10 133
157
7010
852-3xx Dimensions
852-2xx Dimensions
Manufacturer:
Ashridge Engineering LtdWest View Road
Okehampton
Devon. UKEX20 1NF
Web: www.ash -eng.co.uk
Agent:
ARGENTINA - Arfin srl
Email: [email protected]
BRAZIL - Tectron Ltda. Email: