    BA2103Messko EPT202-IM

    DNP3.0 interface description

    BA2103/00/01 Page 1 of 8 22/04/2008

    Messko EPT202-IM interfaceVendor Name: Messko GmbH

    Device Name: EPT202IM

    Highest DNP Level Supported:

    For Requests: Level 1For Responses: Level 1

    Device Function:

    Slave

    GENERAL INFORMATION:

    Maximum Data Link Frame Size (octets):

    Transmitted: 300Received: (must be 292)

    Maximum Application Fragment Size (octets):

    Transmitted: 200 (if >2048, must beconfigurable)Received: 2048 (must be > = 249)

    Maximum Data Link Re-tries:

    Unlimited

    Maximum Application Layer Re-tries:

    Unlimited

    Requires Data Link Layer Confirmation:

    Never

    Requires Application Layer Confirmation:

    When reporting Event Data ( Remote devices only)

    Publisher:Messko GmbHGablonzer Str. 25-27D-61440 Oberursel

  • 8/12/2019 Monitor de Temperatura Ba2103

    2/8

    BA2103/00/01 Page 2 of 8 22.04.2008

    Timeouts while waiting for:

    Data Link Confirm None Fixed at________ Variable Configurable*

    Complete Appl. Fragment None Fixed at________ Variable Configurable*

    Application Confirm None Fixed at 5s(1

    Variable Configurable*

    Complete Appl. Response None Fixed at________ Variable Configurable*

    Others _____________________________________________________________________*Attach explanation if Variable or Configurable was checked for any timeout1)

    If it was not possible to resend the message for more than 5s it is discarded

    Default Status Object/Variation:

    No Status objects reported

    Configurable (attach explanation)

    Default Static Object ___________

    Default Static Variation ___________

    Default Event Object ___________

    Default Event Variation ___________

    Point-by-point list attached

    Default Analog Object/Variation:

    No Analog objects reported

    Configurable (attach explanation)

    Default Static Object ______________

    Default Static Variation ______________

    Default Event Object ______________

    Default Event Variation ______________

    Point-by-point list attached

    Default Counter Object/Variation:

    No Counters reported

    Configurable (attach explanation)

    Default Static Object ___________

    Default Static Variation ___________

    Default Event Object ___________

    Default Event Variation ___________

    Point-by-point list attached

    Counters Roll Over at:

    No Counters Reported

    Configurable (attach explanation)

    16 Bits

    32 Bits

    Other Value _____________

    Point-by-point list attached

    Default Frozen Counter Object/Variation:

    No Frozen Counters reported

    Configurable (attach explanation)

    Default Static Object ___________

    Default Static Variation ___________

    Default Event Object ___________

    Default Event Variation ___________Point-by-point list attached

    Counters frozen by means of:

    Remote device time based

    Fixed time

    Configurable; range _____ to _____

    Master Request (see implementationtable for supported function codes)

    Both

    Analog Deadbands:

    Fixed

    Configuring Analog Deadbands:

    Not Applicable

    Are the updated deadband values preserved through a device reset:

    NO

    The number of multiple objects allowed in a single read request message:

    Number of multiple objects allowed: Maximum length of application frame message is thelimit.

    Ability to DISABLE/ENABLE DNP databasepoints:

    Not Applicable

    IIN 1-6 Device Trouble Bit

    Never used

  • 8/12/2019 Monitor de Temperatura Ba2103

    3/8

  • 8/12/2019 Monitor de Temperatura Ba2103

    4/8

    BA2103/00/01 Page 4 of 8 22.04.2008

    ENABLE/DISABLE Unsolicited

    Function codes 20,21 supported

    Minimum number of events and/or minimumtime before transmission of an unsolicitedmessage.

    # of events:1

    min. amount of time(msec) : 100

    Assign Class Function code supported:

    NO

    Is the Event Buffer size configurable: NO

    Configurable Per Class buffer:

    NO

    Are the updated ENABLE/DISABLEunsolicited settings saved through adevice reset:

    NO

    Are the updated Assign Class settings savedthrough a device reset:

    NO

    Supports Collision Avoidance:

    Never

    Source Address Filtering:

    Not Supported

    Supports Multi-drop communications: Yes NoOne master and multiple slaves on the line are supported because the unit ignores messages with otheraddresses than its own.

    Sends Multi-Fragment Responses: Yes No

    Supported Application Layer Function Codes

    - Direction PrimarySecondary

    o Confirm (0x00)

    o Read (0x01)

    o Write (0x02)

    o Enable Unsolicited Respones (0x14)

    o Disable Unsolicited Responses (0x15)

    o Delay Measurement (0x17)

    - Direction Secondary

    Primaryo Response (0x81)

    o Unsolicited Response (0x82)

  • 8/12/2019 Monitor de Temperatura Ba2103

    5/8

    BA2103/00/01 Page 5 of 8 22.04.2008

    Supported Objects

    OBJECT REQUEST

    (slave must parse)

    RESPONSE

    (master must parse)

    Obj Var Description FuncCodes(dec)

    Qual Codes(hex)

    Func Codes(dec)

    Qual Codes(hex)

    1 0 Binary Input - All Variations1

    (Read)06

    (No Range)

    1 1 Binary Input1(Read)

    06

    (No Range)

    129

    (Response)

    130

    (Unsol Resp)

    00

    (Start-Stop)

    30 0 Analog Input - All Variations1

    (Read)06

    (No Range)

    30 2 16-Bit Analog Input 1(Read)

    06(No Range)

    129

    (Response)130

    (Unsol Resp)

    00(Start-Stop)

    50 0 Time and Date - All Variations

    50 1 Time and Date1(Read)

