Hoja Coordinacion Aislamiento

8
24.0 19.6 Urp(p-e) en KV = 19.40 Urp(p-p) en KV = 33.60 19.40 Kv 33.60 Kv Ue2 en p.u = 2.9 Ue2 en p.u = 2.5 2.6 Up2 en p.u = 4.35 Up2 en p.u = 3.75 4.34 Uet en p.u = 3.38 Uet en p.u = 2.88 3.00 Upt en p.u = 5.008 Upt en p.u = 4.258 4.995 Uet en Kv = 66.136 Uet en Kv = 56.338 58.788 98 12 83 43 9 88 Overvolteges originating from station 1 Energization and re-energization Ue2 en p.u = Up2 en p.u = Uet en p.u = Upt en p.u = Uet en Kv = U K STEP 1: Determination of the representative overvoltages (Urp) Kv phase-to-phase Phase-to-phase : Urp(p-p) = Us = Power-frecuency Voltage Temporary overvoltages Earth faults Load rejection 1.4 Kv (crest) Urp(p-e) en KV = 19.40 Earth-fault factor: k = 1.4 Max. Overvoltage en p.u = 1.0 p.u = Resulting representative overvolteges Phase-to-earth : Urp(p-e) = Slow-front overvoltages Overvolteges originating from station 2 Re-energization Capacitor switching Upt en Kv = 98.127 Upt en Kv = 83.43 97.88 No Yes Phase-to-earth : Urp = Ups = 45 Kv Urp(p-e) = 45 Kv Urp(p-e) = 45 Kv Phase-to-phase : Urp = 2Ups = 90 Kv Urp(p-p) = 97.88 Kv Urp(p-p) = 90 Kv 54 45 Upl en Kv = For other equipment With or without capacitor switching Capacitor switching at station 2 Uet > Ups Upt > 2 Ups For Line entrance equipment Arresters at line entrance and near transformers : Ups en Kv = Upt en Kv = Fast-front overvoltages Evaluated in step 2

description

Hoja coordinacion de aislamiento

Transcript of Hoja Coordinacion Aislamiento

  • 24.019.6

    Urp(p-e) en KV = 19.40Urp(p-p) en KV = 33.60

    19.40 Kv 33.60 Kv

    Ue2 en p.u = 2.9 Ue2 en p.u = 2.5 2.6Up2 en p.u = 4.35 Up2 en p.u = 3.75 4.34Uet en p.u = 3.38 Uet en p.u = 2.88 3.00Upt en p.u = 5.008 Upt en p.u = 4.258 4.995Uet en Kv = 66.136 Uet en Kv = 56.338 58.788U K 98 12 U K 83 43 9 88

    Overvolteges originating from station 1

    Energization and re-energization

    Ue2 en p.u =Up2 en p.u =Uet en p.u =Upt en p.u =Uet en Kv =U K

    STEP 1: Determination of the representative overvoltages (Urp)

    Kv phase-to-phase

    Phase-to-phase : Urp(p-p) =

    Us =Power-frecuency Voltage

    Temporary overvoltages

    Earth faults

    Load rejection 1.4

    Kv (crest)

    Urp(p-e) en KV = 19.40Earth-fault factor: k = 1.4

    Max. Overvoltage en p.u =

    1.0 p.u =

    Resulting representative overvoltegesPhase-to-earth : Urp(p-e) =

    Slow-front overvoltages

    Overvolteges originating from station 2

    Re-energization Capacitorswitching

    Upt en Kv = 98.127 Upt en Kv = 83.43 97.88

    No YesPhase-to-earth : Urp = Ups = 45 Kv Urp(p-e) = 45 Kv Urp(p-e) = 45 KvPhase-to-phase : Urp = 2Ups = 90 Kv Urp(p-p) = 97.88 Kv Urp(p-p) = 90 Kv

    5445 Upl en Kv =

    For other equipment

    With or without capacitor switching Capacitor switching at station 2Uet > Ups Upt > 2 Ups

    For Line entrance equipment

    Arresters at line entrance and near transformers : Ups en Kv =

    Upt en Kv =

    Fast-front overvoltages Evaluated in step 2

  • a) Ups/Ue2 = 0.79 a) 2Ups/Up2 = 1.06 1) Ups/Ue2 = 0.92 1) 2Ups/Up2 = 1.225b) Ups/Ue2 = 0.92 b) 2Ups/Up2 = 1.22 2) Ups/Ue2 = 0.88 2) 2Ups/Up2 = 1.06

    a) Kd = 1.08 a) Kd = 1.00 0 1) Kcd = 0.00b) Kd = 0.00 b) Kd = 0.00 1.06 2) Kcd = 1.00

    Kcd = 1.08 1.080.00

    Ucw = Kcd x Urp Ucw = Kcd x Urp 48.38 1) Ucw = 0.00Ucw (KV)= 48.38 Ucw (KV)= 90 0.00 2) Ucw = 97.88

    a) From reenergization at station 2 1) With capacitor switching at station 2b) From capacitor swithing at station 2 2) Without capacitor switching at station 2

    1) kcd =2) kcd =

    1) Kcd =2) Kcd =

    2) Ucw =

    Retained value :

    1) Ucw =

    Retained value :

    Phase to phase

    1Temporary overvoltage

    Phase to earth en Kv : Ucw = Kc x Urp =Phase to phase en Kv: Ucw = Kc x Urp =

    Kc Factor =

    Phase to phase Phase to earthPhase to earth

    19.4033.6

    STEP 2: Determination of the coordination withstand voltages (Ucw)

