Detector Industrial de Metales

106
THS – FI022GB2K8v3 i Detector Industrial de Metales THS Número de Serie: . ................... Versión del Programa: THSV3.390 ALMV1060 Rev.: FI 022 GB 2K8 v3 Fecha: 2004-10-26

Transcript of Detector Industrial de Metales

Page 1: Detector Industrial de Metales

THS – FI022GB2K8v3 i

Detector Industrial de Metales THS

Número de Serie: . ...................

Versión del Programa: THSV3.390 ALMV1060 Rev.: FI 022 GB 2K8 v3 Fecha: 2004-10-26

Page 2: Detector Industrial de Metales

II- INSTALACIÓN

Instrucciones ESTE MANUAL HA DE SER LEIDO POR LAS SIGUIENTES PERSONAS:

- EL DUEÑO - EL OPERADOR - EL TÉCNICO DE MANTENIMIENTO

Lee este manual antes de instalar, operar o llevar a cabo el mantenimiento del dispositivo. Guarda el manual en un lugar seguro y en perfectas condiciones para consultas en el futuro. Este manual debe acompañar al dispositivo descrito ahí en caso cambie de dueño, o el dispositivo se descom-ponga. • Follow the instructions contained in this manual for all

operations relating to installation, use and maintenance of the device. CEIA cannot be held responsible for any damage resulting from procedures which are not expressly indicated in this manual, or from any lack of attention, either partial or total, of the procedures described therein .

• Whenever there is any suggestion that the level of pro-tection has been reduced, the device should be taken out of service and secured against any possibility of unintentional use, and authorised service technicians should be called. The level of protection is considered to have been reduced when: - the device shows visible signs of wear and tear; - the device does not operate correctly; - the device has been stored for long periods in suboptimal conditions; - the device has suffered severe stress during transport; - the device has come into contact with liquids.

• The final user is responsible for selecting the appropriate sensitivity for their application. After this selection has been made, and programming has been adjusted accordingly, it is also the final user's responsibility to verify calibration using the test object(s) appropriate to the level of security selected. Additionally, this test should be carried out peri-odically to insure no changes have occurred in the equipment.

• Handle the device with care and without excessive force during installation, use and maintenance.

• After installation the device should be stable, and not subject to vibration or accidental movement. All con-necting cables should be properly fastened down, in order to avoid knocks and accidental damage and to obtain optimum performance.

• Position the device as far as possible from sources of electromagnetic interference, such as transformers or motors.

• Before connecting the device to the power supply, ensure that the power supply voltage corresponds to that indicated on the plate affixed to the device. The device should be connected to the mains voltage only after all connections required for full installation have been carried out.

• The device must be connected to a power supply circuit fitted with a switch or other device which allows the power to be cut off.

• Ensure that replacement fuses are of the correct rating and of the prescribed type. Makeshift fuses and short-circuiting of the fuse boards are strictly forbidden.

• If the device is to be powered via an external autotrans-former to regulate the voltage, ensure that the common terminal of the autotransformer is connected to the neutral of the power-supply circuit.

• The power-supply plug must only be inserted into a socket fitted with an earth/ground connection. Any break in the safety conductor, either inside or outside the device, or disconnection of the earth/ground safety terminal, will render the device dangerous. Intentional cutting or disconnection is strictly forbidden.

• To avoid damage due to lightning, disconnect the power-supply cable during storms.

• This device contains electrical and electronic components, and may therefore be susceptible to fire. Do not install in explosive atmosphere or in contact with inflammable material, Do not use water or foam in the case of fire when the device is powered up.

• The device must be disconnected from all power sources before undergoing any maintenance or cleaning, and before being moved.

• Do not wash the device with liquid detergents or chemical sub-stances. Any cleaning should be done using a slightly-damp, non-abrasive cloth.

• Read the chapter on “Maintenance” carefully before calling the service centre. Whatever the problem, only specialised service personnel authorised to work with CEIA equipment should be called.

• Any damaged parts of the device should be replaced with original components only.

• Any maintenance or repair of the device while open and energised should be avoided, and in any case should only be carried out by trained personnel who are fully aware of the risks which the operation entails, following the instructions given in the “Maintenance” section.

• Disposal of parts with environmental impact: follow the regulations in force in the country where the device is being used (refer to the “Maintenance” section).

SYMBOLS The equipment is marked with this symbol wherever the user should refer to this manual in order to avoid possible damage. The same symbol appears in the manual at points where warnings or particularly important instructions, essential for safe, correct operation of the device, are given. The equipment is marked with this symbol in the areas where there is dangerous voltage. Only trained maintenance personnel should carry out work in these areas.

Warranty conditions The Warranty on all CEIA equipment relates to goods delivered from our factory, under our general and specific conditions of sale.

Page 3: Detector Industrial de Metales

THS – FI022GB2K8v3 iii

Contents INSTRUCTIONS ......................................................................................................................................................................................................................II SYMBOLS ...............................................................................................................................................................................................................................II WARRANTY CONDITIONS .....................................................................................................................................................................................................II CONTENTS ............................................................................................................................................................................................................................III DESCRIPTION.........................................................................................................................................................................................................................1 GENERAL INFORMATION ......................................................................................................................................................................................................1 POWER-SUPPLY AND CONTROL UNIT ................................................................................................................................................................................3

Control Power Box ............................................................................................................................................................................................................3 Conveyor Control System .................................................................................................................................................................................................4

METAL DETECTOR ................................................................................................................................................................................................................5 Models available ...............................................................................................................................................................................................................5 Options .............................................................................................................................................................................................................................9

THS-FB Conveyor Belt ..............................................................................................................................................................................................9 Features .............................................................................................................................................................................................................9 THS-FB conveyor belt options ..........................................................................................................................................................................10

Other optionals for THS metal detectors..................................................................................................................................................................11 THS metal detector accessories ..............................................................................................................................................................................12

TECHNICAL CHARACTERISTICS ........................................................................................................................................................................................13 INSTALLATION.....................................................................................................................................................................................................................15 GUIDE TO THE APPLICABLE INSTALLATION OPERATIONS ............................................................................................................................................16

General guidelines for mechanical installation ................................................................................................................................................................16 GENERAL GUIDELINES FOR ELECTRICAL INSTALLATION..............................................................................................................................................17 INSTALLATION OF A CEIA THS-FB INTEGRATED SYSTEM WITH CONVEYOR BELT.....................................................................................................19

Mechanical installation of THS-FB integrated system with conveyor belt........................................................................................................................19 Positioning the conveyor belt ...................................................................................................................................................................................19 Ejector: mounting the safety shield ..........................................................................................................................................................................19 Assembling the buzzer/flasher.................................................................................................................................................................................19 Adjusting the height of the belt.................................................................................................................................................................................19

ELECTRICAL INSTALLATION - GENERAL NOTES .............................................................................................................................................................20 Connecting to the mains power supply ...........................................................................................................................................................................20

Connection to the ground ........................................................................................................................................................................................20 Control Power Box...................................................................................................................................................................................................20 Conveyor Control System ........................................................................................................................................................................................20 Selection of the power supply voltage for the metal detector only - Control Power Box Power Supply Unit.............................................................21

CONNECTION OF THE COMPRESSED AIR SUPPLY.........................................................................................................................................................21 NON-INTEGRATED THS SYSTEM SUPPLIED WITHOUT CONVEYOR BELT: DETAILED CONSTRUCTION NOTES AND SELECTION OF OPERATING PARAMETERS ................................................................................................................................................................................................22

Mechanical Installation....................................................................................................................................................................................................22 Controls ...................................................................................................................................................................................................................22 Mechanical installation of the metal detector ...........................................................................................................................................................22 Mechanical installation of the power supply unit ......................................................................................................................................................22 Mechanical installation of the THS/G probe.............................................................................................................................................................22

Proximity limits around the THS/G probe..........................................................................................................................................................22 THS/G : mounting the power supply unit ..........................................................................................................................................................23

Conveyor belt...........................................................................................................................................................................................................24 Inserting the conveyor belt on the THS/A model......................................................................................................................................................26

Transit speed ..................................................................................................................................................................................................................27 Accessory devices ..........................................................................................................................................................................................................29

Photocell – General rules ........................................................................................................................................................................................29 Photocell self-diagnosis ....................................................................................................................................................................................29

Ejector – General rules ............................................................................................................................................................................................29 THS/M – Specific instructions for ejector .................................................................................................................................................................30

Applications at high speed (belt speeds greater than 60 m/min).....................................................................................................................................31 Programming used in a few common types of installation...............................................................................................................................................31 Mechanical installation of a bar code reader...................................................................................................................................................................32

Safety precautions ...................................................................................................................................................................................................32 Barcode reader kit ...................................................................................................................................................................................................32 Distance between the reader and the metal detector probe and distance between packs.......................................................................................33 Position of the reader and the label in transit...........................................................................................................................................................33 Reading features .....................................................................................................................................................................................................34

Step-Ladder mode............................................................................................................................................................................................34 Picket-Fence mode...........................................................................................................................................................................................34

Kit installation procedure .........................................................................................................................................................................................35 ELECTRICAL INSTALLATION: DETAILED NOTES ..............................................................................................................................................................36

ALM card electrical connections .....................................................................................................................................................................................39 Conveyor Control System: Power-supply and motor connections ...................................................................................................................................41

MDT card.................................................................................................................................................................................................................41 MDL card ( ATTENTION: 230V 1~ only! ) ..............................................................................................................................................................42

Operation of the relays (J15 and J19 connectors) ..........................................................................................................................................................43 Ejector relay (Eject relay):........................................................................................................................................................................................43 Alarm relay ..............................................................................................................................................................................................................43 Malfunction relay (Fault relay)..................................................................................................................................................................................43 Upstream belt authorisation relay (Preceding conveyor relay) .................................................................................................................................43 Auxiliary relay for signalling when periodic test is due (TEST LAMP relay)..............................................................................................................43

Timing.............................................................................................................................................................................................................................43 Belt blocking with manual alarm reset (EM=B) ........................................................................................................................................................43

Conveyor Control System power supply unit ....................................................................................................................................................43 Control Power Box power supply unit ...............................................................................................................................................................43

Belt blocking with photocell synchronisation and manual alarm reset (EM=SB) ......................................................................................................43 Conveyor Control System power supply unit ....................................................................................................................................................44 Control Power Box power supply unit ...............................................................................................................................................................44

Automatic ejection with alarm synchronisation (EM=F)............................................................................................................................................44 Automatic ejection with photocell synchronisation (EM=S) ......................................................................................................................................45

Serial line connection (J3 and J4 connectors).................................................................................................................................................................46 Inputs..............................................................................................................................................................................................................................47

Bar-code reader.......................................................................................................................................................................................................47 Downstream belt authorisation (Following conveyor - Conveyor Control System only) ............................................................................................47 Photocell..................................................................................................................................................................................................................47

Page 4: Detector Industrial de Metales

II- INSTALLAZIONE

Ejection confirmation (Eject confirmation)................................................................................................................................................................47 Container full (Full bin).............................................................................................................................................................................................47 Impulse encoder (Encoder)......................................................................................................................................................................................47 Alarm reset (Reset)..................................................................................................................................................................................................47 Inhibition ..................................................................................................................................................................................................................47 Air pressure sensor..................................................................................................................................................................................................47 Container absent (Bin absent) .................................................................................................................................................................................47

OPERATING INSTRUCTIONS ..............................................................................................................................................................................................48 LIST OF PRELIMINARY CHECKS.........................................................................................................................................................................................48 OPERATIONS DURING USE AND AREAS OF COMPETENCE...........................................................................................................................................48 CONTROLS AND INDICATORS............................................................................................................................................................................................49

Power switch...................................................................................................................................................................................................................49 Control panel of the probe/electronics unit......................................................................................................................................................................49

Acoustical indicators ................................................................................................................................................................................................49 Controls ...................................................................................................................................................................................................................50

Conveyor Control System power supply unit control panel .............................................................................................................................................50 Visible/audible alarm signalling device............................................................................................................................................................................51

SWITCHING ON THE METAL DETECTOR...........................................................................................................................................................................51 Checking the safety features ..........................................................................................................................................................................................51 Signals at power-up ........................................................................................................................................................................................................52

SIGNALS GIVEN DURING USE ............................................................................................................................................................................................52 Indication of the received signal......................................................................................................................................................................................52 Checking for environmental electromagnetic interference...............................................................................................................................................53 Display Messages...........................................................................................................................................................................................................53

DISPLAY OF THE STATUS OF THE METAL DETECTOR....................................................................................................................................................54 USE OF THE CONVEYOR BELT ..........................................................................................................................................................................................54

Starting/stopping the conveyor belt .................................................................................................................................................................................54 Adjustment of the belt speed ..........................................................................................................................................................................................54 Emergency button...........................................................................................................................................................................................................55 Automatic stop ................................................................................................................................................................................................................55

ALARM RESET......................................................................................................................................................................................................................55 AUTOMATIC OPERATION USING A BAR-CODE READER .................................................................................................................................................55 PHOTOCELL SELF-DIAGNOSIS...........................................................................................................................................................................................56 PROGRAMMING THE METAL DETECTOR ACCORDING TO THE KIND OF PRODUCT....................................................................................................56

Procedure for minimising the "product effect" ..........................................................................................................................................................56 ANALYSIS MODE SELECTION CRITERIA ...........................................................................................................................................................................58 SENSITIVITY CHECK WITH REFERENCE SAMPLE ...........................................................................................................................................................59

Test using a sample defined by the customer.................................................................................................................................................................59 Test using a CEIA sample ..............................................................................................................................................................................................59

Periodic test management .......................................................................................................................................................................................59 Test procedure ........................................................................................................................................................................................................59

PROGRAMMING...................................................................................................................................................................................................................61 GENERAL POINTS ON PROGRAMMING.............................................................................................................................................................................61 PROGRAMMING INSTRUCTION ..........................................................................................................................................................................................63

Products menu................................................................................................................................................................................................................63 Autolearn menu ..............................................................................................................................................................................................................64 Detection menu...............................................................................................................................................................................................................65 Ejection menu .................................................................................................................................................................................................................66

Ejection time menu ..................................................................................................................................................................................................67 Counters menu ...............................................................................................................................................................................................................68 Barcode reader menu .....................................................................................................................................................................................................68 THS Configuration menu.................................................................................................................................................................................................70

Date settings menu..................................................................................................................................................................................................72 Change Password menu..........................................................................................................................................................................................73

ALM Configuration menu ................................................................................................................................................................................................73 I/O Status menu..............................................................................................................................................................................................................77 MD Test menu ................................................................................................................................................................................................................77

Print menu ...............................................................................................................................................................................................................78 Print report menu.....................................................................................................................................................................................................79

Quality Control menu (Q.C.Report) .................................................................................................................................................................................80 Test Sensitivity menu (Test sensitiv.).......................................................................................................................................................................80

Commands accessible only in Remote Programming .....................................................................................................................................................81 REMOTE PROGRAMMING VIA SERIAL LINK......................................................................................................................................................................82

Communication parameter settings: ...............................................................................................................................................................................82 Entering remote programming ........................................................................................................................................................................................82

Connecting to a metal detector (via RS 232) ...........................................................................................................................................................82 Long-distance connection to a single metal detector (via RS 485) ..........................................................................................................................82 Network connection (via RS 485).............................................................................................................................................................................82 Connecting to a metal detector in a network............................................................................................................................................................83 3.13.3 - Displaying a parameter setting ...................................................................................................................................................................83 3.13.4 - Changing a parameter setting.....................................................................................................................................................................83 3.13.5 - Executing a function ...................................................................................................................................................................................83

MAINTENANCE.....................................................................................................................................................................................................................84 PERIODIC MAINTENANCE...................................................................................................................................................................................................84 SELF-DIAGNOSIS.................................................................................................................................................................................................................85 STORAGE .............................................................................................................................................................................................................................86 TRANSPORT AND MOVEMENT OF THE CONVEYOR BELT ..............................................................................................................................................86 ADJUSTMENT OF CONVEYOR BELT TENSION .................................................................................................................................................................86

Replacing the belt ...........................................................................................................................................................................................................87 DISPOSAL OF THE DEVICE AND OF CONSUMABLES WITH ENVIRONMENTAL IMPACT ..............................................................................................87 FUSES...................................................................................................................................................................................................................................87 TROUBLESHOOTING ...........................................................................................................................................................................................................87

Self-resetting protections .........................................................................................................................................................................................87 Replacing Card SCD.......................................................................................................................................................................................................89

Procedure ................................................................................................................................................................................................................89 CHECKING ENVIRONMENTAL ELECTROMAGNETIC INTERFERENCE............................................................................................................................90 APPENDICES........................................................................................................................................................................................................................91 DECLARATION OF CONFORMITY CE .................................................................................................................................................................................91 SPARE PARTS, OPTIONS AND ACCESSORIES.................................................................................................................................................................92

Ordering spare parts .......................................................................................................................................................................................................92 THS standard model / THS/3F........................................................................................................................................................................................92 THS /A ............................................................................................................................................................................................................................92

Page 5: Detector Industrial de Metales

THS – FI022GB2K8v3 v

THS/SL ...........................................................................................................................................................................................................................93 THS/MN..........................................................................................................................................................................................................................93 THS/PH...........................................................................................................................................................................................................................94 THS/G.............................................................................................................................................................................................................................95 THS-FB...........................................................................................................................................................................................................................95 THS Accessories - Test pieces.......................................................................................................................................................................................99 THS Accessories - MD CAD - 27185 ............................................................................................................................................................................100

CEIA reserves the right to make changes, at any moment and without notice, to the models (including programming), their accessories and optionals, to the prices and conditions of sale.

Page 6: Detector Industrial de Metales
Page 7: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I -DESCRIPCIÓN 1

DESCRIPCIÓN

Información General

El THS es un detector de metales extremadamente compacto con una sensibilidad muy alta, controlada por un microprocesador y diseñada para uso industrial. El disposotivo contiene:

el explorador del Detector de Metales, junto con la unidad de control electrónica.

un suministro eléctrico y unidad de control, para conectar el dispositivo a la red eléctrica y a los apoyos externos (celula fotoeléctrica, eyectores, etc.)

1 probe- Metal Detector 2 power supply unit with conveyor belt control

(Control Power Box) 3 connecting cable 4 tunnel 5 control panel

Fig. I-1a - THS system (probe-electronics unit + Control Power Box power supply unit) installed on a CEIA conveyor belt.

1 probe- Metal Detector 2 power supply unit with conveyor belt control

(Conveyor Control System) 3 conveyor belt load-bearing structure 4 conveyor belt control panel 5 idler 6 motor roller

Fig. I-1b - THS system (probe- Metal Detector + Conveyor Control System power supply unit) installed on a CEIA THS-FB conveyor belt.

2

1

3

4 5

2

4

6

1

5

3

Page 8: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I - DESCRIPTION 2

THS-Control Power Box

Probe-Metal Detector

Power supply unit(Control Power Box)

Producttransit

photocell

set-asidefull

sensor

ejectionconfirmsensor

Alarm resetcontact

Inhibitioncontact

ejector

buzzer/flashing light

Computeror printer

Encoderto measure belt

movement

Flashing lightindicating test due

Airpressuresensor

ConveyorBelt

malfunction

alarm

bar-codereader

Fig I-2a - Block diagram of the system CEIA THS-Control Power Box system

THS-Conveyor Control System

Probe-Metal Detector

Power supply unit(Conveyor Control System)

downstreambelt author-

isationEncoder

to measure beltmovement

motor

upstreambelt

authorisationAlarm reset

Inhibitioncontact

malfunction

alarm

buzzer/flashing light

Motor driver card

Computeror printer

bar-codereader Flashing light indicating

test due

Producttransit

photocell

set-asidefull

sensor

ejectionconfirmsensor

ejectorAir

pressuresensor

ConveyorBelt

Fig I-2b - Block diagram of the system CEIA THS-Conveyor Control System.

THS-FB/1

THS-FB/2

THS-FB/3

THS-FB/3

Probe-Metal Detector

Power supply unit (Conveyor Control System)

downstream belt author-

isation motor

upstream belt

authorisation Alarm reset

Inhibition contact

malfunction alarm

buzzer/flashing light

MDL inverter card

Computer or printer

bar-code reader

Flashing light indicating test due

Conveyor Belt CEIA

THS-FB/2THS-FB/1

Product transit

photocell

set-aside full

sensor

ejection confirm sensor

ejector

Air presssure

sensor

Fig I-2c - Block diagram of a CEIA THS-FB integrated system including the conveyor belt, the THS unit, the Conveyor Control System power supply unit and the sensors and actuators needed for operation.

Page 9: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I -DESCRIPTION

3

Power-supply and control unit The power-supply and control unit is housed in a watertight box in stainless steel which is designed to be attached by means of four screws and through which pass the connecting cables. The power supply unit is available in two versions:

Control Power Box , containing the metal detector power supply section and designed to allow connection of external sensors and slave devices

Conveyor Control System, with the same functions as the Control Power Box, but with the addition of a conveyor belt motor driver/control section

Control Power Box

Fig. I-3a - Control Power Box in stainless steel casing

Fig. I-3b – Internal view of the ALM card

Fig. I-3c - Control Power Box with RCU remote control panel (model

THS/G or other models on request) The module contains only the electronics needed for supplying power to the probe and the connection terminals for external sensors and slave devices. The card inside (card ALM), allows connections to be made to the following:

• metal detector probe • mains power supply • product transit photocell • external activators and sensors • personal computer

Fig. I-4 Control Power Box: rear and side views

Page 10: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I - DESCRIPTION 4

Conveyor Control System In addition to the functions provided by the Control Power Box, this includes a module to drive the conveyor belt motor. This module is available in two versions:

• Card MDT, for fixed-speed applications; in this case, a three-phase input power supply (230V or 400V) is required;

• Card MDL, for variable-speed applications; in this case, a single-phase input power supply is required, as the card incorporates an inverter with three-phase outputs.

