1.-PARAMETROS DE DISEÑO PICUROYACU 2011 CORREG.xlsx

download 1.-PARAMETROS DE DISEÑO PICUROYACU 2011 CORREG.xlsx

of 55

Transcript of 1.-PARAMETROS DE DISEÑO PICUROYACU 2011 CORREG.xlsx

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    1/55

    PROYECTO ::

    1.- DATOS DE LA LOCALIDAD DEL CASERIO DEL PICURUYACU BAJO SEGN LOS CENSOS POBLACIONALES

    :

    LOCALIDAD : : PICUROYACU PROVINCIA: LEONCIO PRADO

    DISTRITO : : RUPA RUPA REGION: HUANUCO

    1.1.- SECTORIZACION POR ZONAS AO 2010ZONA A : DOMESTICO PUBLICO

    MANZANA 1 2 3 4 5 6 7 8 9 10 TotalLOTES 1 1 1 1 1 1 1 1 1 1 10

    HAB/VIV 4 4 4 4 4 4 4 4 4 4HAB 4 4 4 4 4 4 4 4 4 4 40

    MANZANA 11 12 13 14 15 16 17 18 19 20LOTES 1 1 1 1 1 1 1 - 1 1 9

    HAB/VIV 4 4 4 4 4 4 4 4 4 4HAB 4 4 4 4 4 4 4 - 4 4 36

    MANZANA 21 22 23 24 25 26 27 28 29 -

    LOTES 1 1 1 - 1 1 1 1 1 - 8HAB/VIV 4 4 4 4 4 4 4 4 4 4

    HAB 4 4 4 - 4 4 4 4 4 - 32

    LOTES DOM 27IEI PICURUY 1LOCAL COM. 1POBLACION 108

    ZONA B : COMERCIAL E INDUSTRIAL

    MANZANA 30 31 32 33 34 35 36 37 38 39 TotalLOTES 1 1 1 1 1 1 1 1 1 1 10

    HAB/VIV 4 4 4 4 4 4 4 4 4 4

    HAB 4 4 4 4 4 4 4 4 4 4 40MANZANA 40 41 42 43 44 45 46 47 48 49LOTES 1 1 1 1 1 1 1 1 1 1 10

    HAB/VIV 4 4 4 4 4 4 4 4 4 4HAB 4 4 4 4 4 4 4 4 4 4 40

    MANZANA 50 51 52 53 54 55 56 57 58 59LOTES 1 1 1 1 1 1 1 1 1 1 10

    HAB/VIV 4 4 4 4 4 4 4 4 4 4HAB 4 4 4 4 4 4 4 4 4 4 40

    MANZANA 60 61 62LOTES 1 1 1 3

    HAB/VIV 4 4 4HAB 4 4 4 12

    LOTES DOM 33COLEGIO -PLAZA : -ESTADIO MU -HOSPITAL -POBLACION 132

    ZONA C : EXPANSIONES URBANASSE CALCULARA DE ACUERDO AL PERIODO DE DISEO Y PLANEAMIENTO DE CRECIMIENTO POBLACIONAL

    MANZANA 63 64 65 66 67 68 69 70 - - TotalLOTES 1 - 1 1 1 1 1 1 - - 7

    HAB/VIV 4 - 4 4 4 4 4 4 - -HAB 4 - 4 4 4 4 4 4 - - 28

    "INSTALACION DEL SISTEMA DE AGUA POTABLE DEL CASERIO DE PICURUYACUBAJO,DISTRITO DE RUPA RUPA, PROVINCIA DE LEONCIO PRADO - HUANUCO".

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    2/55

    LOTES DOM 7POST MED. : 1POBLACION 28

    ZONA D : EXPANSIONES URBANASSE CALCULARA DE ACUERDO AL PERIODO DE DISEO Y PLANEAMIENTO DE CRECIMIENTO POBLACIONAL

    MANZANA 71 72 73 74 75 76 77 78 79 80 TotalLOTES 1 1 1 1 1 1 1 1 1 1 10

    HAB/VIV 4 4 4 4 4 4 4 4 4 4HAB 4 4 4 4 4 4 4 4 4 4 40

    MANZANA 81 - - - - - - - - - TotalLOTES 1 - - - - - - - - - 1

    HAB/VIV 4 - - - - - - - - -HAB 4 - - - - - - - - - 4

    LOTES DOM 11POBLACION 44

    ZONA E : INTANGIBLE DE RIESGO

    SON ZONAS INTAGIBLES , CONSERVACION NATURAL, ZONAS DE RIESGO POBLACIONAL..ETC.

    1.2.- DATOS CENSALES POBLACIONALES

    ZONA ZONA ZONA ZONA POBLACIONAO (X) A (Y) B (Y) C (Y) D (Y) TOTAL

    1,961 60 40 2 8 1101,972 75 60 5 13 1531,981 80 80 9 17 1861,993 85 100 11 20 2162,005 88 105 12 22 2272,009 95 115 15 25 2502,010 108 132 28 44 312 ACTUAL

    1.3.- DATOS CATASTRALES 2011

    LOTES DOM 78MERCADO 1CENT.CIVICO 1COLEGIO 1PLAZA : -ESTADIO MU -POST MED. : 1POBLACION 312

    -

    50

    100

    150

    200

    250

    300

    350

    1,961 1,972 1,981 1,993 2,005 2,009 2,010

    POBLACION GENERAL SEGUN CENSOS

    CURVA POBLACIONAL

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    3/55

    2.- DATOS LOCALIDAD DEL CASERIO DE PICURUYACU BAJO SEGN LOS CENSOS POBLACIONALES CADA 10 AOS

    CON LAS ECUACIONES:INTERPOLANDO EXTRAPOLANDO

    ZONA ZONA ZONA ZONA POBLACIONAO A (Y) B (Y) C (Y) D (Y) TOTAL1965 65 47 2 2 1171975 77 67 3 3 1491985 82 87 10 5 1831995 86 101 11 20 2182005 88 105 12 22 2272015 173 217 93 139 6222025 258 329 174 256 1,0172035 343 441 255 373 1,412

    ZONA A ZONA B ZONA C ZONA D

    AOS HAB. T. CREC. AOS HAB. T. CREC. AOS HAB. . CREC AOS HAB. T. CREC.1965 65 - 1,965 47 - 1,965 2 - 1,965 2 -1975 77 1 1,975 67 2 1,975 3 0 1,975 3 01985 82 1 1,985 87 2 1,985 10 1 1,985 5 01995 86 0 1,995 101 1 1,995 11 0 1,995 20 22005 88 0 2,005 105 0 2,005 12 0 2,005 22 02015 173 9 2,015 217 11 2,015 93 8 2,015 139 122025 258 9 2,025 329 11 2,025 174 8 2,025 256 122035 343 9 2,035 441 11 2,035 255 8 2,035 373 12

    2015, 173

    2015, 9-

    50

    100

    150

    200

    250

    300

    350

    400

    1960 1980 2000 2020 2040

    HABITANTES

    TIEMPO (AOS)

    CURVA POBLACION

    Series1 TASA DE CRECIMIENTO

    -

    50

    100

    150

    200

    250

    300

    350400

    450

    500

    1,960 1,980 2,000 2,020 2,040

    Series1 TASA DE CRECIMIENTO

    TIEMPO ( AOS)

    HABITANTES

    CURVA POBLACION

    -

    50

    100

    150

    200

    250

    300

    1,960 1,980 2,000 2,020 2,040

    HABITANTES

    TIEMPO (AOS)

    CURVA POBLACION

    Series1 TASA DE CRECIMIENTO

    -

    50

    100

    150

    200

    250

    300

    350400

    1,960 1,980 2,000 2,020 2,040

    HABITANTES

    TIEMPO (AOS)

    CURVA POBLACION

    Series1 TASA DE CRECIMIENTO

    11

    12

    12 )(*)( YXXXX

    YYY

    22

    12

    12 )(*)( YXXXX

    YYY

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    4/55

    3.- DOTACIONES

    3.1 DOTACIN PARA EL AO 2010 EN BASE AL CONSUMO POR TIPO DE EDIFICACIN:

    CLASIFICACION DEL CONSUMO (SEGN R.N.E OS.100)

    CONTRIBUCION PERCAPITA DE AGUA LTS/HAB/DIA)

    FRIO TE180120

    30

    DOTACION220.00 lt/h

    5.00 lt/m20.00 lt/m

    800.00 lt/c300.00 lt/h

    20.00 lt/a25.00 lt/a15.00 lt/a

    300.00 lt/h15.00 lt/m

    300.00 lt/c

    SEGN EL PLANO DE ZONIFICACIN DEL CASERIO DE PICURUYACU BAJO SE TIENE ENTRE LOTES > 90 M2 Y

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    5/55

    SE TIENE LA DISTRIBUCION DE CAUDALES PARA LAS AREAS VERDES

    DESCRIPCION AREA VERDE AREA (M2) DOTACION

    PLAZA DE ARMAS 800 5.00 4000.00 0.05PARQUE 600 5.00 3000.00 0.03

    0.08

    SE TIENE PARA LAS OFICINAS

    DESCRIPCION DE OFICINAS AREA (M2) DOTACION

    LOCAL COMUNAL 40 20.00 800.00 0.010.01

    SE CUENTA CON UN CENTRO DE SALUD

    DESCRIPCION AREA VERDE N DE CAMAS DOTACION

    CENTRO DE SALUD 5 800.00 4000.00 0.050.05

    LA DOTACION PARA EL SECTOR EDUCACION

    DESCRIPCION N DE ALUMNO DOTACION

    I.E.I PICURUYACU 25 25.00 625.00 0.010.01

    SE CUENTA CON UN MERCADO

    DESCRIPCION MERCADO AREA DOTACION

    MERCADO DE ABASTOS 80 15.00 1200.00 0.010.01

    SE CUENTA CON UN CAMAL

    DESCRIPCION CAMAL MUNIC # DE ANIMALES DOTACION

    CAMAL MUNICIPAL 20 300.00 6000.00 0.070.07

    POBLACION2011

    Consumolts/dia

    Qp=Pob. x Dot./86400

    Qp=Caudal mediolts/seg

    POBLACION

    2010

    Consumo

    lts/dia

    Qp=Pob. x Dot.

