Page 1: New FCU Presentation

FCU & AHU

Creates A Better Life

23/4/28

Page 2: New FCU Presentation

Fan coil unit

Page 3: New FCU Presentation

How to Read the Model Name?

T1 127V 60 Hz Duct Type

F1 Exposed Floor-stand Type (side air intake)

Nominal Air Volume(CFM)

Chilled Water Fan coil unit

C One Way Cassette T DuctA 4 Way Cassette B 4 Way Cassette (Compact)

T2 2nd Generation Duct Type

Type Code

F2 Exposed Flood-stand Type (below air intake)F3 Concealed Flood-stand Type

-- Normal Static Pressure H High Static Pressure

E with Electrical HeaterR Remote Control RA Remote Control with Electrical HeaterFunction Code

T3 New High-static Pressure Type

G Wall-mounted TypeH1 Exposed Ceiling and Floor Type (side air intake)

H2 Exposed Ceiling and Floor Type (back air intake)H3 Concealed Ceiling and Floor Typy

Page 4: New FCU Presentation

Fan Coil

Ceiling and

Floor

Duct Wall mounted

Floor Standing

Cassette

Page 5: New FCU Presentation

1-Way4-Way

Compact

4-Way 4 pipes

Cassette

MKCMKBMKA MKD

Page 6: New FCU Presentation

1.1. Cooling capacity: 5.7~10.4kW;Cooling capacity: 5.7~10.4kW;

2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);

3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);

4.4. Maximum water inlet temp. is 70 ;℃Maximum water inlet temp. is 70 ;℃

Four-way Cassette

Model List:Model List:

*EAH: Electric Auxiliary Heater

Without EAH With EAHMKA-600R MKA-600RA 2100wMKA-750R MKA-750RA 2100wMKA-850R MKA-850RA 2700wMKA-950R MKA-950RA 2700wMKA-1200R MKA-1200RA 2700w

Page 7: New FCU Presentation

Four-way cassette

Variable color for the panel:

5.5. LED display in the panel;LED display in the panel;6.6. Different color for the panel;Different color for the panel;7.7. Fresh air function;Fresh air function;8.8. Reserve spaces for air side-outletReserve spaces for air side-outlet

3 Pre-cut holeSend air to the nearby room

BlueWhite Grey Black

Page 8: New FCU Presentation

New design

1.1. Cooling capacity: 3.0~5.5kW;Cooling capacity: 3.0~5.5kW;

2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);

3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);

4.4. Maximum water inlet temp. is 70℃Maximum water inlet temp. is 70℃5.5. Dimension: 580×254×580Dimension: 580×254×580

Four-way Cassette(60*60)

Model List:Model List:Without EAH* With EAH

MKB-300R MKB-300RA 1000wMKB-400R MKB-400RA 1000wMKB-450R / /MKB-500R / /

*EAH: Electric Auxiliary Heater

Compact

Page 9: New FCU Presentation

1.1. Cooling capacity: 3040w, 3790w;Cooling capacity: 3040w, 3790w;

2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);

3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);

One-way Cassette

Model List:Model List:

Without EAH With EAHMKC-300R MKC-300RA 1000wMKC-400R MKC-400RA 1000w

*EAH: Electric Auxiliary Heater

Page 10: New FCU Presentation

4-way pipe

Heat water pipe

Chill water pipe

Models MKD-600F

MKD-750F

MKD-850F

MKD-950F

MKD-1200F

MKD-1500F

Cooling capacity(Btu/h) 17406 20239 21058 22867 31672 36109

Heating capacity(Btu/h)

22765 26860 27509 29590 39761 43072

1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.

2.2. Save a lot of energies in winter.Save a lot of energies in winter.

3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.

Page 11: New FCU Presentation

4-way pipe

Heat water pipe

Chill water pipe

Models MKD-300

MKD-400

MKD-500

Cooling capacity(Btu/h) 10236 12624 15354

Heating capacity(Btu/h)

13648 17401 20472

1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.

2.2. Save a lot of energies in winter.Save a lot of energies in winter.

3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.

Page 12: New FCU Presentation

Accessories for cassette

EAH Filter Additional drain pan

3-way valve

Connection kit

Controller

MKA C S O O O SMKB C S O O O SMKC C S O O O SMKD C S O O O SC: the accessories is optional, but it should be assembled in the factory;

S: the accessories is standard;

O: the accessories is optional, it can installed by the installer.

Accessories table:

Page 13: New FCU Presentation

Block for air outlet hole:

Accessories for cassette

Note: the block is only for four-way cassette(80*80 type).

(Optional)

Page 14: New FCU Presentation

Accessories for cassette

Additional drain pan (optional):

For 4-way cassette compact For 4-way cassette

Page 15: New FCU Presentation

Accessories for cassette

3-way valve Connection Kit

Electronic coil

Valve

(Optional) (Optional)

Page 16: New FCU Presentation

Wireless controller

Wired controller

Central controller

Controllers for cassette

Standard Optional Optional

Note: NIM is necessary if use central controller to control the cassette.

Page 17: New FCU Presentation

2 Rows

3 Rows

4 Rows

Duct

HSP

MKT2 MKT3 MKT4 MKT5 MKT3H

4 Pipe

Page 18: New FCU Presentation

Duct (2-Rows without EAH)

1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are optional (Assembled in factory);Air return plenums (including filter) are optional (Assembled in factory);3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

12Pa 30(50)PaMKT2-200 MKT2H-200MKT2-300 MKT2H-300MKT2-400 MKT2H-400MKT2-500 MKT2H-500MKT2-600 MKT2H-600MKT2-800 MKT2H-800

MKT2-1000 MKT2H-1000MKT2-1200 MKT2H-1200MKT2-1400 MKT2H-1400

Model List:Model List:

MKT2, MKT2HMKT2, MKT2H

Page 19: New FCU Presentation

Duct (2-Rows with EAH)

MKT2-xxxE, MKT2H-xxxEMKT2-xxxE, MKT2H-xxxE

Model List:Model List:

12Pa 30(50)Pa EAHMKT2-200E MKT2H-200E 500wMKT2-300E MKT2H-300E 650wMKT2-400E MKT2H-400E 1000wMKT2-500E MKT2H-500E 1000wMKT2-600E MKT2H-600E 1500wMKT2-800E MKT2H-800E 2000w

MKT2-1000E MKT2H-1000E 2000wMKT2-1200E MKT2H-1200E 3000wMKT2-1400E MKT2H-1400E 3000w

1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are standard;Air return plenums (including filter) are standard;3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Page 20: New FCU Presentation

1.1. Cooling capacity:Cooling capacity: 2.2~12.1kW;2.2~12.1kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. For For MKT3H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Duct (3-Rows without EAH)

12Pa 30(50)PaMKT3-200 MKT3H-200MKT3-300 MKT3H-300MKT3-400 MKT3H-400MKT3-500 MKT3H-500MKT3-600 MKT3H-600MKT3-800 MKT3H-800

MKT3-1000 MKT3H-1000 MKT3-1200 MKT3H-1200

Model List:Model List:

Page 21: New FCU Presentation

1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Duct (4-Rows without EAH)

30PaMKT4H-200MKT4H-300MKT4H-400MKT4H-500MKT4H-600MKT4H-800

MKT4H-1000MKT4H-1200MKT4H-1500MKT4H-2000

Model List:Model List:

Page 22: New FCU Presentation

1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Duct (4-Rows with EAH)

30PaMKT4H-200EMKT4H-300EMKT4H-400EMKT4H-500EMKT4H-600EMKT4H-800E

MKT4H-1000EMKT4H-1200EMKT4H-1500EMKT4H-2000E

Model List:Model List:

Page 23: New FCU Presentation

High Static Pressure Duct (without EAH)

1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Static PressureMKT3H-800 70Pa

MKT3H-1000 70PaMKT3H-1200 70PaMKT3H-1400 70PaMKT3H-1600 100PaMKT3H-2000 100PaMKT3H-2200 100Pa

Model List:Model List:MKT3H SeriesMKT3H Series

Page 24: New FCU Presentation

With EAH EAH Static Pressure

MKT3H-800E 3Kw 70PaMKT3H-1000E 3Kw 70PaMKT3H-1200E 3Kw 70PaMKT3H-1400E 3Kw 70PaMKT3H-1600E 10Kw 100PaMKT3H-2000E 10Kw 100PaMKT3H-2200E 10Kw 100Pa

High Static Pressure Duct (with EAH)

Model List:Model List:MKT3H-xxxE SeriesMKT3H-xxxE Series

1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Page 25: New FCU Presentation

4 Pipe ducted type

1 fan 2 fans 4 fans

Models MkT5-200

MkT5-300

MKT5-400

MKT5-500

MKT5-600

MkT5-800

MkT5-1000

MkT5-1200

Cooling capacity(Btu/h) 6826 9215 12287 14676 17065 23208 26621 34812

Heating capacity(Btu/h)

10239 13652 17747 19454 24573 32765 36860 46075

1.For ESP,12Pa and 30Pa are optional.1.For ESP,12Pa and 30Pa are optional.2.The functions are same as 2 pipe ducted type.2.The functions are same as 2 pipe ducted type.

Page 26: New FCU Presentation

Accessories for duct

EAH Air return plenum &Filter

Additional drain pan

3-way valve

Connection kit

Controller

MKT2No C S O O OYes S S O O O

MKT3 No C S O O O

MKT4No C S O O OYes S S O O O

MKT3HNo C S O O OYes S S O O O

MKT5 No C S O O OC: the accessories are optional, but it should be assembled in the factory;

S: the accessories are standard;

O: the accessories are optional, it can be installed by the installer.

Accessories table:

Page 27: New FCU Presentation

Air return plenums and electrical heaters:

Accessories for duct

The EAH must be installed in the factory;The air return plenums must be installed in the factory;The duct with EAH must select air return plenums, because the EAH is installed inside the air return plenums;

Page 28: New FCU Presentation

3-way valve

Electronic coil

Valve

Accessories for duct

(Optional)Connection Kit

(Optional)

Page 29: New FCU Presentation

Thermostat.

For the units without EAH

For the units with EAH

Controllers for Duct

OptionalOptional

Page 30: New FCU Presentation

MKF1 MKF2 MKF3 MKF5

Floor Standing

MKF4

ExposedFlat panel

Side intake

ExposedCurving panel

Bottom intake

ExposedFlat panel

Bottom intake

ConcealedExposedCurving panel

Side intake

Page 31: New FCU Presentation

Floor-standing

Exposed typeExposed type Exposed MKF1-150 MKF2-150MKF1-250 MKF2-250MKF1-300 MKF2-300MKF1-400 MKF2-400MKF1-450 MKF2-450MKF1-500 MKF2-500MKF1-600 MKF2-600MKF1-800 MKF2-800MKF1-900 MKF2-900

Model List:Model List:

MKF1: air return from front side

MKF2: air return from bottom ( standard with foot)

1. Vertical installation on the floor- much more comfortable in heating mode;

2. 3-way valve can be built in the cabinet;

3. Pipe connection can be left or right (installer change it).

Page 32: New FCU Presentation

Flat type air outlet grill

Exposed type New air outlet grill

Floor-standing

ExposedMKF4-150 MKF5-150MKF4-250 MKF5-250MKF4-300 MKF5-300MKF4-400 MKF5-400MKF4-450 MKF5-450MKF4-500 MKF5-500MKF4-600 MKF5-600MKF4-800 MKF5-800MKF4-900 MKF5-900MKF4: air return from front side

MKF5: air return from bottom ( standard with foot)

Model List:

The grill is modular design- easily removed and cleaned

Page 33: New FCU Presentation

Floor-standing

Concealed typeConcealed typeModel List:Model List:

ConcealedMKF3-150MKF3-250MKF3-300MKF3-400MKF3-450MKF3-500MKF3-600MKF3-800MKF3-900

1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;

Page 34: New FCU Presentation

Accessories for Floor standing

C: the accessories is optional, but it should be assembled in the factory;

S: the accessories is standard;

O: the accessories is optional, it can installed by the installer.

