Llenado de Tuberia

download Llenado de Tuberia

of 5

description

calcular el porcentaje de llenado de tubería para cables electricos

Transcript of Llenado de Tuberia

Hoja1# AWGdiametro cable (sobre el aislamiento) [mm]numero de circuitos (cables)limite de llenadoarea cables mm^2diam mnimo tubera requerida [mm]diam mnimo tubera requerida [in]diam mnimo tubera requerida [in] (En una sola Formula)Monopolar1 x 4/016.10440%814.3350.912.002.00Monopolar1 x 2/013.41340%423.7136.721.451.45Monopolar1 x 1/012.28540%592.1843.421.711.71Monopolar1 x 123.151540%116.9019.290.760.76Monopolar1 x 85.19640%126.9320.100.790.79Multiconductor4 x 232.25153%816.7644.301.741.74Multiconductor4 x 424.05153%454.2833.041.301.30Multiconductor4 x 618.78153%277.0025.801.021.02Multiconductor4 x 816.51153%214.0822.680.890.89Multiconductor4 x 1012.65153%125.6817.380.680.68Multiconductor3 x 129.60340%217.1526.291.041.04Multiconductor1 x 7 x 1412.66153%125.8817.390.680.68Multiconductor1 x 7 x 1214.85153%173.2020.400.80Multiconductor1 x 4T x 1614.45153%163.9919.850.78Multiconductor1 x 12T x 1625.35153%504.7134.821.37Multiconductor3 X 815.10153%179.0820.740.82CALCULO PORCENTAJE LLENADO DE TUBERIACABLESTUBERIAcalculo caida de tension trifasicoarea cable42.9084960375area tubo285.0229569923porcentaje llendo45.16%raiz 31.7320508076caida de tensionlongitud1902.20%dia exterior7.3914valor19.05in22.206r0.623cablecantidad cable3pulg0.75x0.1482 awgmm19.05fp0.9area cable0cables por fase1nivel tension208dia exterior0cantidad cable0area cable0dia exterior0cantidad cable0

Hoja2# conductoresFACTOR4-60.807-90.7010-200.5021-300.4531-400.4041 y ms0.35Correccion de ampacidad por agrupamiento de conductores1-34-67-910-2021-3031-4041 y ms12 awg252017.512.511.25108.7510 awg352824.517.515.751412.25

Hoja3