    /86400

    Qp=Caudal medio

    lts/seg

    POBLACION2010

    Consumolts/dia

    Qp=Pob. x Dot./86400

    Qp=Caudal mediolts/seg

    POBLACION2011

    Consumolts/dia

    Qp=Pob. x Dot./86400

    POBLACION2010

    Consumolts/dia

    POBLACION2010 Consumolts/dia Qp=Pob. x Dot./86400 Qp=Caudal mediolts/seg

    Qp=Pob. x Dot./86400

    Qp=Caudal mediolts/seg

    Qp=Caudal mediolts/seg

    Pgina_B 5

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    6/55

    LA DOTACION PARA ESTADIOS Y SIMILARES

    DESCRIPCION N DE ASIENTO DOTACION

    LOSA DEPORTIVA 100 15.00 1500.00 0.020.02

    RESUMEN TOTALESN Edificaciones = 82.00 edif.Factor d edificaciones p/uso = 20.00Dotacin para el A O 2010 en base al consumo por tipo de edificac = 880.05 Lit./edif./daEl caudal medio total = 1.04 lts/seg

    3.2 DOTACIN PARA EL AO 2010 EN BASE AL CONSUMO POR HABITANTE:

    DOTACION DE AGUA SEGN EL TIPO ( AO BASE 2010 )

    COSUMO ITEM l/hab.dia l/hab.diaPERDIDAS (5-

    45)%DOMESTICO 190.00 15.07

    ASEO PERSONAL 60.00DESCARGA DE SANITARIOS 45.00

    LAVADO DE ROPA 32.00COCINA 25.00RIEGO DE JARDINES 16.00LAVADO DE PISOS 12.00

    COMERCIAL E INDUSTRIAL 40.00 15.07LECHERIAS 8.00FABRICA DE BEBIDAS 2.50FABRICAS DE HIELO 2.50CURTIEMBRES 2.00EDIFICIOS INDUSTRIALES 15.00ALMACENES 10.00

    PUBLICO 36.00 15.07LAVADO DE CALLES 12.00MATADEROS 2.30

    HOSPITALES 1.70RIEGO DE PARQUES 12.00LAVADO DE ALCANTARILLADO 8.00

    CONSUMO POR INCENDIO

    TOTAL CONSUMO 266.00 45.22

    Qp=Caudal mediolts/seg

    POBLACION2010

    Consumolts/dia

    Qp=Pob. x Dot./86400

    Pgina_B 6

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    7/55

    DOTACIONES SEGN EL TIPO DE COMUNIDAD AO BASE 2010: DOTACION POBL. X SECTO EDIF. X SECTOR ED

    TIPO I DOMESTICO Y PUBLICO 256 l/hab.dia 108 29TIPO II COMERCIAL E INDUSTRIAL 311 l/hab.dia 132 33TIPO III EXPANSIONES URBANAS 227 l/hab.dia 28 8TIPO IV EXPANSIONES URBANAS 205 l/hab.dia 44 11

    TOTAL 312 81

    ZONA A

    ZONA I :DATOS TIPO1( unid.)= 29 TIPO2( unid.) = TIPO3( unid.) = TI

    Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da L

    Mximo 2,100 215Mnimo 250 145Promedio 352 256

    Consumo promedio por edificacin/ da = =

    Poblacin en el Ao 2010: 35% = 108 ha

    Densidad poblacional promedio por edificacin = 3.72 ha

    Dotacin para el AO 2010 en base al consumo por tipo de edificacin = 94.63 Lt

    Dotacin para el AO 2010 en base al consumo por habitante = 256.15 Lt

    TOMANDO EL VALOR MAYOR DE DOTACIN TENDREMOSConsumo promedio instantaneo para la zona A = 0.32 Lt

    ZONA B

    ZONA I :DATOS TIPO1( unid.)= TIPO2( unid.) 33 TIPO3( unid.) = TI

    Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da L

    Mximo 1,900 250Mnimo 200 160Promedio 264 311

    Iniciamos el proceso de estimacin calculando la dotacin promedio CATASTRAL, en funcin al consumo promedio cuantificado por tipo de EHABITANTE, as como el consumo promedio en Lt./seg.

    Iniciamos el proceso de estimacin calculando la dotacin promedio CATASTRAL, en funcin al consumo promedio cuantificado por tipo de EHABITANTE, as como el consumo promedio en Lt./seg.

    Pgina_B 7

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    8/55

    Consumo promedio por edificacin/ da = =

    Poblacin en el Ao 2010: 42% = 132 ha

    Densidad poblacional promedio por edificacin = 4.00 ha

    Dotacin para el AO 2010 en base al consumo por tipo de edificacin = 66.00 Lt

    Dotacin para el AO 2010 en base al consumo por habitante = 311.22 Lt

    TOMANDO EL VALOR MAYOR DE DOTACI N TENDREMOSConsumo promedio instantaneo para la zona B = 0.48 Lt

    ZONA C

    ZONA I :DATOS TIPO1( unid.)= TIPO2( unid.) = TIPO3( unid.) = 8 TI

    Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da LMximo 1,700 245Mnimo 100 195Promedio 132 227

    Consumo promedio por edificacin/ da = =

    Poblacin en el Ao 2010: 9% = 28 ha

    Densidad poblacional promedio por edificacin = 3.50 ha

    Dotacin para el AO 2010 en base al consumo por tipo de edificacin = 37.72 Lt

    Dotacin para el AO 2010 en base al consumo por habitante = 227.10 Lt

    TOMANDO EL VALOR MAYOR DE DOTACIN TENDREMOSConsumo promedio instantaneo para la zona C = 0.07 Lt

    Iniciamos el proceso de estimacin calculando la dotacin promedio CATASTRAL, en funcin al consumo promedio cuantificado por tipo de EHABITANTE, as como el consumo promedio en Lt./seg.

    Pgina_B 8

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    9/55

    ZONA D

    ZONA I :DATOS TIPO1( unid.)= TIPO2( unid.) = TIPO3( unid.) = TI

    Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da Lit./edif./da Lit./hab./da L

    Mximo

    MnimoPromedio

    Consumo promedio por edificacin/ da = =

    Poblacin en el Ao 2010: 14% = 44 ha

    Densidad poblacional promedio por edificacin = 4.00 ha

    Dotacin para el AO 2010 en base al consumo por tipo de edificacin = 33.00 Lt

    Dotacin para el AO 2010 en base al consumo por habitante = 205.07 Lt

    TOMANDO EL VALOR MAYOR DE DOTACIN TENDREMOSConsumo promedio instantaneo para la zona D = 0.10 Lt

    0.35 0.42 0.09 0.14CUADRO 01.-

    DEMANDA CATASTRAL: Zona "A" Zona "B" Zona "C" Zona "D"

    Poblacin Total ao 2010( habitantes ) 108 132 28 44Dotacin para el ao 2010(Lt./hab./da) 256.15 311.22 227.10 205.07Consumo promedio ao 2010 ( Lt./seg. ) 0.32 0.48 0.07 0.10

    TOMANDO EL VALOR MAYOR DE DOTACIN TENDREMOSConsumo promedio instantaneo para ao 2010 (Lt./seg.) =

    DEMANDA GENERAL

    DEMANDA CATASTRAL: Zona "A" Zona "B" Zona "C" Zona "D"

    Poblacin Total ao 2010( habitantes ) 108 132 28 44Dotacin para el ao 2010(Lt./hab./da) 288.00 288.00 288.00 288.00Consumo promedio ao 2010 ( Lt./seg. ) 0.36 0.44 0.09 0.15

    Iniciamos el proceso de estimacin calculando la dotacin promedio CATASTRAL, en funcin al consumo promedio cuantificado por tipo de EHABITANTE, as como el consumo promedio en Lt./seg.

    Pgina_B 9

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    10/55

    4.- CALCULO DEL CONSUMO DE AGUA

    4.1.- CALCULO DE LOS CONSUMO PROMEDIO ANUAL5.1.1 GASTO PROMEDIO

    El gasto promedio diario se define como el promedio de los consumos diarios durante un ao.Por lo tanto, el gasto promedio diarioexpresa la relacion entre el volumen total consumido por la poblacion en un dia se expresa generalmente en lts/seg y esta represntado por:

    Tambien por :

    GASTO CUADRO 02.- LOCALIDAD CACHICOTO ( Consumo promedio ao 2010)PROM. GASTO VOLUM. PRODUCC. VOLUM. DE

    HORAS @ 2 horas PROM @ 2HR. VOLUMEN ACUMUL. ACUM.24 Hr. CONSUM.RES.% del Qprom. 100 % Dprom. 100% Dprom.

    (Lt./seg.) (Lts./s.) (Lts.) (Lts.) (Lts.) (Lts.)0 0

    0 10.00% 0.10 1,116 1,116 7,566 6,450.13

    2 20.00% 0.21 2,448 3,564 15,132 11,568.26

    4 45.00% 0.47 4,860 8,424 22,698 14,274.39

    6 85.00% 0.88 7,488 15,912 30,265 14,352.52

    8 115.00% 1.20 8,064 23,976 37,831 13,854.65

    10 100.00% 1.04 11,232 35,208 45,397 10,188.78

    12 200.00% 2.08 12,924 48,132 52,963 4,830.91

    14 145.00% 1.51 9,540 57,672 60,529 2,857.04

    16 110.00% 1.14 8,784 66,456 68,095 1,639.17

    18 125.00% 1.30 10,116 76,572 75,661 -910.70

    20 145.00% 1.51 10,118 86,690 83,227 -3,462.08

    22 100.00% 1.04 4,104 90,794 90,794 0.05

    24 10.00% 0.10 90,794 90,794 0.05

    POR DA 12.48 90,794 90.79 Reserv(100%)= 17,814.60 0(Lts./s.) 0.00(Lts./s.) (Lts.) (M3) (M3) 14,352.52 MAX + 0.00

    -3,462.08 MIN -

    Qp = 0.97 - 1.04 = -0.07

    4.2.- CALCULO DE LAS VARIACIONES DE CONSUMO

    5.1.1 VARIACION DE CONSUMODe acuerdo a condiciones de cada ciudad el consumo de agua sufre variaciones diarias determinadas por las estaciones, costumbres,etc. Lo c

    (Prdidas en la red yConex.Gland)

    La cantidad de agua que se consume en una red publica varia continuamente bajo la influnencia de las actividades y habitos de la poblacion,condiciones de

    durante un mes hay dias de mayor consumo, lo mismo que durante el dia,el consumo varia constantemente.Los consumos de agua de la ciudad tiene pues vconsumo o gastos promedio(Qo).