    07(Count of

    Points whereRange = 1)

    129

    (Response)

    07(Count of

    Points whereRange = 1)

    50 1 Time and Date2(Write)

    07(Count of

    Points whereRange = 1)

    52 2 Time Delay Fine 129(Response)

    07

    (Count ofPoints whereRange = 1)

    60 0

    60 1 Class 0 Data1(Read)

    06(No Range)

    60 2 Class 1 Data1(Read)

    06(No Range)

    60 3 Class 2 Data1(Read)

    06(No Range)

    80 1 Internal Indications1(Read)

    00, 01129

    (Response)

    80 1 Internal Indications2

    (Write)

    00

    (index=7)

    129

    (Response)

  • 8/12/2019 Monitor de Temperatura Ba2103

    6/8

    BA2103/00/01 Page 6 of 8 22.04.2008

    Data items

    Description Index Default Static Variation

    Obj Var Desc Unit Scale Range Point Name

    Analog Input 0 30 2 16bit withStatus

    C 10 -5002500 Oil Temperature

    Analog Input 1 30 2 16bit withStatus

    C 10 -5002500 Winding 1 Temperature

    Analog Input 2 30 2 16bit withStatus

    C 10 -5002500 Winding 2 Temperature

    Analog Input 3 30 2 16bit withStatus

    C 10 -5002500 Winding 3 Temperature

    Analog Input 4 30 2 16bit withStatus

    A 0 032767 Load Current 1

    Analog Input 5 30 2 16bit withStatus

    A 0 032767 Load Current 2

    Analog Input 6 30 2 16bit withStatus

    A 0 032767 Load Current 3

    Analog Input 7 30 2 16bit withStatus

    % 0 0100 Oil Level 1

    Analog Input 8 30 2 16bit withStatus

    % 0 0100 Oil Level 2

    Analog Input 9 30 2 16bit withStatus

    C 10 -5002500 Ambient Temperature

    Analog Input 10 30 2 16bit with

    Status

    % 10 01000 Life Consumption

    Analog Input 11 30 2 16bit withStatus

    % 10 01000 Analog Input 1

    Analog Input 12 30 2 16bit withStatus

    % 10 01000 Analog Input 2

    Binary Input 0 1 1 No Status OL-Module On

    Binary Input 1 1 1 No Status CT-Module On

    Binary Input 2 1 1 No Status Winding On

    Binary Input 3 1 1 No Status Set Time

    Binary Input 4 1 1 No Status S5 active

    Binary Input 5 1 1 No Status S6 active

    Binary Input 6 1 1 No Status Lock active

    Binary Input 7 1 1 No Status Error active

    Binary Input 8 1 1 No Status Ambient Temperature On

    Binary Input 9 1 1 No Status S1 active

    Binary Input 10 1 1 No Status S2 active

  • 8/12/2019 Monitor de Temperatura Ba2103

    7/8

    BA2103/00/01 Page 7 of 8 22.04.2008

    Description Index Default Static Variation

    Obj Var Desc Unit Scale Range Point Name

    Binary Input 11 1 1 No Status S3 active

    Binary Input 12 1 1 No Status S4 active

    Binary Input 13 1 1 No Status Temperature Test Mode active

    Binary Input 15 1 1 No Status PC-Test Mode active

    Binary Input 17 1 1 No Status Winding 1 On

    Binary Input 18 1 1 No Status Winding 2 On

    Binary Input 19 1 1 No Status Winding 3 On

    Binary Input 21 1 1 No Status OL1 On

    Binary Input 22 1 1 No Status OL2 On

    Binary Input 24 1 1 No Status OL1 Max active

    Binary Input 25 1 1 No Status OL2 Min active

    Binary Input 26 1 1 No Status OL2 Max active

    Binary Input 27 1 1 No Status OL1 Min active

    Binary Input 28 1 1 No Status IM Module On

    Binary Input 29 1 1 No Status S8 active

    Binary Input 30 1 1 No Status S7 active

    Binary Input 31 1 1 No Status Oil Level Test active

    Binary Input 32 1 1 No Status Datalogger defect

    Binary Input 33 1 1 No Status Error Analog Output Oil Temp

    Binary Input 34 1 1 No Status Error Oil Temp Sensor

    Binary Input 35 1 1 No Status Error Supply Voltage

    Binary Input 36 1 1 No Status Error Analog Output Wind Temp

    Binary Input 37 1 1 No Status Error Ambient Temp Sensor

    Binary Input 40 1 1 No Status Error OL1 Sensor

    Binary Input 41 1 1 No Status Error Analog Output OL1

    Binary Input 42 1 1 No Status Error OL2 Sensor

    Binary Input 43 1 1 No Status Error Analog Output OL2

    Binary Input 44 1 1 No Status Error Analog Output WT2

    Binary Input 45 1 1 No Status Error Analog Output WT3

    Binary Input 46 1 1 No Status Error IM1 Sensor

    Binary Input 47 1 1 No Status Error IM2 Sensor

    Binary Input 49 1 1 No Status Input 1 active

    Binary Input 50 1 1 No Status Input 2 active

  • 8/12/2019 Monitor de Temperatura Ba2103

    8/8

    BA2103/00/01 Page 8 of 8 22.04.2008

    Description Index Default Static Variation

    Obj Var Desc Unit Scale

    Range Point Name

    Binary Input 51 1 1 No Status Input 3 active

    Binary Input 52 1 1 No Status Input 4 active

    Binary Input 57 1 1 No Status Error Sensor Analog Input 1

    Binary Input 58 1 1 No Status Error Sensor Analog Input 2