The versions available, therefore, are the following:

Version Application Input Voltage Maximum

power absorbed

Output voltage (motor power supply) *

Maximum power of motor

Conveyor Control System/MDT with MDT module for 230V power supply

Fixed speed 230V -18% / +10%, three-phase without neutral, 48-62Hz

1250VA 230V -18% / +10%, three-phase 48-62Hz

750W

Conveyor Control System/MDT with MDT module for 400V power supply

Fixed speed 400V -18% / +10%, three-phase with neutral, 48-62Hz

2500VA 400V -18% / +10%, three-phase 48-62Hz

1500W

Conveyor Control System/MDL with MDL module

Variable speed

230V ± 10% single-phase 48-62Hz

1000VA 230V three-phase 20-60Hz

750W

* three-phase asynchronous motor , delta connection

N.B.: if the device is to be mounted on the customer’s own conveyor belt, please specify the power supply voltage in the order. The unit also incorporates the main switch, the controls for activating the belt and the LED indicators needed for operation (STC card).

1 On/Off switch 2 control panel

Fig. I-4a: View of the Conveyor

Control System

Fig. I-4b: Internal view of the Conveyor Control System-MDT

Fig. I-4c: Internal view of the Conveyor Control System-MDL

Fig. I-5 Conveyor Control System: rear and side views

2

1

MDL card

ALM card

ALM card

STC card

MDT card

Page 11: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I -DESCRIPTION

5

Metal detector The metal detector is enclosed in an extremely robust metal casing, in a tunnel shape (see fig. below), which is designed to be mounted on the conveyor belt or other feed system. The unit contains the sensitive antenna and the control panel. A cable leads from the unit (on the side of the control panel) to connect up with the power supply unit.

Models available

THS/STD

Fig. I-7 Order code: THS-DWxDH (see table I-3)

Application Model for universal use, for mounting on a conveyor belt Power-supply and control unit • Power Control Box • Conveyor Control System

2204

Fig. I-8

TABLE I - 3 . THS/STD & THS/3F * Model (opening)

DW DH TH DL FHL TP FHP FHW DC TW

Series A 200, 250, ..., 1000 100, 125, 395 290 190 105 TP+10 DW-20 205 DW+420 150,175 TP-30** DW+60** Series B 350, 400, ..., 800 200, 225, ..,275 545 390 290 160 TP+10 DW-20 280 DW+520 Series C 450, 500, ..., 1000 300, 325, 350 635 490 390 210 TP+10 DW-20 320 DW+620 Series D 500, 600, ..., 1300 400, 450, 500 905 490 390 260 TP+10 DW-20 455 DW+720

* For customised versions with different dimensions, see the configuration card at the end of the booklet. ** The position of the support depends on the shape of the load-bearing structure.

THS/3F

Fig. I-9 Order code: THS/3F-DWxDH (see table I-3)

Application multi-frequency model for mounting on a conveyor belt , for use with a variety of products with significant chemico-physical differences (variable conductivity and so on) Application examples • Semi-frozen products in aluminised packaging • Products preserved in vinegar or oil, meat, fish etc. Power-supply and control unit • Power Control Box • Conveyor Control System Dimensions As for the THS/STD model

Page 12: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I - DESCRIPTION 6

THS/MN

Fig. I-10 Order code: THS/MN-DWxDH (see table I-4)

Application model for mounting on a conveyor belt, with high discrimination between contaminating ferromagnetic metal and product, which can also be used with product packed in non-magnetic metal containers Application examples • Products in packaging with a high aluminium content Power-supply and control unit The power supply group comprises two units: a standard power supply unit (PCB or CCS) and a probe power-supply unit. • Power Control Box • Conveyor Control System • Probe power-supply unit

pm2071ab

Fig.I-11

TABLE I - 4 .THS/M * Model (opening) DW DH TH FHW TW 150 350, 550 150 570 DW+60 DW+620 200 350, 550 200 620 DW+60 DW+620 * For customised versions with different dimensions, see the configuration card at the end of the booklet.

THS/SL

Fig. I-12 Order code: THS/SL-DWxDH (see table I-5)

Application SLIM LINE model for mounting on a conveyor belt , with extremely reduced dimensions in the direction of transit Application example • Weighing machines Power-supply and control unit • Power Control Box • Conveyor Control System

Fig. I-13 – Drawing M2202D

TABLE I - 5 .THS Slim Line* Model opening) DW DH TH DL FHL TP FHP FHW TW Series A 125, 150, ..., 450 100, 125 330 175 90 105 TP+10 DW- 20 DW+400Series B 150, 200, ..., 450 150, 175, 200 405 175 90 105 TP+10 DW- 20 DW+400* For customised versions with different dimensions, see the configuration card at the end of the booklet.

Page 13: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I -DESCRIPTION

7

THS/A

Fig. I-14 Order code: THS/A-DWxDH (see table I-6)

Application model for universal use, with a tunnel that can be opened if the conveyor belt can not be interrupted for installation purposes Application examples • Plastic recycling, quarries, mines etc. Power-supply and control unit • Power Control Box • Conveyor Control System

m2205

Fig.I-15

TABLE I - 6 . THS/A* Model (opening)

DW DH TH DL DP FHL RW DS FHW TW

50 285 290 100 Family A 250, 300, ..., 1500 100 335 290 DS+35 DL+50 30 100 DW-20 DW+150 150 385 290 100 200 535 390 150 250 585 500 30 150 DW+150 300 735 500 30 200 DW+150 350 785 600 50 200 DW+170 400 935 600 50 250 DW+170 Family B 500, 550, ..., 1500 450 985 600 DS+35 DL+50 50 250 DW-20 DW+170 500 1035 600 50 250 DW+170 550 1185 750 50 300 DW+170 600 1235 750 50 300 DW+170 650 1385 750 50 350 DW+170

* For customised versions with different dimensions, see the configuration card at the end of the booklet..