    Efectuamos las estimaciones de las demanda por variaciones de consumo diarias en funcin a los datos suministrados del diario promedio

    horario y del diario maximo horario en Lt./seg.Para determinar el caudal medio en Lt./seg. durante el ao 2010, se proceder a desarrollar el cuadro que contiene las variaciones horarias delconsumo promedio durante el ao, que representa en forma analtica a la curva masa ( Produccin y Demanda vrs. Tiempo).

    /86400

    P

    Poblacion DotacionQ l seg

    24 3600P

    Poblacion DotacionQ

    horas s

    Pgina_C 10

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    11/55

    A) GASTO MAXIMO DIARIO

    Se define como maximo diario al dia de maximo consumo de unaserie de registros observados durante 365 dias de un ao.

    COEFICIENTE DE VARIACION DIARIA.K1

    Es la relacion existente entre el gasto efectuado en el dia de maximo consumo y el gasto promedio.

    El gasto maximo diario representa pues el promedio diario por el coeficiente de variacion diaria, o sea:

    DONDE :Qmd = Gasto maximo diario expresado en lts/s

    Qp = Gasto promedio expresado en Hs/sK1= Coeficiente de variacion diaria que varia 1.3-2.0 (Segn tipo de habilitacion)

    B) GASTO MAXIMO HORARIO

    El valor maximo que se tiene durante un dia sera hora de maximo consumoEl gasto maximo horario sera relacionado respecto al gasto promedio,segn la siguiente expresion:

    DONDE :Qmh= Gasto maximo Horario expresado en lts/s

    Qp = Gasto promedio expresado en lts/sK2= Coeficiente de variacion Horaria que varia entre 1.8-2.5 (Segn tipo de habilitacion)

    respecto al gasto promedio.

    consumos,igualmente existen horas en que se presentan maximos y minimos consumos.

    De acuerdfo a las variaciones de todo un ao se puede determinar el dia mas critico que nesesariamente tiene que ser satisfecho

    1

    . . . .

    .

    Gasto del Da mximo consumok

    Gasto promedio

    1md pQ Q k

    2mh pQ Q k

    Pgina_C 11

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    12/55

    GASTO CUADRO 03.- LOCALIDAD CACHICOTO (Consumo del da mximo ao 2010 )PROM. GASTO VOLUM. PRODUCC. VOLUM. DE

    HORAS @ 2 horas PROM @ 2HR. VOLUMEN ACUMUL. ACUM.24 Hr. CONSUM.RES.% del Qprom. 100 % Dprom. 100% Dprom.

    (Lt./seg.) (Lts./s.) (Lts.) (Lts.) (Lts.) (Lts.)0 0

    0 20.00% 0.21 2,268 2,268 14,988 12,720.00

    2 40.00% 0.42 4,896 7,164 29,976 22,812.00

    4 90.00% 0.94 9,756 16,920 44,964 28,044.00

    6 170.00% 1.77 14,976 31,896 59,952 28,056.00

    8 230.00% 2.39 16,092 47,988 74,940 26,952.00

    10 200.00% 2.08 22,464 70,452 89,928 19,476.00

    12 400.00% 4.16 25,848 96,300 104,916 8,616.00

    14 290.00% 3.02 19,116 115,416 119,904 4,488.0016 220.00% 2.29 17,604 133,020 134,892 1,872.00

    18 250.00% 2.60 20,232 153,252 149,880 -3,372.00

    20 290.00% 3.02 18,360 171,612 164,868 -6,744.00

    22 200.00% 2.08 8,244 179,856 179,856 0.00

    24 20.00% 0.21 179,856 179,856 0.00

    POR DA 24.98 179,856 179.86 Reserv(100%)= 34,800.00(Lts./s.) (Lts.) (M3) 28,056.00 MAX +

    -6,744.00 MIN -

    Qprom = 1.94 K2 = 2.15 K1 = 1.30

    PERSISTENCIA MAYOR AL 50%

    RESUMEN AO 2010

    a) GASTO PROMEDIO

    = 1.04 l/sb) GASTO MAXIMO DIARIO

    = 1.35 l/sc) GASTO MAXIMO HORARIO

    = 2.23 l/s

    Para determinar los parmetros mximos de las variaciones horarias de consumo, se desarrollar el cuadro que contiene los datos en el da de mximoconsumo de la localidad CACHICOTO obteniendo la Curva masa ( Produccin y Demanda vrs. Tiempo ) que segn datos tiene una persistencia anualde 5 a 8% entre 1997 y 2011, asumiendo sta caracteristica para el 2010 y clculo de los parametros de diseo del sistema.

    /86400

    P

    Poblacion DotacionQ l seg

    1md pQ Q k

    2mh pQ Q k

    Pgina_C 12

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    13/55

    5.- PRODUCCION Y DEFICIT DEL SERVICIO 2010

    CUADRO 04.-

    PRODUCCIN 9.24

    Caudal que se deriva a la zona A = 0.36

    Caudal que se deriva a la zona B = 0.44

    Caudal por derivar a la zona C = 0.09

    Caudal por derivar a la zona D = 0.15

    POBLACIONCATASTRAL

    DEMANDA CATASTRAL CALCULADA = 1.04

    SUPERAVIT DE SERVICIO EN EL AO 2010 788.16%

    Habitantes coen SUPE

    PRODUCCIN Y DEFICIT DEL SERVICIO EN EL AO 2010 Producc. (Lt./seg.)

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    14/55

    6.- VERIFICACION DEL CAUDAL DE DEMANDA Ecuacion de Equilibrio) AO 2010

    6.1.- ANALISIS DEL CAUDAL DE OFERTA

    El caudal de oferta ser el de minimo en epocas de estiaje

    El caudal de la fuente fue obtenida mediante el aforo correspondiente, en epoca de estiaje

    Ancho de Rio (B) (m) = 0.25Tirante medio de Quebrada (Y) (m) = 0.1Longuitid de Analisis del Fuente (L) (m) = 2.5Tiempo promedio de Medicion (t) (s) = 3.91

    V = 0.64 m/sA = 0.025 m2

    Q O = 0.016 m3/s

    6.2.- ANALISIS DEL CAUDAL DE DEMANDA

    Datos:

    Caudal de diseo (Qm) (l/s) = 1.35Porcentaje de perdida en Filtro (Pf) (%) = 5.00Porcentaje de perdida en Sedimentador (Ps) (%) = -

    Porcentaje de perdida en Desarenador (Pd) (%) = -

    Perdida total = 5.00 %

    Qa = 1.42 l/s (Caudal a Captar)

    6.3.- EQUACION DE EQUILIBRIO

    Datos:

    Caudal a Captar (Qa) (l/s) = 1.42Caudal de Preservacion Ambiental (Qpa=Q (l/s) = 5.33Caudal de Requirimiento aguas abajo (Qra) (l/s) = -

    Qdemanda = 6.75 l/s

    15.98 6.75 OKS!!!

    Para determinar si la fuente proporcina el caudal adecuado sin afectar al medio ambiente y a otros usuarios del mismo. Por tal motivose tendra que determinar cual es caudal maximo que se podra obtener de la fuente de captacion y comparar con el caudal de demandade la loaclidad en analisis.

    Por lo tanto debera de cumplir la ecuacion de equilibrio

    = 15.98 l/s

    LV

    t

    OFERTA DEMANDAQ Q

    Q V A A B Y

    .OFERTA MIN RIOQ Q

    OFERTA DEMANDAQ Q

    Pgina_D 14

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    15/55

    7.- DATOS LOCALIDAD DEL CASERIO DE PICURUYACU BAJO SEGN LOS CENSOS POBLACIONALES CADA 10 AOS

    EXTRAPOLANDO E INTERPOLANDO

    ZONA A ZONA B ZONA C ZONA DAOS HAB. T. CREC. AOS HAB. T. CREC. AOS HAB. T. CREC. AOS HAB. T. CREC.1965 65 - 1965 47 - 1965 2 - 1965 2 -1975 77 1 1975 67 2 1975 3 0 1975 3 0

    1985 82 1 1985 87 2 1985 10 1 1985 5 01995 86 0 1995 101 1 1995 11 0 1995 20 22005 88 0 2005 105 0 2005 12 0 2005 22 02015 173 9 2015 217 11 2015 93 8 2015 139 12

    Pgina_E 15

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    16/55

    8.- GRAFICANDO LA POBLACION SEGN LOS DATOS CENSALES CADA 10AOS

    ZONA A CUADRO 05.-y = 52.906e0.152x y = 6.4096x2 - 28.423x + 97.315

    R2 = 0.7132 R1= 0.8234AOS HAB. T. CREC. POL2 EXP

    -8 1875 0 16-7 1885 0 18-6 1895 0 21-5 1905 0 25-4 1915 0 29-3 1925 0 34-2 1935 1 39-1 1945 1 450 1955 1 531 1965 65 12 1975 77 13 1985 82 14 1995 86 05 2005 88 06 2015 173 97 2025 4 2128 2035 7 2809 2045 8 361

    10 2055 9 45411 2065 11 560

    HABITANTES SIN SERVICIO : 1875 16HABITANTES CON SERVICIO: 2010 131POB.EST.OPER.PROYECTO : 2013 156POB.ASUMIDO PER.DIS. : 2040 320

    PERIODO DISEO: 2033 266.6

    y = 6.4096x2- 28.423x + R = 0.8234

    020406080

    100120140160180200

    1965 1975 1985 1995 2005

    HAB.

    AOS

    SECTOR I

    y = 52.906e0.152xR = 0.7132

    020406080

    100120140160180200

    1965 1975 1985 1995 2005

    HAB.

    AOS

    SECTOR I

    Pgina_E 16

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    17/55

    ZONA B CUADRO 06.-y = 7.1374x2 - 22.025x + 72.742 y = 37.118e0.261x

    R1 = 0.8795 R2 = 0.9079AOS HAB. T. CREC. POL2 EXP

    -10 1855 3

    -9 1865 0 4-8 1875 0 5-7 1885 0 6-6 1895 0 8-5 1905 0 10-4 1915 0 13-3 1925 0 17-2 1935 1 22-1 1945 1 290 1955 1 371 1965 47 12 1975 67 23 1985 87 24 1995 101 1

    5 2005 105 06 2015 217 117 2025 5 2688 2035 9 3539 2045 10 453

    10 2055 11 56611 2065 13 694

    HABITANTES SIN SERVICIO : 1855 3HABITANTES CON SERVICIO: 2010 161POB.EST.OPER.PROYECTO : 2013 195POB.ASUMIDO PER.DIS. : 2040 403

    PERIODO DISEO: 2033 336.3

    y = 7.1374x2- 22.025x +R = 0.8795

    0

    50

    100

    150

    200

    250

    1965 1975 1985 1995 2005

    HAB.