    Slow-front overvoltage Deterministic metod used = Kcd factor

    Line entrance equipement (external insulation only) Other equipment

    Parameter A = 900Span length Lsp = 100 mOutage rate Rkm = 0.03 Km/yearAcceptable failure rate Ra = 0.0067 Years

    Arrester Lightning protection level : Upl = 54 KvMax. Separation from internal insulation: L = 8 m La = 223.33 mMax. Separation from external insulation: L = 15 m

    Internal insulation : Ucw 76.27 KvExternal Insulation : Ucw 95.75 Kv

    n = 1n = Numero de lineas conectadas a la Subestacion

    performance requiredData from experience

    Fast-front overvoltages Simplified statical method used

    aspplcw LL

    LnAUU *

  • Internal insulation : Ks =External insulation : Ks =

    Internal insulation : Urw = Ucw x KsExternal insulation : Urw = Ucw x Ks x Ka

    Kv Kv Kv Kv

    K KI l i

    Internal Insulation

    ExternalI l i

    22.31Internal

    Insulation38.64

    External

    Insulation

    Phase to earth Phase to phase Phase to earth Phase to phase

    Line entrance

    I l i

    87.71External Insulation

    External Insulation

    87.71

    Temporary overvoltage withstand Switching impulse withstand Lighting impulse withstand

    ExternalI l i

    Internal Insulation

    External

    equipment

    Phase to earth Phase to phase

    Line entranceequipment

    Internal

    Atmospheric correction factor Altitude H = 3570 m

    Step 3 : Determination of the required withstand voltages (Urw)

    Safety factor 1.151.05

    Power - frequency withstand Switching impulse withstand Lighting impulse withstand

    Phase to earth Phase to phase Phase to earth Phase to phase Phase to earth Phase to phase

    m = 1

    Ka = 1.5497

    m = 0.5

    Ka = 1.2449

    8 1 146 44

    m = 1

    Ka = 1.550

    m = 1

    Ka = 1.5497

    Required withstand voltages

    Kv Kvkv kv kv kv

    1) kv 1) kv2) kv 2) kv

    1) With capacitor switching at station 21) kv 1) kv 2) Without capacitor switching at station 22) kv 2) kv

    m =H =Ka =

    3570

    25.36 43.92

    InternalInsulation

    ExternalInsulation

    55.630.00

    Otherequipment

    78.710.00

    Insulation Insulation Insulation

    Insulation

    Otherequipment

    Internal

    155.80

    0.00112.56External

    155.80Insulation

    1.4197

    78.71 146.44

    0.8

    Insulation0.00

    159.27

    8150.

    Hm

    a eK

  • External insulation : External insulation :- phase to earth 0.6 + Urw/8500 - phase to earth 1.3- phase to phase 0.6 + Urw/12700 - phase to phase 1.05 + Urw/9000

    Internal insulation : Internal insulation :- phase to earth 0.5 - phase to earth 1.1- phase to phase 0.5 - phase to phase 1.1

    - phase to earth - phase to earth - phase to earth - phase to earthKv 1) Kv Kv 1) Kv

    2) Kv 2) Kv- phase to phase - phase to phase

    Kv - phase to phase Kv - phase to phase1) Kv 1) Kv2) Kv 2) Kv

    - phase to earth - phase to earth1) Kv 1) Kv

    Step 4 : Conversion to withstand voltages normalized for range I

    Conversion of switching impulse withstandVoltages to lightning impulse

    withstand voltagesConversion of switching impulse withstandVoltages to short-duration power.frequency

    withstand voltagesConversion factorsConversion factors

    Line entranceequipment

    Internal Insulation

    otherequipment

    External insulation External Insulation

    61.19

    otherequipment

    0.0097.56

    External Insulation47.96 102.33 102.33

    Internal Insulation27.82

    0.00 0.00156.15

    0.00170.05

    Line entranceequipment

    47.96

    89.55

    External insulation

    1) Kv 1) Kv2) Kv 2) Kv- phase to phase - phase to phase1) Kv 1) Kv2) Kv 2) Kv

    0.00

    0.0056.28 123.82

    0.00

    0.00

    61.1927.82

  • Frecuencia Fase - TierraIndustrial Fase - Fase

    Impulso de Fase - TierraManiobra Fase - FaseImpulso Fase - Tierra

    Atmosferico Fase - Fase

    * 70 kV Para tensiones de soportabilidad de corta duracion a frecuencia industrial * 170 kV Para tensiones de soportabilidad al impulso atmosferico

    Para el aislamiento de equipos en S.U. 22.9 kV se selecciona las siguientes tensiones de soportabilidad

    RESUMEN DE LAS TENSIONES DE SOPORTABILIDAD REQUERIDAS

    Urw(s) Urw22.31 0.00

    de maniobra y rayo Urw(s)25.36

    Urw Urw(s)

    155.80156.15155.80

    KV r.m.s paraFrecuencia industrial

    Kv Pico para impulsosAislamiento externo

    Equipos entradade linea Otros equipos

    78.71146.4443.92

    47.9689.55

    102.33

    56.2897.560.00

    87.71 0.00112.5638.64

    155.80

    43.92159.27

    Aislamiento interno

    (1) (1) (1)0.00

    Urw25.36 0.00

    87.71 123.82 De acuerdo a la tabla 2 de la Norma IEC 60071-1 se selecciona valores normalizados de aislamiento

    que cubriran cualquier aislamiento externo e interno fase-fase y fase-tierra.

    155.80

    12345