BA2103Messko EPT202-IM
DNP3.0 interface description
BA2103/00/01 Page 1 of 8 22/04/2008
Messko EPT202-IM interfaceVendor Name: Messko GmbH
Device Name: EPT202IM
Highest DNP Level Supported:
For Requests: Level 1For Responses: Level 1
Device Function:
Slave
GENERAL INFORMATION:
Maximum Data Link Frame Size (octets):
Transmitted: 300Received: (must be 292)
Maximum Application Fragment Size (octets):
Transmitted: 200 (if >2048, must beconfigurable)Received: 2048 (must be > = 249)
Maximum Data Link Re-tries:
Unlimited
Maximum Application Layer Re-tries:
Unlimited
Requires Data Link Layer Confirmation:
Never
Requires Application Layer Confirmation:
When reporting Event Data ( Remote devices only)
Publisher:Messko GmbHGablonzer Str. 25-27D-61440 Oberursel
-
8/12/2019 Monitor de Temperatura Ba2103
2/8
BA2103/00/01 Page 2 of 8 22.04.2008
Timeouts while waiting for:
Data Link Confirm None Fixed at________ Variable Configurable*
Complete Appl. Fragment None Fixed at________ Variable Configurable*
Application Confirm None Fixed at 5s(1
Variable Configurable*
Complete Appl. Response None Fixed at________ Variable Configurable*
Others _____________________________________________________________________*Attach explanation if Variable or Configurable was checked for any timeout1)
If it was not possible to resend the message for more than 5s it is discarded
Default Status Object/Variation:
No Status objects reported
Configurable (attach explanation)
Default Static Object ___________
Default Static Variation ___________
Default Event Object ___________
Default Event Variation ___________
Point-by-point list attached
Default Analog Object/Variation:
No Analog objects reported
Configurable (attach explanation)
Default Static Object ______________
Default Static Variation ______________
Default Event Object ______________
Default Event Variation ______________
Point-by-point list attached
Default Counter Object/Variation:
No Counters reported
Configurable (attach explanation)
Default Static Object ___________
Default Static Variation ___________
Default Event Object ___________
Default Event Variation ___________
Point-by-point list attached
Counters Roll Over at:
No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value _____________
Point-by-point list attached
Default Frozen Counter Object/Variation:
No Frozen Counters reported
Configurable (attach explanation)
Default Static Object ___________
Default Static Variation ___________
Default Event Object ___________
Default Event Variation ___________Point-by-point list attached
Counters frozen by means of:
Remote device time based
Fixed time
Configurable; range _____ to _____
Master Request (see implementationtable for supported function codes)
Both
Analog Deadbands:
Fixed
Configuring Analog Deadbands:
Not Applicable
Are the updated deadband values preserved through a device reset:
NO
The number of multiple objects allowed in a single read request message:
Number of multiple objects allowed: Maximum length of application frame message is thelimit.
Ability to DISABLE/ENABLE DNP databasepoints:
Not Applicable
IIN 1-6 Device Trouble Bit
Never used
-
8/12/2019 Monitor de Temperatura Ba2103
3/8
-
8/12/2019 Monitor de Temperatura Ba2103
4/8
BA2103/00/01 Page 4 of 8 22.04.2008
ENABLE/DISABLE Unsolicited
Function codes 20,21 supported
Minimum number of events and/or minimumtime before transmission of an unsolicitedmessage.
# of events:1
min. amount of time(msec) : 100
Assign Class Function code supported:
NO
Is the Event Buffer size configurable: NO
Configurable Per Class buffer:
NO
Are the updated ENABLE/DISABLEunsolicited settings saved through adevice reset:
NO
Are the updated Assign Class settings savedthrough a device reset:
NO
Supports Collision Avoidance:
Never
Source Address Filtering:
Not Supported
Supports Multi-drop communications: Yes NoOne master and multiple slaves on the line are supported because the unit ignores messages with otheraddresses than its own.