    AOS

    SECTOR II

    y = 37.118e0.261x

    R = 0.9079

    0

    50

    100

    150

    200

    250

    1965 1975 1985 1995 2005

    HAB.

    AOS

    SECTOR II

    Pgina_E 17

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    18/55

    ZONA C CUADRO 07.-y = 6.7262x2 - 33.269x + 36.233 y = 0.9034e0.6714x

    R1 = 0.8148 R2 = 0.8726AOS HAB. T. CREC. POL2 EXP

    -9 1865 0-8 1875 0 0-7 1885 0 0

    -6 1895 0 0-5 1905 0 0-4 1915 0 0-3 1925 0 0-2 1935 0 0-1 1945 0 00 1955 0 11 1965 2 02 1975 3 03 1985 10 14 1995 11 05 2005 12 06 2015 93 87 2025 4 1338 2035 7 2019 2045 8 282

    10 2055 9 37611 2065 11 484

    HABITANTES SIN SERVICIO : 1865 0HABITANTES CON SERVICIO: 2010 53POB.EST.OPER.PROYECTO : 2013 77POB.ASUMIDO PER.DIS. : 2040 241

    PERIODO DISEO: 2033 187

    y = 6.7262x2- 33.269xR = 0.8148

    -20

    0

    20

    40

    60

    80

    100

    1965 1975 1985 1995 2005

    HAB

    .

    AOS

    SECTOR III

    y = 0.9034e0.6714xR = 0.8726

    0

    20

    40

    60

    80

    100

    1965 1975 1985 1995 2005

    HAB.

    AOS

    SECTOR III

    Pgina_E 18

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    19/55

    ZONA D CUADRO 08.-y = 10.333x2 - 50.695x + 52.6 y = 0.6362e0.8168x

    R2 = 0.8605 R2 = 0.9334AOS HAB. T. CREC. POL2 EXP

    -7 1885 0-6 1895 0-5 1905 0 0-4 1915 0 0-3 1925 0 0-2 1935 0 0-1 1945 0 00 1955 0 11 1965 2 02 1975 3 03 1985 5 04 1995 20 25 2005 22 06 2015 139 127 2025 7 2048 2035 10 3089 2045 12 433

    10 2055 15 57911 2065 17 745

    HABITANTES SIN SERVICIO : 1885 0HABITANTES CON SERVICIO: 2010 81POB.EST.OPER.PROYECTO : 2013 116POB.ASUMIDO PER.DIS. : 2040 371

    PERIODO DISEO: 2033 287.5

    y = 10.333x2- 50R = 0.8

    -20

    0

    20

    40

    60

    80100

    120

    140

    160

    1965 1975 1985 1995 2005

    HAB

    .

    AOS

    SECTOR IV

    y = 0.6362

    R = 0.9

    020406080

    100120140160

    1965 1975 1985 1995 2005

    HAB.

    AOS

    SECTOR IV

    Pgina_E 19

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    20/55

    Zona A:HABITANTES SIN SERVICIO : 1875 16HABITANTES CON SERVICIO: 2010 131POB.EST.OPER.PROYECTO : 2013 156POB.ASUMIDO PER.DIS. : 2040 320PERIODO DISEO: 2033 266.6

    Zona B:

    HABITANTES SIN SERVICIO : 1855 3HABITANTES CON SERVICIO: 2010 161POB.EST.OPER.PROYECTO : 2013 195POB.ASUMIDO PER.DIS. : 2040 403PERIODO DISEO: 2033 336.3

    Zona C:HABITANTES SIN SERVICIO : 1865 0HABITANTES CON SERVICIO: 2010 53POB.EST.OPER.PROYECTO : 2013 77POB.ASUMIDO PER.DIS. : 2040 241PERIODO DISEO: 2033 187

    Zona D:HABITANTES SIN SERVICIO : 1885 0HABITANTES CON SERVICIO: 2010 81

    POB.EST.OPER.PROYECTO : 2013 116POB.ASUMIDO PER.DIS. : 2040 371PERIODO DISEO: 2033 287.5

    RESUMENPOBLACION BASE 2010 425POB.EST.OPER.PROYECTO : 2013 543POB.ASUMIDO PER.DIS. : 2040 1335 ASUMIDOPERIODO DISEO: 2033 1077 CALCULO

    Pgina_E 20

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    21/55

    9.- ESQUEMA DEL SISTEMA NUEVO DE AGUA POTABLE DEL CASERIO DEL PICURUYACU BAJO

    QuebradaCaptacin

    . Nueva= 15.98 l/s

    Q:demanda total = 1.42 l/s

    DesarenadorNueva= 1.35 l/s Sedimentador

    Nueva

    DiferenciaLinea de conduccin de cotas:

    Nueva

    Reservorio 01= 2.23 l/s Nueva

    Linea de AduccionNueva

    ZD

    Red de DistribucionZB Nueva

    ZA ZC

    ( Aguas Residualesse vierten si Tratamiento)

    HUALLAGA

    PROBLEMAS DE INFRAESTRUCTURA

    Infraestructuras NUEVA Complementaria-Captacion 1-Desarenador 0.5-Sedimentador 0.5-Linea de Conduccion 1-Reservorio 2-Linea de Aduccion 1-Red de Distribucion 1-Conexiones Domiciliarias 1

    2mh pQ Q k

    1md pQ Q k

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    22/55

    10.- ACTUALIZACION DE DOTACION

    DEMANDA CATASTRAL: Zona "A" Zona "B" Zona "C" Zona "D" Total

    Poblacin Total ao 2010 ( habitantes ) 108 132 28 44 312.Dotacin para el ao 2010(Lt./hab./da) 288 288 288 288 1,152.Consumo promedio ao 2010 ( Lt./seg. ) 0.36 0.44 0.09 0.15 1.Poblacin Total ao 2011( habitantes ) 139 172 61 92 372Consumo promedio ao 2011 ( Lt./seg. ) 0.46 0.57 0.20 0.31 1.55

    Poblacin Total ao 2012 ( habitantes ) 148 183 69 104 400Consumo promedio ao 2012 ( Lt./seg. ) 0.49 0.61 0.23 0.35 1.68

    Poblacin Total ao 2013 ( habitantes ) 156 195 77 116 427Consumo promedio ao 2013 ( Lt./seg. ) 0.52 0.65 0.26 0.39 1.81

    Poblacin Total ao 2014 ( habitantes ) 165 206 85 127 455Consumo promedio ao 2014 ( Lt./seg. ) 0.55 0.69 0.28 0.42 1.94

    Poblacin Total ao 2015 ( habitantes ) 173 217 93 139 483Consumo promedio ao 2015 ( Lt./seg. ) 0.58 0.72 0.31 0.46 2.07

    Poblacin Total ao 2025 ( habitantes ) 212 268 133 204 614Consumo promedio ao 2025 ( Lt./seg. ) 0.71 0.89 0.44 0.68 2.73

    Poblacin Total ao 2035 ( habitantes ) 280 353 201 308 834Consumo promedio ao 2035 ( Lt./seg. ) 0.93 1.18 0.67 1.03 3.81

    Poblacin Total ao 2040 ( habitantes ) 320 403 241 371 965Consumo promedio ao 2040 ( Lt./seg. ) 1.07 1.34 0.80 1.24 4.45

    Poblacin Total ao 2045 ( habitantes ) 361 453 282 433 1,095Consumo promedio ao 2045( Lt./seg. ) 1.20 1.51 0.94 1.44 5.09

    Poblacin Total ao 2055 ( habitantes ) 454 566 376 579 1,396Consumo promedio ao 2055 ( Lt./seg. ) 1.51 1.89 1.25 1.93 6.58

    Poblacin Total ao 2065 ( habitantes ) 560 694 484 745 1,738Consumo promedio ao 2065( Lt./seg. ) 1.87 2.31 1.61 2.48 8.28

    32

    31

    32

    31

    CUADRO 09.- POBLACIN Y CONSUMOS PROMEDIOS (Considerando que la demanda es cte. durante el periodo de diseo)

    1

    26

    16

    2

    3

    4

    5

    6

    Pgina_G 22

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    23/55

    Teniendo en cuenta que la demanda vara con respecto al tiempo efectuamos las correccionesUsando la Expresin de CAPEN (Pg.7 AA-Simn Arocha) adaptada al dato base de cada zonapoblacional:

    G = k p 0.125 Donde : G = Consumo por habitante Lit/hab./da

    P = Poblacin en milesK = 204.4

    Adaptando los valores de k para cada zona poblacional tendremos:Zona A:ka 380.4 Zona B:kb 371 Zona C:kc 450.3 ZonaD: kd 425.6Con stos valores reprocesamos el cuadro No. 9 (corregido usando el modelo adaptado de CAPEN)

    DEMANDA CATASTRAL: Zona "A" Zona "B" Zona "C" Zona "D" Total

    Poblacin Total ao 2010 ( habitantes ) 108 132 28 44 312.0Dotacin para el ao 2010(Lt./hab./da) 288 288 288 288 1,152.0Consumo promedio ao 2010 ( Lt./seg. ) 0.36 0.44 0.09 0.15 1.0Poblacin Total ao 2011( habitantes ) 139 172 61 92 464

    Dotacin para el ao 2011 ( Lt./seg. ) 297 298 317 316Consumo promedio ao 2011 ( Lt./seg. ) 0.48 0.59 0.22 0.34 1.63

    Poblacin Total ao 2012 ( habitantes ) 148 183 69 104 504Dotacin para el ao 2012 ( Lt./seg. ) 299 300 322 321Consumo promedio ao 2012 ( Lt./seg. ) 0.51 0.64 0.26 0.39 1.79

    Poblacin Total ao 2013 ( habitantes ) 156 195 77 116 543Consumo promedio ao 2013 ( Lt./seg. ) 302 302 327 325Consumo promedio ao 2013 ( Lt./seg. ) 0.54 0.68 0.29 0.43 1.95

    Poblacin Total ao 2014 ( habitantes ) 165 206 85 127 583Consumo promedio ao 2014 ( Lt./seg. ) 304 304 331 329Consumo promedio ao 2014 ( Lt./seg. ) 0.58 0.73 0.33 0.48 2.11

