VIGAS CONTINUAS DE CIMENTACION1. Colocar dimensiones de la viga continua
20,0 cm
3 1/2 '' As Positivo 1,49 cm20,0 cm
2 1/2" Para evitar el pandeo del estribo2,58 cm
40,0 cm
As Negativo 1,59 cm3 1/2 ' ' 120,0 cm
2,58 cm
2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.REFUERZO POSITIVO REFUERZO NEGATIVO ACERO MINIMO:
f`c = 210,00 Kg/cm2 f`c = 210,00 Kg/cm2 min = 0,0024
fy = 4200,00 Kg/cm2 fy = 4200,00 Kg/cm2 As min = 2,58 cmb = 120,00 cm b = 20,00 cm barra = 3/4 ''
h = 60,00 cm h = 60,00 cm As = 2,850 cm
barra = 1/2 '' barra = 1/2 '' Tomamos 1 3/4 ''
estribo = 3/8 '' estribo = 3/8 '' ACERO MAXIMOrecub. = 5,00 cm recub. = 7,50 cm max = 0,0163
d = 53,41 cm d = 50,91 cm As max = 17,38 cmM = 3,00 Tn-m M = 3,00 Tn-m barra = 3/4 ''
a = 0,292 cm a = 1,868 cm As = 2,850 cm
As = 1,49 cm As = 1,59 cm Tomamos 7 3/4 ''
3. Aceros Negativos y Positivos Finales
ACERO POSITIVO ACERO NEGATIVOAs Positivo 2,58 cm As Negativo 2,58 cm 0,43
barra = 1/2 '' barra = 1/2 ''
As = 1,267 cm As = 1,267 cm
Tomamos 3 1/2 '' Tomamos 3 1/2 ''
DISEO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION
Verificar As min y As max
Verificar As min y As max
ACERO LONGITUDINAL
-
7/24/2019 Diseovigadecimentacion Carmen
2/2
sadm Suelo = 18,000 Tn/m REFUERZO NEGATIVOs diseo = 27,000 Tn/m f`c = 210,00 Kg/cm2
Tomando B = 1,20 m 3/8 '' @ 0,12 fy = 4200,00 Kg/cm2Mom. Neg = 4,05 Tn-m b = 120,00 cm
20,0 cm h = 40,00 cm
barra = 1/2 ''
20,0 cm 1/2 '' @ 0,39 estribo = 3/8 ''recub. = 5,00 cm
50,0 cm d = 33,41 cm
M = 4,05 Tn-m
40,0 cm a = 0,635 cm
As = 3,24 cm120,0 cm barra = 1/2 ''
As = 1,267 cm
32,40 Tn/m @ = 39,00
Vu = 0,050 Tn A cara de columna .Vc = Vud =
Wu = 3,33 Tn/m 24,217 Tn > -0,980 Tn Ok
recub. = 7,50 cm
barra = 1/2 ''
estribo = 3/8 ''
b = 120,00 cm
d = 30,91 cm
REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTOSe colocar refuerzo Transversal por confinamiento a una distancia "2d"medida desde la cara del apoyo.
2d = 1,018 m
estribo = 3/8 ''La separacion de los estribos debe ser:
S d/4 = 12,73 cm S = 12,00 cm 3/8 '' @ 0,12
S 30,00 cm
REFUERZO FUERA DE LA ZONA DE CONFINAMIENTOLa separacion de los estribos debe ser:
S = 25,00 cm 3/8 '' @ 0,25
DISEO DE REFUERZO TRANSVERSAL
VERIFICACION POR CORTANTE
ACERO TRANSVERSAL