Sends Multi-Fragment Responses: Yes No
Supported Application Layer Function Codes
- Direction PrimarySecondary
o Confirm (0x00)
o Read (0x01)
o Write (0x02)
o Enable Unsolicited Respones (0x14)
o Disable Unsolicited Responses (0x15)
o Delay Measurement (0x17)
- Direction Secondary
Primaryo Response (0x81)
o Unsolicited Response (0x82)
-
8/12/2019 Monitor de Temperatura Ba2103
5/8
BA2103/00/01 Page 5 of 8 22.04.2008
Supported Objects
OBJECT REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description FuncCodes(dec)
Qual Codes(hex)
Func Codes(dec)
Qual Codes(hex)
1 0 Binary Input - All Variations1
(Read)06
(No Range)
1 1 Binary Input1(Read)
06
(No Range)
129
(Response)
130
(Unsol Resp)
00
(Start-Stop)
30 0 Analog Input - All Variations1
(Read)06
(No Range)
30 2 16-Bit Analog Input 1(Read)
06(No Range)
129
(Response)130
(Unsol Resp)
00(Start-Stop)
50 0 Time and Date - All Variations
50 1 Time and Date1(Read)
07(Count of
Points whereRange = 1)
129
(Response)
07(Count of
Points whereRange = 1)
50 1 Time and Date2(Write)
07(Count of
Points whereRange = 1)
52 2 Time Delay Fine 129(Response)
07
(Count ofPoints whereRange = 1)
60 0
60 1 Class 0 Data1(Read)
06(No Range)
60 2 Class 1 Data1(Read)
06(No Range)
60 3 Class 2 Data1(Read)
06(No Range)
80 1 Internal Indications1(Read)
00, 01129
(Response)
80 1 Internal Indications2
(Write)
00
(index=7)
129
(Response)
-
8/12/2019 Monitor de Temperatura Ba2103
6/8
BA2103/00/01 Page 6 of 8 22.04.2008
Data items
Description Index Default Static Variation
Obj Var Desc Unit Scale Range Point Name
Analog Input 0 30 2 16bit withStatus
C 10 -5002500 Oil Temperature
Analog Input 1 30 2 16bit withStatus
C 10 -5002500 Winding 1 Temperature
Analog Input 2 30 2 16bit withStatus
C 10 -5002500 Winding 2 Temperature
Analog Input 3 30 2 16bit withStatus
C 10 -5002500 Winding 3 Temperature
Analog Input 4 30 2 16bit withStatus
A 0 032767 Load Current 1
Analog Input 5 30 2 16bit withStatus
A 0 032767 Load Current 2
Analog Input 6 30 2 16bit withStatus
A 0 032767 Load Current 3
Analog Input 7 30 2 16bit withStatus
% 0 0100 Oil Level 1
Analog Input 8 30 2 16bit withStatus
% 0 0100 Oil Level 2
Analog Input 9 30 2 16bit withStatus
C 10 -5002500 Ambient Temperature
Analog Input 10 30 2 16bit with
Status
% 10 01000 Life Consumption
Analog Input 11 30 2 16bit withStatus
% 10 01000 Analog Input 1
Analog Input 12 30 2 16bit withStatus
% 10 01000 Analog Input 2
Binary Input 0 1 1 No Status OL-Module On
Binary Input 1 1 1 No Status CT-Module On
Binary Input 2 1 1 No Status Winding On
Binary Input 3 1 1 No Status Set Time
Binary Input 4 1 1 No Status S5 active
Binary Input 5 1 1 No Status S6 active
Binary Input 6 1 1 No Status Lock active
Binary Input 7 1 1 No Status Error active
Binary Input 8 1 1 No Status Ambient Temperature On
Binary Input 9 1 1 No Status S1 active
Binary Input 10 1 1 No Status S2 active
-
8/12/2019 Monitor de Temperatura Ba2103
7/8
BA2103/00/01 Page 7 of 8 22.04.2008
Description Index Default Static Variation
Obj Var Desc Unit Scale Range Point Name
Binary Input 11 1 1 No Status S3 active
Binary Input 12 1 1 No Status S4 active
Binary Input 13 1 1 No Status Temperature Test Mode active
Binary Input 15 1 1 No Status PC-Test Mode active
Binary Input 17 1 1 No Status Winding 1 On
Binary Input 18 1 1 No Status Winding 2 On
Binary Input 19 1 1 No Status Winding 3 On
Binary Input 21 1 1 No Status OL1 On
Binary Input 22 1 1 No Status OL2 On
Binary Input 24 1 1 No Status OL1 Max active
Binary Input 25 1 1 No Status OL2 Min active
Binary Input 26 1 1 No Status OL2 Max active
Binary Input 27 1 1 No Status OL1 Min active
Binary Input 28 1 1 No Status IM Module On
Binary Input 29 1 1 No Status S8 active
Binary Input 30 1 1 No Status S7 active
Binary Input 31 1 1 No Status Oil Level Test active
Binary Input 32 1 1 No Status Datalogger defect
Binary Input 33 1 1 No Status Error Analog Output Oil Temp
Binary Input 34 1 1 No Status Error Oil Temp Sensor
Binary Input 35 1 1 No Status Error Supply Voltage
Binary Input 36 1 1 No Status Error Analog Output Wind Temp
Binary Input 37 1 1 No Status Error Ambient Temp Sensor
Binary Input 40 1 1 No Status Error OL1 Sensor
Binary Input 41 1 1 No Status Error Analog Output OL1
Binary Input 42 1 1 No Status Error OL2 Sensor
Binary Input 43 1 1 No Status Error Analog Output OL2
Binary Input 44 1 1 No Status Error Analog Output WT2
Binary Input 45 1 1 No Status Error Analog Output WT3
Binary Input 46 1 1 No Status Error IM1 Sensor
Binary Input 47 1 1 No Status Error IM2 Sensor
Binary Input 49 1 1 No Status Input 1 active
Binary Input 50 1 1 No Status Input 2 active
-
8/12/2019 Monitor de Temperatura Ba2103
8/8
BA2103/00/01 Page 8 of 8 22.04.2008
Description Index Default Static Variation
Obj Var Desc Unit Scale
Range Point Name
Binary Input 51 1 1 No Status Input 3 active
Binary Input 52 1 1 No Status Input 4 active
Binary Input 57 1 1 No Status Error Sensor Analog Input 1
Binary Input 58 1 1 No Status Error Sensor Analog Input 2