    Poblacin Total ao 2015 ( habitantes ) 173 217 93 139 622Consumo promedio ao 2015 ( Lt./seg. ) 305 307 335 333

    Consumo promedio ao 2015 ( Lt./seg. ) 0.61 0.77 0.36 0.54 2.28Poblacin Total ao 2025 ( habitantes ) 212 268 133 204 818Consumo promedio ao 2025 ( Lt./seg. ) 313 315 350 349Consumo promedio ao 2025 ( Lt./seg. ) 0.77 0.98 0.54 0.82 3.11

    1

    2

    3

    4

    5

    6

    16

    CUADRO 10.- POBLACIN Y CONSUMOS PROMEDIOS

    Pgina_G 23

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    24/55

    Poblacin Total ao 2033 ( habitantes ) 266.60 336.33 187.03 287.49 1,077.45Consumo promedio ao 2033 ( Lt./seg. ) 322 324 365 364Consumo promedio ao 2033 Lt./seg. ) 0.99 1.26 0.79 1.21 4.26

    Poblacin Total ao 2035 ( habitantes ) 280 353 201 308 1,142Consumo promedio ao 2035 ( Lt./seg. ) 324 326 368 367Consumo promedio ao 2035 ( Lt./seg. ) 1.05 1.33 0.86 1.31 4.55

    Poblacin Total ao 2040 ( habitantes ) 320 403 241 371 1,335Consumo promedio ao 2040 ( Lt./seg. ) 330 331 377 376Consumo promedio ao 2040 ( Lt./seg. ) 1.22 1.54 1.05 1.61 5.43

    Poblacin Total ao 2045 ( habitantes ) 361 453 282 433 1,528Consumo promedio ao 2045 ( Lt./seg. ) 335 336 384 383Consumo promedio ao 2045( Lt./seg. ) 1.40 1.76 1.25 1.92 6.33

    Poblacin Total ao 2055 ( habitantes ) 454 566 376 579 1,975Consumo promedio ao 2055 ( Lt./seg. ) 345 346 398 397Consumo promedio ao 2055 ( Lt./seg. ) 1.81 2.26 1.73 2.66 8.47

    Poblacin Total ao 2065 ( habitantes ) 560 694 484 745 2,484Consumo promedio ao 2065 ( Lt./seg. ) 354 354 411 410Consumo promedio ao 2065( Lt./seg. ) 2.29 2.85 2.30 3.54 10.98

    32

    26

    31

    32

    31

    Pgina_G 24

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    25/55

    11.- ANALISIS DEL PERIODO DE DISEO

    USANDO LOS DOS TERMINOS DE LA FORMULA DE LAURIA:

    X*1: Periodo optimo: Factor de economia sin escala

    r: Tasa de interes(10-12%).

    CONSIDERANDO LA SIGUIENTE DESCRIPCIN SIMPLIFICADA DE NUEVAS:N.C. = NUEVA CAPTACIN N.C.D. = CAJA DE DISTRIBUCIN

    N.L.C. = NUEVA LNEA DE CONDUCCIN RD.N."A" = REDES NUEVAS PARA "A" RD.N."D" = RD.N."B" = REDES NUEVAS PARA "B"

    N.R.P.=RESERVORIO PRINCIPAL RD.N."C" = REDES NUEVAS PARA "C"

    No. ORDEN ESTRUCT. C. EJEC. C.OP.yMANT. F. ESCAL. TASA INT. %COSTONUEVAS ( S/.) ( S/.) a r

    01 N.C. 3,030 757 0.300 0.200 0.

    02 N.L.C. 25,393 6,348 0.300 0.200 0.03 N.R.P. 8,377 2,094 0.300 0.200 0.04 N.C.D. 2,083 521 0.300 0.200 0.05 RD.N."A" 2,276 569 0.300 0.200 0.

    06 RD.N."B" 2,276 569 0.300 0.200 0.07 RD.N."C" 2,276 569 0.300 0.200 0.08 RD.N."D" 2,276 569 0.300 0.200 0.

    47,985 1

    A O Q (m3/seg.) CAPACID.(m3) POB.(2013) COSTO(Dato) POB.(2040)

    1 RELACIN ENTRE CAPTACIN Y NUEVA CAPTACIN PARALELA (N.C.)COST.EJECUC. 2,010 0.001 .. 543 2,404 1,COST.MANT.. 2,010 0.001 .. 543 601 1,

    A O Q (m3/seg.) CAPACID.(m3) POB.(2013) COSTO(Dato) POB.(2040)

    2 RELACIN ENTRE LINEA EXIST. Y NUEVA LINEA DE CONDUCCIONCOST.EJECUC. 2,010 0.001 .. 543 20,145 1,COST.MANT.. 2,010 0.001 .. 543 5,036 1,

    A O Q (m3/seg.) CAPACID.(m3) POB.(2013) COSTO(Dato) POB.(2040)3 RELACIN ENTRE RESERVORIO PRINCIPAL EXIST. Y NUEVO RESERVORIO PRINCIPAL.

    COST.EJECUC. 2,010 0.001 .. 543 6,646 1,COST.MANT.. 2,010 0.001 .. 543 1,662 1,

    A O Q (m3/seg.) CAPACID.(m3) POB.(2013) COSTO(Dato) POB.(2040)

    4 RELACIN ENTRE CAJA DE DISTRIBUCION EXIST. Y NUEVA CAJA DE DISTRIBUCION.COST.EJECUC. 2,010 0.001 .. 543 1,653 1,COST.MANT.. 2,010 0.001 .. 543 413 1,

    5 RD.N..."A" A O Q (m3/seg.) CAPACID.(m3) POB.(2013) COSTO(Dato) POB.(2040)

    COST.EJECUC. 2,010 0.001 .. 543 1,805 1,COST.MANT.. 2,010 0.001 .. 543 451 1,

    6 RD.N.."B" A O Q (m3/seg.) CAPACID.(m3) POB.(2013) COSTO(Dato) POB.(2040)

    COST EJECUC 2 010 0 001 543 1 805 1

    SE CALCULA EL PERODO DE DISEO EN BASE A LOS DATOS CON QUE SE CUENTA, QUE INDICA QUE SOZONAS A, B Y C,D POR LO QUE Xo TIENE UN VALOR VARIABLE PARA CADA CADA CASO UTILIZANDO EL MAY

    INICIAMOS EL CALCULO ASUMIENDO UN PERIODO DE DISEO DE 30 AOS (2040) USANDO EL CUADRO 09 Y CONSFUNCIONA HASTA EL 2013 PARA A , B ,CY D

    Para determinar el periodo de diseo de las obras complementarias usaremos los resultados de las estimaciones de los aos hanecesidades de agua de las zona "A" Y "B" segn la demanda y las ecuaciones del crecimiento poblacional planteados y proyeuna primera proyeccin al 2040, ao en que por dato se necesitara construir los reservorios zonales por razones de expansin

    21

    85.0

    012.1

    *

    1

    )1(3.0)1(6.2xx

    r

    xa

    rX

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    26/55

    ESTIMACI N DE COSTOS DE LAS ESTRUCTURAS COMPLEMENTARIAS Y REDES EN LAS ZONAS "A,B,CyD"

    ESTIMAREMOS EL VALOR DE Xo PARA CADA ZONA SEGN EL CRECIMIENTO TEORICO ANUAL DE LA POBL

    Se considera el ao 2013, como aquel en donde empezar a operar el proyecto ( Estudio y ejecucin = 3 aos)PARA TODAS LAS OBRAS NUEVAS

    ZONA A: Pob.ref.(2010)= 108 hab. % incid. = 34.62% = r ABCD2013 2005 156 88 R (crec.an 2013 - 2010 = 8 Aos 817 -589 = 68 Hab

    Xo = Poblacin Deficit ( a2013- a1875) / Crecimiento anual poblacional =No existe Deficit en la Poblacin si se tiene en cuenta que su dimensionamiento cubra la demanda al 2065

    ZONA B: Pob.ref.(2010)= 132 hab. % incid. = 42.31% = r ABCD2013 2005 195 105 R (crec.an 2013 - 2010 = 8 Aos 1955 - 1387 = 90 Hab

    Xo = Poblacin Deficit ( a2013- a1875) / Crecimiento anual poblacional =No existe Deficit en la Poblacin si se tiene en cuenta que su dimensionamiento cubra la demanda al 2065

    ZONA C: Pob.ref.(2010)= 28 hab. % incid. = 8.97% = r ABCD2013 1865 77 0 R (crec.an

    2013 - 1875 = 148 Aos 109 - 0 = 77 HabXo = Poblacin Deficit ( a2013- a1875) / Crecimiento anual poblacional =

    No cuentan con el servcio de agua

    ZONA D: Pob.ref.(2010)= 44 hab. % incid. = 14.10% = r ABCD2013 1885 116 0 R (crec.an 2013 - 1875 = 128 Aos 162 - 0 = 116 Hab

    Xo = Poblacin Deficit ( a2013- a1875) / Crecimiento anual poblacional =No cuentan con el servcio de agua

    No. ORDEN Xo X'' (S D) X''(Pond.)

    01 37.49 10.22 0.6502 37.49 10.22 5.41

    03 37.49 10.22 1.7804 37.49 10.22 0.4405 37.49 10.22 0.48

    06 37.49 10.22 0.48

    07 37.49 10.22 0.4808 37.49 10.22 0.48

    299.90 81.77 10.22

    X' + X '' = 8.46 + 32.42 = 18.94 Aos

    SE ASUME = 20.00 Aos2013 20 = 2033.00 Aos

    _Colectores secundarios : 25 aos o m_Colectores principales,emisores,interceptores : 40 a 50 a_Planta de tratamiento : 10 a 15 a

    "LA EVALUACIN SE EFECTUARA TENIENDO COMO BASE LA POBLACION QUE SATURO EL SERVICIO DEL SISTEMPROPORCION A LA POBLACION INCREMENTADA AL AO 2013, AL CONSIDERARSE ESTE AO COMO EN EL QUE EDE AMPLIACIN SE OBTENDRAN LOS COSTOS INCREMENTADOS EN 5% POR AO (04 AOS) DE ACUERDO A LOS

    12.1

    *

    1

    (3.0)1(6.2

    rX

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    27/55

    12.- ANALISIS DEL VOLUMNE DE ALMACENAMIENTO PARA EL RESERVORIO

    NORMA OS. 03012.1.- DATOS BASICOS ALMACENAMIENTO DE AGUA PARA CONSUMO HUMANO

    DEMANDA CATASTRAL: Zona "A" Zona "C"

    Poblacin Total ao 2010( habitantes ) 108 2

    Dotacin para el ao 2010(Lt./hab./da) 288.00 288.0Consumo promedio ao 2010 ( Lt./seg. ) 0.36 0.0

    Poblacin Total ao 2013( habitantes ) 156 7

    Dotacin para el ao 2013(Lt./hab./da) 301.57 326.7Consumo promedio ao 2013 ( Lt./seg. ) 0.54 0.2

    PERIODO DE DISEOPoblacin Total ao 2033( habitantes ) 267 18

    Dotacin para el ao 2033(Lt./hab./da) 322.46 365.