THS/G

Fig.I-19

Application model with circular tunnel for products transported in tubing In the case of the THS/G model, the probe is designed to be fixed, generally, in an inaccessible position. The detector controls are therefore incorporated into the power supply unit, on the RCU card fixed to the casing cover. Application examples • Installation between multi-head weighing machines and

packaging machines • Gravitational and pneumatic product transport in

general: powders, granulated products, liquids etc. Power supply unit • Power Control Box Order code: THS/G-T (see table I-7)

Page 14: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I - DESCRIPTION 8

Probe-Metal Detector

Power supply unit(Control Power Box)

Producttransit

photocell

set-asidefull

sensor o

ejectionconfirmsensor

Alarm reset contact

Inhibitioncontact

ejector

Computeror printer

Airpressuresensor

THS/G

malfunction

alarm

Buzzer/flashinglight

Flashing lightindicating test due

Fig. I-20a - Model THS/G: ALM & RCU cards Fig. I-20b - Model THS/G: Block diagram

Fig. I-21 THS/G : probe dimensions (Drawing PM2581F)

TABLE I - 7 THS/G*

Model (opening) T TW DH VL HL THS/G-50 50 380 250 205 226 THS/G-100 100 380 250 205 226 THS/G-150 150 430 300 255 276 THS/G-200 200 480 350 305 326 THS/G-250 250 530 400 355 376

* For customised versions with different dimensions, see the configuration card at the end of the booklet.

ALMRCU

Page 15: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I -DESCRIPTION

9

Options

THS-FB Conveyor Belt Belt with speed adjustment, robustly built and with simplified maintenance, available in several versions

Features • Belt available in PVC approved for food handling. • Adjustable speed: 19...58m/'. • Electrical characteristics: see Conveyor Control System unit. • Compressed air supply:

pressure: 200-1000 kPa; airflow: 50 litres/min (piston ejector),

600 litres/min (airblow ejector, optional) • Dimensions: see figures below. Models * Application Features Models THS Type (width x belt

length) THS

THS/SL THS/M THS/3F

THS-FB/1

300 x 1500mm 500 x 1500mm

packaged or loose product

Conveyor belt with block. Devices included: • photocell • buzzer/flashing light • two auxiliary emergency buttons

• • •

THS-FB/2

300 x 1500mm 500 x 1500mm

packaged product

Conveyor belt with piston ejector. Devices included: • as THS-FB type 1

• piston ejector

• • •

THS-FB/3

300 x 1500mm 500 x 1500mm

packaged product

Conveyor belt with piston ejector and accessory devices. Devices included: • as THS-FB type 2

• ejection confirmation sensor • full set-aside container sensor • insufficient air-pressure sensor • blue flashing light to indicate test due

“Supermarket compliant" system

• • •

* N.B.: the conveyor belt is available only for probes belonging to the A and B Series.

Fig. I-22a Photocell (A) and retroreflector (B)

Fig. I-22b buzzer/flashing light Fig. I-22c auxiliary emergency button

Fig. I-22d ejector unit

Fig. I-22e detail of ejector piston

Fig. I-22f ejection confirmation sensor (A) and full set-aside container sensor (B)

Fig. I-22g insufficient air pressure sensor

Fig. I-22h blue flashing light to indicate test due

A

B

A

B

A

B

Page 16: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I - DESCRIPTION 10

Fig. I-24a conveyor belt

with THS probe from Family A

THS-FB conveyor belt options

Fig. I-23a - Product-containment panels Code: 21533

Fig. I-23b – Castor Code: 21548

Fig. I-23c - Foot Code: 21525

Fig. I-23d – Mounting kit for bar-code readers (both types) Code: 21613

Fig. I-24b conveyor belt with THS probe from Family B

Fig. I-23f – Airblow ejector Characteristics: Max. weight of pack (for pack with low sliding friction): 1 kg; Compressed air supply: pressure 200-1000 kPa; min. airflow 600 litres/min Code: 22477

Page 17: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I -DESCRIPTION

11

Other optionals for THS metal detectors Models THS

Option

THS/

STD

TH

S/SL

SL

THS/

M

THS/

G

THS/

3F

Connecting cable between power supply unit and probe of non-standard length (max. 40m) Order code: 19992

• • • •

RS485 interface, required for: • network connection of several metal detectors • connection of one or more metal detectors over long distances Order code: 17828 • • • •

Management of Picket-Fence barcode reader. N.B.: the bar-code reader application is an alternative to use of the remote control unit Order code: 18701

• • •

Management of Step-Ladder barcode reader. N.B.: the bar-code reader application is an alternative to use of the remote control unit Order code: 19012

• • •

Remote control unit on Control Power Box (for probes located in inaccessible positions). Cable length: 2.5m N.B.: the remote control unit application is an alternative to use of the bar-code reader Order code: 21560

• • •

Remote control unit on Conveyor Control System (for probes located in inaccessible positions) Cable length: 2.5m N.B.: the remote control unit application is an alternative to use of the bar-code reader Order code: 21559

• • •

Power supply transformer unit 115/230V~ transformer unit, to be used to power a THS fitted with an MDL module at 115V~. Order code: 23181 400/230V~ transformer unit, to be used to power a THS, whether fitted with an MDL module or not, at 400V~. Order code: 23182 • • • •

Page 18: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I - DESCRIPTION 12

THS metal detector accessories

Set of quality control test samples Available in the following versions:

Code Samples in ferrous Samples in stainless Samples in non-ferrousmetal AISI 420 steel AISI 316 metal

18711 ø0.8mm ... ø2.5mm sphere ø1.0mm ... ø3.5mm sphere ---22605 ø3.0mm ... ø5.5mm sphere ø4.0mm ... ø6.5mm sphere ---22606 ø3.0mm ... ø5.5mm sphere --- ø4.0mm ... ø6.5mm sphere22607 ø0.8mm ... ø2.5mm sphere --- ø1.0mm ... ø3.5mm sphere