Accessories table:

Filter Additional drain pan

3-way valve

Connection kit

Controller

Exposed S S O O OConcealed / S O O O

Page 35: New FCU Presentation

Accessories for Floor standing

3-way valve, connection kit and additional drain pan

3-way valve-Optional

Connection kit-Optional

Page 36: New FCU Presentation

Thermostat (optional):

Controllers for Floor-standing

KJR-15B/E Simple controller

KJR-15B/E(P) With anti cold air function

The controller can be hided in the cabinet (only for MKF1,2,4,5)

Optional

Optional

Page 37: New FCU Presentation

MKH2 MKH3

Ceiling and Floor

ExposedCurving panel

Back intake

ConcealedExposedCurving panel

Side intake

MKH1

Page 38: New FCU Presentation

Ceiling-Floor

Exposed typeExposed type Model List:Model List:

air return from front side

1. Vertical installation on the floor- much more comfortable in heating mode;

2. 3-way valve can be built in the cabinet;

3. Pipe connection can be left or right (installer change it);

4. Ceiling and Vertical installation for optional will be more convenience.

ExposedMKH1-150MKH1-250MKH1-300MKH1-400MKH1-450MKH1-500MKH1-600MKH1-800MKH1-900

Page 39: New FCU Presentation

Ceiling-Floor

Exposed typeExposed type Model List:Model List:

air return from bottom

1. Vertical installation on the floor- much more comfortable in heating mode;

2. 3-way valve can be built in the cabinet;

3. Pipe connection can be left or right (installer change it);4. Ceiling and Vertical installation for optional will be more convenience.

ExposedMKH2-150MKH2-250MKH2-300MKH2-400MKH2-450MKH2-500MKH2-600MKH2-800MKH2-900

Page 40: New FCU Presentation

Concealed typeConcealed type Model List:Model List: ConcealedMKH3-150MKH3-250MKH3-300MKH3-400MKH3-450MKH3-500MKH3-600MKH3-800MKH3-900

1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;

Ceiling-Floor

Page 41: New FCU Presentation

Accessories for Ceiling and Floor

C: the accessories is optional, but it should be assembled in the factory;

S: the accessories is standard;

O: the accessories is optional, it can installed by the installer.

Accessories table:

Filter Additional drain pan

3-way valve

Connection kit

Controller

Exposed S S O O OConcealed / S O O O

Page 42: New FCU Presentation

3-way valve, connection kit and additional drain pan

3-way valve-Optional

Connection kit-Optional

Accessories for Ceiling and Floor

Page 43: New FCU Presentation

Wall Mounted

MKG-250MKG-300MKG-400MKG-500MKG-600

Model List:Model List:

1.1. Capacity: 2.24~4.5kW;Capacity: 2.24~4.5kW;

2.2. 3-way valve is inside the indoor unit;3-way valve is inside the indoor unit;

3.3. ON/OFF terminal for simple remote control ;ON/OFF terminal for simple remote control ;

4.4. Variable color for the panel;Variable color for the panel;

5.5. Multi direction of pipe connection.Multi direction of pipe connection.

MKG SeriesMKG Series

Page 44: New FCU Presentation

3-way valve Controller Filter

MKG S S See in next page

S: the accessories are standard;

Accessories for Wall mounted

Accessories table:

Page 45: New FCU Presentation

Bio filter Silver lon filterGTP filter Deodorization filterAnti- formaldehyde filter Silver lon filterHEAP filter Three-tier healthy filterHEPA air fresh filter Anti-acarus filtervitamin filter Active carbon filterNano photocatalyst filter Bio filterCompound air fresh filter

Accessories for Wall mounted

Filter list:

Page 46: New FCU Presentation

Wireless Wired controller Central controller

Controllers for wall mounted

Standard Optional Optional

Remark: It doesn’t need NIM when choose CCM.

Page 47: New FCU Presentation

Air Handle Unit

Page 48: New FCU Presentation

Dual Skinned Horizontal Type

Dual Skinned Vertical Type

Dual Skinned Ceiling Suspended Type

Page 49: New FCU Presentation

Standard AHU

Dual Skinned (56 Models)

Horizontal Vertical Ceiling Suspended

Models List

Page 50: New FCU Presentation

◆ Horizontal Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020W ~ MKW2-600W

◆ Vertical Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020L ~ MKW2-600L

◆ Ceiling Suspended Type Air Volume: 2,000 ~ 15,000m3/h Model: MKS020D1 ~ MKS150D1

Specification

Page 51: New FCU Presentation

Air Out Type

1 2

Ceiling suspended

V e r t ic a l

1 2

H o r iz o n t a l

3 4

Page 52: New FCU Presentation