    Consumo promedio ao 2033 ( Lt./seg. ) 0.99 0.7

    RESUMEN AO 2010 RESUMEN AO DE DISEO 203

    a) GASTO PROMEDIO a) GASTO PROMEDIO

    = 1.04 l/s

    b) GASTO MAXIMO DIARIO b) GASTO MAXIMO DIARIO

    K1 = 1.30= 1.35 l/s

    c) GASTO MAXIMO HORARIO c) GASTO MAXIMO HORARIO

    K2 = 2.15= 2.23 l/s

    d) CAUDAL DE OFERTA d) CAUDAL DE OFERTA

    Qofer= 15.98 l/s Qofer

    d) CAUDAL DE DEMANDA c) CAUDAL DE DEMANDA

    Caudal de diseo (Qm) (l/s) = 1.35 Caudal de diseo (Qm)Porcentaje de perdida en Filtro (Pf) (%) = 5.00 Porcentaje de perdida en Filtro Porcentaje de perdida en Sedimentador (Ps) (%) = - Porcentaje de perdida en SedimPorcentaje de perdida en Desarenador (Pd) (%) = - Porcentaje de perdida en Desar

    Perdida total = 5.00 %

    (Caudal a Captar) Qa = 1.42 l/s

    e) EQUACION DE EQUILIBRIO e) EQUACION DE EQUILIBRIO

    Caudal a Captar (Qa) (l/s) = 1.42 Caudal a Captar (Qa)Caudal de Preservacion Ambiental (Qpa=Qo/3) (l/s) = 5.33 Caudal de Preservacion AmbieCaudal de Requirimiento aguas abajo (Qra) (l/s) = 0.00 Caudal de Requirimiento aguas

    Qdemanda = 6.75 l/s

    15.98 6.75

    OKS!!!

    132

    Zona "B"

    288.000.44

    195

    302.350.68

    336

    323.76

    1.26

    /86400

    P

    Poblacion DotacionQ l seg

    1md pQ Q k

    2mh pQ Q k

    PQ

    OFERTA DEMANDAQ Q

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    28/55

    12.1.- VOLUMEN DE ALMACENAMIENTO(reservorio) 2010 VOLUMEN DE ALMACENAM

    Valmacenamiento=Vregul.+Vinc.+Vreserva Valmacenamie

    VAlmacenamiento= 30.66 M3 VAlmacenamien

    a.- VOLUMEN DE REGULACION: a.- VOLUMEN D

    VRegulacion= 30.66 m3 VRegulaci

    b.- VOLUMEN DE RESERVA: b.- VOLUMEN DEl volumen de reserva El volumen de

    Vreserv.= QpxT

    con:2Hr.

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    29/55

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    30/55

    GASTO CUADRO 02.-PROM. GASTO VOLUM. PRODUCC. VOLUM

    HORAS @ 2 horas PROM @ 2HR. VOLUMEN ACUMUL. ACUM.24 Hr. CONSUM% del Qprom. 100 % Dprom. 100% D

    (Lt./seg.) (Lts./s.) (Lts.) (Lts.) (Lts.) (Lt

    0 00 10.00% 0.43 4,608 4,608 30,660 262 20.00% 0.85 9,972 14,580 61,320 464 45.00% 1.92 19,944 34,524 91,980 576 85.00% 3.62 30,672 65,196 122,640 578 115.00% 4.90 32,976 98,172 153,300 5510 100.00% 4.26 46,008 144,180 183,960 39

    12 200.00% 8.52 52,884 197,064 214,620 1714 145.00% 6.17 39,060 236,124 245,280 916 110.00% 4.68 36,000 272,124 275,940 318 125.00% 5.32 41,364 313,488 306,600 -620 145.00% 6.17 37,548 351,036 337,260 -1322 100.00% 4.26 16,884 367,920 367,92024 10.00% 0.43 367,920 398,580 30

    POR DA 51.10 367,920 367.92 Reserv(100%)= 71(Lts./s.) (Lts.) (M3) (M3) 57

    -13

    Qp = 3.96 - 4.26 =

    Efectuamos las estimaciones de las demanda por variaciones de consumo diarias en funcin a los datos suministrados del diario promediPara determinar el caudal medio en Lt./seg. durante el ao 2033, se proceder a desarrollar el cuadro que contiene las variaciones horarias del c

    representa en forma analtica a la curva masa ( Produccin y Demanda vrs. Tiempo).

    LOCALIDAD CACHICOTO ( Consumo promedio ao 2033)

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    31/55

    13.- DISEO DEL FILTRO LENTO

    .- umero e ros

    Se considera como minimo dos unidades para casos de mantenimiento

    .- rea uper c a e ro s

    El area del filtro se puede obtener del caudal y la tasa de filtracin

    III.- Coeficiente de un minimo costo (K)

    IV.- Longitud de la unidad

    V.- DIMENSIONAMIENTO

    Donde As = m2Qd =N =Vf =

    Nota :

    Qd = 5.53 l/s 19.93 m3/hN = 2.00 und 2.00 undVf = 7.00 0.29 m/h

    As = 34.16 m2

    K = 1.33L = 6.75 = 12.00 mB = 5.06 = 8.00 m

    As = 96.00 m2 OK

    VI.- Dimensionamiento del Vertedero de Control

    Vertedero Triangular

    Donde Q =h =

    m3/(m2.dia)

    Caudal en (m3/s)Carga de agua en el vertedero (m)

    Caudal de diseo en (m3/h)Numero de unidadesVelocidad de filtracion (m/h)

    La tasa de filtracin debera estar comprendida entre 2 y 8 m3/(m2.dia). Cuando el unico proceso considerado sea el filtro lento se adoptaranvelocidades de 2 a 3 m3/(m2.dia). En caso de considerar tratamiento preliminar se podran emplear tasas de hasta 5 a 8 m3/(m2.dia)

    1/2( * )L As K

    2*

    1

    NK

    N

    *

    QdAs

    N Vf

    2.51.434*Q h

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    32/55

    14.- DISEO DEL SEDIMENTADOR

    .- arame ros e se o

    Caudal de diseo (Qd)

    Velocidad de sedimentacion (Vs)

    .- rea uper c a e a un a s

    .-

    Donde As =

    Qd =Vs =

    Qd = 5.53 l/s = 0.006 m3/sVs = 0.12 = 0.001 m/s

    As = 4.61 m2

    As = 30.94 m2

    Como el area existente es ma or al area calculada ara el sedimentador entonces la estructura existente se mantiene

    cm/s

    Calculada

    Existente

    El area del sedimentador se puede obtener del caudal y la velocidadde sedimentacion

    Area en m2

    Caudal de diseo en (m3/s)Velocidad de cedimentacion (m/s)

    QdAs

    Vs

    Pgina_K 32

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    33/55

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    34/55

    14.- DISEO DEL DESARENADOR

    .- arame ros e se o

    Caudal de diseo (Qd)

    Velocidad de sedimentacion (Vs)

    II.- Area Superficial de la unidad (As)

    III.- DIMENSIONAMIENTO

    Donde As =Qd =Vs =

    Qd = 5.53 l/s = 0.006 m3/sVs = 0.12 = 0.001 m/s

    As = 4.61 m2

    As = 30.94 m2

    Como el area existente es mayor al area calculada para el sedimentador entonces la estructura exixtente se mantien

    cm/s

    Calculada

    Existente

    El area del sedimentador se puede obtener del caudal y la velocidadde sedimentacion

    Area en m2Caudal de diseo en (m3/s)Velocidad de cedimentacion (m/s)

    QdAs

    Vs

    Pgina_L 34

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    35/55

    e

    Pgina_L 35

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    36/55

    15.- CALCULO DE DIAMETRO ENTRE CAPTACION Y RESERVORIO

    CALCULO DE DIAMETRO ENTRE CAPTACION Y RESERVORIO

    Qdiseo = 5.81 Lts/segCota nivel max. = 811.77 m CAPTACIONCota nivel min. = 708.75 m RESERVORIO

    Dimetro = 63 mm = 2 pugC = 150 Para tubera de PVC

    Longitud total = 370.00 m

    DIMETRO DE TUBERA

    : Coeficiente del dimetroC : Coeficiente de rugosidad del material de la tuberaD : Dimetro de la tubera

    H = 103.02 m Cota de fuente de abastecimiento - Cota de reservorio

    = 0.001943172 Coeficiente del dimetro calculado

    VERIFICACI N DE LA APLICACI N DE LA F RMULA DE HAZEN Y WILLIAM:

    Se debe cumplir: Tipo de flujo : Turbulento Re > 2300Velocidad < 3 m/seg

    Si el flujo es de tipo Laminar entonces usar ecuacin de DARCYHallando la velocidad media:

    V : Velocidad media del flujo

    Q : Caudal de diseoA : rea de la seccin tubera

    A = 0.00 m2

    V = 1.86 m/seg OK

    Tipo de flujo :

    Re : Velocidad media del flujo

    V : Caudal de diseoD : rea de la seccin tubera

    : viscosidad del flujo

    Re = 117180.00 OK

    CHEQUEANDO PRESIN POR PERDIDAS

    Hmin = 3.00 mH = 103.02L = 370.00J = 18.32 OK Requisito : J < H

    84.70 OK

    USAR TUBERA DE 63mm

    CARGA DISPONIBLE EN RESERV. =

    DV Re

    A

    QV

    85.1

    1 QLJ AD

    87.485.1

    31072.1

    DC

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    37/55

    16.- CALCULO DE DIAMETRO ENTRE RESERVORIO Y CAJA DE DISTRIBUCION

    Qdiseo = 5.81 Lts/segCota nivel max. = 708.75 mCota nivel min. = 653.87 m

    Dimetro Existente = 63 mm = 2 pugC = 150 Para tubera de PVC

    Longitud total = 480.00 m

    DIMETRO DE TUBERA

    : Coeficiente del dimetroC : Coeficiente de rugosidad del material de la tuberaD : Dimetro de la tubera