MD Scope program Remote control and programming with oscilloscope function Order code: 26894

Page 19: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I -DESCRIPTION

13

Technical Characteristics

Control Power Box Standard power supply unit

In watertight casing (grade of protection: IP65) Dimensions: 250x150x300mm (wxdxh) Power supply voltage: 115/230 V~ (+10 / -22%), single phase - 48/62 Hz Maximum power absorbed: 60 VA (THS/MN: 200VA)

Conveyor Control System Power supply unit with inverter card

In watertight casing (grade of protection: IP65) Dimensions: 250x180x300mm (wxdxh) Models available

Version Application Input Voltage Maximumpowerabsorbed

Output voltage(motor power supply)*

Maximumpower ofmotor

Conveyor Control System/MDTwith MDT module for 230V powersupply

Fixed speed 230V -18% / +10%,three-phase withoutneutral, 48-62Hz

1250VA 230V -18% / +10%,three-phase 48-62Hz

750W

Conveyor Control System/MDTwith MDT module for 400V powersupply

Fixed speed 400V -18% / +10%,three-phase withneutral, 48-62Hz

2500VA 400V -18% / +10%,three-phase 48-62Hz

1500W

Conveyor Control System/MDLwith MDL module

Variable speed 230V ± 10% single-phase 48-62Hz

1000VA 230V three-phase20-60Hz

750W

* three-phase asynchronous motor , delta connection

Probe-electronics unit Tunnel-shaped metal structure containing the sensitive antenna and the control panel Dimensions: see preceding pages.

Special features • Ultra-high sensitivity • High immunity to environmental interference • LCD display (4 lines of 20 characters each) to show data • Remote or direct programming of the operating parameters (type of product,

immunity level, speed of transit, processing of signal, control over external actuators, etc.) by means of keyboard

• Audio and visual detection indicators. • Display of the signal level by means of bar-graph. • Statistical analysis of the number of inspected and contaminated products • ISO 9001 product quality control • THS/A model: model with tunnel that can be opened • Model THS/SL (Slim Line): extremely compact probe • Model THS/3F: detector for magnetic and non-magnetic metals, for use with

different types of product thanks to selection of the operating frequency • Model THS/PH: model especially designed for the pharmaceutical industry • Model THS/M: detection of ferromagnetic metals when considerable quantities of

aluminium or other non-magnetic metals are present • Model THS/G: probe with circular opening for checking material transported in

tubing.

Password 6 levels: operator / supervisor /engineer/ quality control operator / head of quality control / remote programming

Stored sets of parameters

250 sets of parameter settings may be stored, corresponding to 250 possible different products

Page 20: Detector Industrial de Metales

THS – FI022GB2K8v3 --- I - DESCRIPTION 14

Control inputs Connector for link-up to • photocell • manual reset button • downstream belt authorisation • ejection confirmation • set-aside contained full sensor • encoder to detect the belt speed • emergency button • barcode reader (on demand) • compressed air pressure sensor (for ejection) Serial interface RS232 Serial interface RS485 (on request)

Outputs 5 programmable relays (250Vac - 3A) to activate the external support units •alarm relay •malfunction relay •ejector relay •upstream belt authorisation relay •auxiliary relay

Ejection The system can use the following types of ejector: •compressed air jet •piston •retractable belt Power: compressed air (200-1000 kPa), pressure: 600 litres/min (airblow ejector); 50 litres/min (piston ejector); 100 litres/min (retractable belt ejector).

Alarm signalling Visual: by means of indicator light on central electronics unit Audio: by means of buzzer on central electronics unit By means of output relays

Environmental conditions

Working temperature: 0-50°C Humidity: 5-90%, without condensation

System including conveyor belt

Belt available in PVC approved for food handling on request., Dimensions, weight and accessories: see the configuration sheet at the end of the manual.

Page 21: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 15

INSTALLATION

Observe current regulations regarding electrical and personal safety for both the operator and the installer when installing the device.

BEFORE INSTALLING THE DEVICE READ THE SECTIONS "General guidelines for mechanical installation" and " General guidelines for electrical installation " CAREFULLY. These sections contain some important information regarding sources of electromagnetic interference which may exist in the installation environment. THEN MOVE ON TO INSTALL THE DETECTOR ACCORDING TO THE FOLLOWING SECTIONS, WHICH DESCRIBE: • OPERATIONS RELATING TO A CEIA INTEGRATED SYSTEM:

models mounted on a CEIA conveyor belt or models that do not need any accessories to operate, such as the THS/PH.

• DETAILED OPERATIONS RELATING TO A NON-INTEGRATED

SYSTEM, CREATED BY THE CUSTOMER AROUND THE THS DETECTOR (METAL DETECTOR + POWER-SUPPLY UNIT), with guidelines on the location of accessory devices and their programming. Reading of point 1 is nevertheless recommended in this case as well.

FINAL CHECKS ON INSTALLATION AND PROGRAMMING For the installation checks you need to be able to switch on the system, understand the signals given during use and set the applicable operating parameters. These operations are described in the first part of the “USE” section.

In order to carry out installation operations properly, refer to the information contained in the " Guide to

the applicable installation operations " on the next page.

Page 22: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 16

Guide to the applicable installation operations

Operation Section / Paragraph to read CEIA integrated system with

conveyor belt Non-integrated THS system, without

conveyor belt

Unpacking the device and checking that the various components of the system are all there.