    H = 54.88 m Cota de fuente de abastecimiento - Cota de reservorio

    = 0.001943172 Coeficiente del dimetro calculado

    VERIFICACIN DE LA APLICACIN DE LA FRMULA DE HAZEN Y WILLIAM:

    Se debe cumplir: Tipo de flujo : Turbulento Re > 2300Velocidad < 3 m/seg

    Si el flujo es de tipo Laminar entonces usar ecuacin de DARCYHallando la velocidad media:

    V : Velocidad media del flujo

    Q : Caudal de diseoA : rea de la seccin tubera

    A = 0.00 m2

    V = 1.86 m/seg OK

    Tipo de flujo :

    Re : Velocidad media del flujo

    V : Caudal de diseoD : rea de la seccin tubera

    : viscosidad del flujo

    Re = 117180.00 OK

    CHEQUEANDO PRESIN POR PERDIDAS

    Hmin = 3.00 mH = 54.88L = 480.00J = 23.77 OK Requisito : J < H

    31.11 OK

    USAR TUBER A DE 63mm

    CARGA DISPONIBLE EN RESERV. =

    DV Re

    A

    QV

    85.1

    1 QLJ AD

    87.485.1

    31072.1

    DC

    Pgina_N 37

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    38/55

    16.- DATOS BASICOS PARA EL CALCULO DE LA RED DE DISTRIBUCION

    I.- DATOS INICIALES

    DEMANDA CATASTRAL: Zona "A" Zona "B" Zona "C" Zona "D" Total DE

    Poblacin Total ao 2010( habitantes ) 108 132 28 44 312

    Dotacin para el ao 2010(Lt./hab./da) 288.00 288.00 288.00 288.00 BAConsumo promedio ao 2010 ( Lt./seg. ) 0.36 0.44 0.09 0.15 1.04

    Poblacin Total ao 2013( habitantes ) 156 195 77 116 543

    Dotacin para el ao 2013(Lt./hab./da) 301.57 302.35 326.72 324.99 OConsumo promedio ao 2013 ( Lt./seg. ) 0.54 0.68 0.29 0.43 1.95

    PERIODO DE DISEO 20Poblacin Total ao 2033( habitantes ) 267 336 187 287 1,077 FINDotacin para el ao 2033(Lt./hab./da) 322.46 323.76 365.17 364.19 CConsumo promedio ao 2033 ( Lt./seg. ) 0.99 1.26 0.79 1.21 4.26

    Poblacion de Diseo : (hab) = 1077Lotes existentes (und) = 82.00Lotes Proyectados (und) = 558Total de Lotes y/o viviendas (und) = 640.00Personas por lotes 1.68

    LOTES A B C D TOTALPROYECTADO 120 170 146 122 558EXISTENTE 150 349 21 26 546CATASTRO 29 33 8 11 81

    P+E 11040

    II.- ESQUEMA DE LA RED

    RESUMEN DE LOTES AO 2033

    Pgina_O38

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    39/55

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    40/55

    III.- ZONIFICACION

    El area de presenta una 04 zonaS, con los siguientes parametros.

    ZONA A,B,C y DCoeficiente de Mayoracion Diaria (k1)Coeficiente de Mayoracion Horaria (k2)

    IV.- DOTACION EN LOS NUDOS DE ANALISIS

    En el siguiente cuadro mostramos la dotacion a emplear en la red

    agua para riego jardinesAgua para viviendas

    Agua para viviendas > 90 m2Agua para viviendas < 90 m2asiloseducacion primariaeducacion secundaria y superiorestadioshospedajeshospitales y centros de salud

    mercados y establecimientosoficinas

    La cantidad de agua que se consume en una red publica varia continuamente

    DESCRIPCION

    3

    1

    3

    1

    1

    1

    11

    1

    3

    -C

    -

    -

    -

    3

    -- 1

    1

    -

    -

    --

    - -

    1

    -

    -

    3

    1 111

    -C

    -

    -

    --

    -C - -

    -

    3

    1

    -

    -

    13111

    1

    - -

    1

    111

    1

    1

    -

    -

    --C

    --

    --

    -

    -

    3

    3

    1 --

    -

    -

    -

    -

    -C

    1

    --

    --

    -

    -

    1

    11

    1

    11

    1

    13

    1

    1

    -

    -

    -C

    --

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    41/55

    NUDO 02

    Zonificacin : ZONA BCota (m) = 796.7

    Caudal Medio (Qm) (l/Dia) =

    NUDO 03

    Zonificacin : ZONA BCota (m) = 795.3

    Caudal Medio (Qm) (l/Dia) =

    NUDO 04

    Zonificacin : ZONA BCota (m) = 794.9

    Caudal Medio (Qm) (l/Dia) =

    Lote Proyectado 0 2 311 0.00

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/dia

    Q MEDIOl/dia

    38248.06

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    Lote existente 73 2 311 38248.06

    Lote existente 40 2 311 20957.84Lote Proyectado 0 2 311 0.00

    AREAS VERDESM2

    DOTACIONL/m2/dia

    Q MEDIOl/dia

    PLAZA DE ARMAS 2000 5 10000.00

    Lotes Proyectados 35 2 311 18338.11

    30957.84

    VIVIENDAS Y/O LOTESPERSONA

    LOTE

    DOTACION

    L/hab/da

    Q MEDIO

    l/da

    29340.97

    Lotes Exisitentes 21 2 311 11002.87

    Pgina_O41

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    42/55

    NUDO 05

    Zonificacin : ZONA BCota (m) = 799.7

    Caudal Medio (Qm) (l/Dia) =

    NUDO 06

    Zonificacin : ZONA BCota (m) = 797.8

    Caudal Medio (Qm) (l/Dia) =

    NUDO 07

    Zonificacin : ZONA BCota (m) = 796

    Caudal Medio (Qm) (l/Dia) =

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    Lotes Exisitentes 7 2 311 3667.62Lotes Proyectados 35 2 311 18338.11

    62005.73

    VIVIENDAS Y/O LOTESPERSONA

    LOTE

    DOTACION

    L/hab/da

    Q MEDIO

    l/da

    hospitales 1 50 800 40000.00

    Lotes Exisitentes 37 2 311 19386.00Lotes Proyectados 25 2 311 13098.65

    39984.65

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    Colegio A. R. 1 300 25 7500.00

    Lotes Exisitentes 10 2 311 5239.46

    Lotes Proyectados 25 2 311 13098.65

    18338.11

    Pgina_O42

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    43/55

    NUDO 08

    Zonificacin : ZONA BCota (m) = 798

    Caudal Medio (Qm) (l/Dia) =

    NUDO 09

    Zonificacin : ZONA BCota (m) = 796.85

    Caudal Medio (Qm) (l/Dia) =

    NUDO 10

    Zonificacin : ZONA BCota (m) = 796.1

    Caudal Medio (Qm) (l/Dia) =

    Lotes Proyectados 25 2 311 13098.65

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    estadios 1 1000 15 15000.00Lotes Exisitentes 23 2 311 12050.76

    Lotes Proyectados 0 2 311 0.00

    40149.41

    VIVIENDAS Y/O LOTESPERSONA

    LOTE

    DOTACION

    L/hab/da

    Q MEDIO

    l/da

    14146.54

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    Lotes Exisitentes 27 2 311 14146.54

    Lotes Exisitentes 13 2 311 6811.30Lotes Proyectados 0 2 311 0.00

    6811.30

    Pgina_O43

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    44/55

    NUDO 11

    Zonificacin : ZONA BCota (m) = 795.5

    Caudal Medio (Qm) (l/Dia) =

    NUDO 12

    Zonificacin : ZONA A

    Cota (m) = 794.7

    Caudal Medio (Qm) (l/Dia) =

    NUDO 13

    Zonificacin : ZONA ACota (m) = 793.8

    Caudal Medio (Qm) (l/Dia) =

    Lotes Proyectados 0 2 311 0.00

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    PARQUE 1000 5 5000.00

    Lotes Exisitentes 57 2 311 29864.92

    34864.92

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    AREAS VERDESM2

    DOTACIONL/m2/dia

    Q MEDIOl/dia

    Lote existente 51 2 256 21992.67Lote Proyectado 0 2 256 0.00

    AREAS VERDESM2

    DOTACIONL/m2/dia

    Q MEDIOl/dia

    CENTRO CIVICO 500 20 10000.00

    Lote Proyectado 25 2 256 10780.72

    31992.67

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    21561.44

    Lote existente 25 2 256 10780.72

    Pgina_O44

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    45/55

    NUDO 14

    Zonificacin : ZONA ACota (m) = 793.1

    Caudal Medio (Qm) (l/Dia) = 58368.09146

    NUDO 15

    Zonificacin : ZONA A

    Cota (m) = 791.9

    Caudal Medio (Qm) (l/Dia) =

    NUDO 16

    Zonificacin : ZONA ACota (m) = 791.85

    Caudal Medio (Qm) (l/Dia) =

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    Lote existente 31 2 256 13368.09Lote Proyectado 0 2 256 0.00

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    AREAS VERDESM2

    DOTACIONL/m2/dia

    Q MEDIOl/dia

    MERCADO 3000 15 45000.00

    Lote existente 21 2 256 9055.80Lote Proyectado 25 2 256 10780.72

    Lote Proyectado 35 2 256 15093.01

    19836.52

    VIVIENDAS Y/O LOTESPERSONA

    LOTE

    DOTACION

    L/hab/da

    Q MEDIO

    l/da

    Camal 1 50 300 15000.00Lote existente 10 2 256 4312.29

    34405.29

    Pgina_O45

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    46/55

    NUDO 17

    Zonificacin : ZONA ACota (m) = 790.7

    Caudal Medio (Qm) (l/Dia) =

    NUDO 18

    Zonificacin : ZONA DCota (m) = 802

    Caudal Medio (Qm) (l/Dia) =

    NUDO 19

    Zonificacin : ZONA DCota (m) = 796

    Caudal Medio (Qm) (l/Dia) =

    NUDO 20

    Zonificacin : ZONA DCota (m) = 798

    Caudal Medio (Qm) (l/Dia) =

    NUDO 21

    Zonificacin : ZONA CCota (m) = 794

    42Lote Proyectado

    2 227 2294.00

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    3058.6622728Lote existente

    Lote existente 12 2 227 4587.99

    Q MEDIOl/da

    DOTACIONL/hab/da

    PERSONALOTE

    VIVIENDAS Y/O LOTES

    Lote Proyectado 35 2 256 15093.01

    VIVIENDAS Y/O LOTES PERSONALOTE

    DOTACIONL/hab/da

    Q MEDIOl/da

    Lote existente 11 2 256 4743.52

    DOTACIONL/hab/da

    Q MEDIOl/da

    16057.972272

    19498.96

    19836.52

    17969.63

    19116.63

    Lote Proyectado 45 2 227 17204.96

    Lote Proyectado 35 2 227 13381.64

    Lote existente 6

    VIVIENDAS Y/O LOTESPERSONA

    LOTE

    Pgina_O46

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    47/55

    Caudal Medio (Qm) (l/Dia) =

    NUDO 22

    Zonificacin : ZONA CCota (m) = 790

    Caudal Medio (Qm) (l/Dia) =

    NUDO 23

    Zonificacin : ZONA CCota (m) = 792

    Caudal Medio (Qm) (l/Dia) =

    Lote existente 6 2 205 2071.47

    15881.30

    24512.44

    Lote Proyectado 66 2 205 22786.21Lote existente 5 2 205 1726.23

    Lote existente 10 2 205 3452.46

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    17262.28

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    Lote Proyectado 40 2 205 13809.83

    VIVIENDAS Y/O LOTESPERSONA

    LOTEDOTACIONL/hab/da

    Q MEDIOl/da

    40 2 205 13809.83Lote Proyectado

    Pgina_O47

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    48/55

    NUDO RESUMEN

    = 5.53 l/s Q= 9.14 l/s Q= 11.88 l/s

    NUDO 232.

    2.

    NUDO 20NUDO 21NUDO 22

    1.30 2.

    0.28 ZONA C 1.30 2.

    2.0.20 ZONA C 1.30 2.0.23 ZONA D 1.30

    0.59 ZONA C 1.30

    NUDO 190.21 ZONA D 1.30

    NUDO 05 0.72 ZONA B 1.30 2.NUDO 04 0.34 ZONA B

    NUDO 06

    NUDO 09NUDO 08 0.46 ZONA B 1.30

    0.22 ZONA D 1.30 2.

    ZONA B 1.30 2.0.46 ZONA B 1.30 2.

    0.16 ZONA B 1.30 2.

    NUDO 01 0.39 ZONA B 1.30 2.

    NUDO 03

    NUDO 18

    0.36 ZONA B 1.30 2.NUDO 02 0.44

    2.NUDO 07 0.21

    NUDO 11

    ZONA B 1.30 2.

    NUDO Qml/dia ZONA k1 k2

    0.40 ZONA B 1.30 2.NUDO 10 0.08 ZONA B 1.30 2.

    NUDO 13 0.25 ZONA A 1.30 2.NUDO 12 0.37 ZONA A 1.30 2.

    NUDO 15 0.23 ZONA A 1.30 2.NUDO 14 0.68 ZONA A 1.30 2.

    NUDO 17 0.23 ZONA A 1.30 2.NUDO 16 0.40 ZONA A 1.30 2.

    Qm = l/seg Qm*K2=Qm = 7.91 l/dia Qm*K1=

    4.26Qm*K2*K1=

    Pgina_O48

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    49/55

    V.- PROPIEDADES DE LOS MATERIALES

    Nudo Inicial Nudo final

    R-02 N-01N-01 N-05N-01 N-02N-01 N-08N-02 N-11N-03 N-02N-04 N-03N-08 N-09N-05 N-06N-10 N-09N-11 N-10N-11 N-12N-06 N-02

    N-06 N-07N-16 N-17N-14 N-16N-12 N-03N-12 N-14N-17 N-15N-15 N-14N-15 N-13N-13 N-04N-13 N-12N-07 N-04N-11 N-23N-23 N-22N-23 N-21N-06 N-20

    N-20 N-19N-20 N-18TUB-30

    662.00418.00192.00244.00

    305.00286.00

    160160160160

    160160

    TUB-25TUB-26TUB-27TUB-28

    TUB-29

    Las tuberas emplear sern de material de fcil adquisicin, de dimetros comerciales y los dimetros no debern ser menores a 75mm (segn RNE), tal como se

    NOMENCLATURA Longitudm

    Diametro(mm)

    TUB-03 291.51 160TUB-04 117.87 160

    TUB-01 1160.44 160TUB-02 241.41 160

    TUB-07 184.29 160TUB-08 187.19 160

    TUB-05 251.58 160TUB-06 217.18 160

    TUB-11 98.27 160TUB-12 212.57 160

    TUB-09 289.54 160TUB-10 124.77 160

    TUB-15 201.91 160TUB-16 198.08 160

    TUB-13 232.13 160

    TUB-14 397.99 160

    TUB-19 210.4 160TUB-20 191.12 160

    TUB-17 243.54 160TUB-18 237.42 160

    TUB-23 188.61 160TUB-24 232.05 160

    TUB-21 238.37 160TUB-22 239.06 160

    Pgina_O49

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    50/55

    VI.- PROCESAMIENTO DE DATOS

    Los datos sern procesados en el software WaterCad empleando los siguientes modelos matemticos

    Hazen-Williams

    Donde:k = Constante (0.85 en SI , 1.32 en US ).

    Darcy-Weisbach

    Esquema de la red principal

    VII.- RESULTADOS DE PROCESAMIENTO

    Pgina_O50

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    51/55

    A) RESULTADO DE CARGA DE PRESIONES

    Pmax = 50 Pmin = 10

    N-01 798.50 2.65 818.79 20.2N-02 796.70 3.02 817.48 20.7N-03 795.30 1.98 817.25 21.9N-04 794.90 2.32 817.22 22.2N-05 799.70 3.03 818.05 18.3N-06 797.80 2.81 817.47 19.6N-07 796.00 1.45 817.28 21.2N-08 798.00 2.47 818.37 20.3N-09 796.85 1.12 817.87 20.9N-10 796.10 0.54 817.59 21.4

    N-11 795.50 2.52 817.38 21.8N-12 794.70 2.89 817.18 22.4N-13 793.80 2.52 817.15 23.3N-14 793.10 3.02 817.06 23.9N-15 791.90 2.32 817.06 25.1N-16 791.85 2.75 817.04 25.1N-17 790.70 2.32 817.04 26.2N-18 802.00 1.73 817.33 15.3N-19 796.00 1.84 817.33 21.2N-20 798.00 1.87 817.35 19.3N-21 794.00 1.66 816.91 22.8N-22 790.00 2.66 816.86 26.8N-23 792.00 2.35 816.92 24.8

    En la tabla se presenta como resultado de la solucin de la red las presiones que existen en los nudos de los puntos. Las presiones mximas esttubera en este caso es de 50 mH2O y la presin de mnima no de ser menor a 10 mH2O segn RNE.

    NUDOElevacion

    (m)Demanda

    (L/s)Energia

    (m)Presio(m H2O

    Pgina_O51

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    52/55

    B) RESULTADO DE VELOCIDADES

    TUB-01 446.27 160 150 51.8TUB-02 241.41 160 150 14.8TUB-03 291.51 160 150 18TUB-04 117.87 160 150 16.1TUB-05 251.58 160 150 4.9TUB-06 217.18 160 150 -8.4TUB-07 184.29 160 150 -2.6TUB-08 187.19 160 150 13TUB-09 289.54 160 150 11.7TUB-10 124.77 160 150 -12.5TUB-11 98.27 160 150 -12.0

    TUB-12 212.57 160 150 7.7TUB-13 232.13 160 150 -1TUB-14 397.99 160 150 5.3TUB-15 201.91 160 150 -0.1TUB-16 198.08 160 150 2.5TUB-17 243.54 160 150 -3.8TUB-18 237.42 160 150 5.6TUB-19 210.4 160 150 -2.4TUB-20 191.12 160 150 -0.0TUB-21 238.37 160 150 -4.7TUB-22 239.06 160 150 -4.1TUB-23 188.61 160 150 -3TUB-24 232.05 160 150 3.8TUB-25 652.08 160 150 6.6TUB-26 384.73 160 150 2.6

    TUB-27 224.67 160 150 1.6TUB-28 248.3 160 150 5.4TUB-29 396.23 160 150 1.8TUB-30 293.35 160 150 1.7

    El dimetro mnimo a emplear es de 75mm segn RNE.

    Longitudm

    Diametro(mm)

    Hazen-WilliamsC

    Cauda(L/s)

    Pgina_O52

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    53/55

    C) GRAFICO DE ALTURA DE PRESIONES

    VII.- CONCLUSIONES

    Las presiones en todos los puntos crticos son menores a 50 m de altura, por lo tanto, se empleara tubera de clase 5

    Las velocidades en las tuberas son menores a 3 m/s, cumpliendo el RNE y pudindose dar el uso de tuberas de PVC

    Los dimetros a emplear en el sistema ser los siguientes.

    VIII.- RECOMENDACIONES

    Para las tuberas se recomienda que cumplan con la Norma Tcnica Peruana: ITINTEC 399-002, en la que indica lo siguiente:

    La tubera es de Policloruro de Vinilo (PVC).

    El dimetro nominal esta dado en milimetros

    160 1160.44 1160.44Todos los Dimetros 6187.29 6187.29

    Se presenta las lneas de conduccin mas criticas del sistema planteado.

    Dimetro (mm) PVC (m) Todos los Materiales (m)

    160 5026.86 5026.86

    Pgina_O53

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    54/55

    Po(hab) Viv hab/viv Tasa crec Dotacion l/hab/dia2009 :

    200 40 5 1.4 2202010 : 401 80 5 1.4 2202011 803 161 5 1.4 2202012 1608 322 5 1.4 2202013 3222 644 5 1.4 2202014 6454 1291 5 1.4 2202015 12930 2586 5 1.4 2202020 26079 5216 5 1.4 2202025 52601 10520 5 1.4 2202030 106095 21219 5 1.4 2202035 213989 42798 5 1.4 2202040 431609 86322 5 1.4 220

  • 8/10/2019 1.-PARAMETROS DE DISEO PICUROYACU 2011 CORREG.xlsx

    55/55

    Q:Dot*Po/86400 l/s

    0.5111.00

    1.02 22.042.04 44.154.09 88.458.20 177.1916.43 354.9832.92 711.1566.41 1434.36133.94 2893.06270.15 5835.20544.88

    1099.00