_

Reading the installation instructions

INSTALLATION SECTION • General guidelines for mechanical

installation • General guidelines for electrical

installation • Installation of a CEIA THS integrated

system with conveyor belt • Electrical installation - General notes

INSTALLATION SECTION • General guidelines for mechanical

installation • General guidelines for electrical

installation • Mechanical installation of the model

THS/PH • Electrical installation - General notes • Non-integrated THS system supplied

without conveyor belt: detailed construction notes and selection of operating parameters

• Electrical installation: detailed notes Switching on and checking the safety devices

OPERATING INSTRUCTIONS SECTION • Controls and indicators • Switching on the metal detector

OPERATING INSTRUCTIONS SECTION • Controls and indicators • Switching on the metal detector

Preliminary operating checks: Setting the applicable installation parameters

OPERATING INSTRUCTIONS SECTION • Automatic operation using a bar-code

reader PROGRAMMING SECTION • Programming instructions

Menus - Ejection - THS Configuration - ALM Configuration - I/O status

INSTALLATION SECTION • Non-integrated THS system supplied

without conveyor belt: detailed construction notes and selection of operating parameters

PROGRAMMING SECTION • Programming instructions

Menus - Ejection - THS Configuration - ALM Configuration - I/O status

Preliminary operating checks: Functional check of the slave devices: motor, ejector, signalling devices etc.

OPERATING INSTRUCTIONS SECTION • Signals given during use • Use of the conveyor belt • Alarm reset PROGRAMMING SECTION • Programming instructions

Menus - Ejection - THS Configuration - ALM Configuration - I/O status

The availability of the various parameters on various models is indicated. If a parameter is specific to the current product it is identified. .

Preliminary operating checks: Checking environmental interference

OPERATING INSTRUCTIONS SECTION • Checking for environmental electromagnetic interference

Preliminary operating checks: Checking the sensitivity using a sample supplied

OPERATING INSTRUCTIONS SECTION • Analysis mode selection criteria • Sensitivity check with reference sample

Memorisation of the products being used with possible use of an autolearn process

OPERATING INSTRUCTIONS SECTION • Analysis mode selection criteria • Programming the metal detector according to the kind of product PROGRAMMING SECTION • Programming instructions (Prod. command). • Automatic operation using a bar-code reader

General guidelines for mechanical installation

Page 23: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 17

• Load-bearing structure

During assembly the solidity of the load-bearing structure should be borne in mind, in order to ensure that the detector does not oscillate, causing false alarms

• Metal structures surrounding the Metal Detector/conveyor belt system

Fixed metal structures All the fixed metallic structures in proximity to the detector must be securely fastened down with bolts and self-blocking nuts and, if they form intermittent loops, soldered. This is due to the fact that sporadic metallic contacts due to vibrations, resulting in the intermittent short-circuiting of the voltages induced by the probe, may lead to interference with subsequent false alarms in the device.

Fig. II-1 Fixed metal structures

THS/M Installation of structures or equipment with ferromagnetic frames in the vicinityof the Metal Detector is not recommended. If this proves unavoidable, they must be placed at least distance D from each side of the probe. Other THS models Fixed metal structures (frames, metal furniture, etc.) must, in all cases, be located at a distance that is at least equal to the height of the probe (A), on both sides of the probe.

| Model THS/M THS/A Other models |

| | | D ≥ 3 DH ≥ 2 DH ≥ DH | | |

Fig. II-2 : Fixed metal structures

Moving metal structures Such structures, especially when of a considerable mass (mills, hoppers, etc.), must be located as far away as possible from the probe.

| Model THS/M THS/A Other models |

| | | D ≥ 10 DH ≥ 10 DH ≥ 6 DH | | |

Fig. II-3 Moving metal structures

General guidelines for electrical installation Possible sources of electrical interference may be power supply cables (electromagnetic fields generated by alternating currents) or impulsive electromagnetic sources (electrical motors with high start-up absorption of power and their power supply cables, fluorescent lights, emergency generators, remote control devices, etc.) located near the probe. • Power supply cables to other devices. The route of the conductors must never be allowed to create a large-scale

electromagnetic loop. The power supply cables must be distanced as far as possible from the probe and braided with the shortest possible pitch. In general, it is advisable that the power supply cable harnesses be inserted into special insulated channels. In the event that the conductors have to pass near the probe of the metal detector, it is advisable that they be inserted into an iron tube, either electro-welded or drawn, which is at least 2 mm thick and has a suitable diameter. N.B: this solution is only valid if the tube is not subject to vibrations; should it be subject to vibrations this solution could even be counter-productive.

• Grounding. This connection must lead directly to the electrical power supply board and must not be derived from any

other electrical devices.

Page 24: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 18

M1 MD M2

QE

Fig.II-4. QE: electrical board; M1: machine 1; M2: machine 2; MD: metal detector. • Warning! If metal ducts are used for production line

power and control lines, it is advisable not to create an electrical connection between the conveyor belt frame and other nearby devices through the same ducts: if this is done, interference due to multiple ground returns could be produced.

M1 MD M2

ci

Fig. II-5. ci: ducts in insulating material; M1: machine 1; M2: machine 2; MD: metal detector

• Impulsive sources. In general, impulsive sources must be distanced or eliminated.

It is therefore recommended that, during installation, the following procedures be carried out: 1 position as far as possible from the probe any motors, electrical power boards or electromagnetic actuators (it is

recommended that they be replaced with similar pneumatic devices); position fluorescent lights and their respective reactors at a distance from the metal detector probe; where possible replace fluorescent lights with filament lights.

2 equip electrical motors with special iron screens and mains filters of sufficient capacity. It is recommended that

motors running on alternating current be used as opposed to those running on direct current. The table that follows provides some general guidelines for the distances to be placed between the probe and asynchronous motors, depending on their power.

Table II-A

Recommended minimum distance between the probe and motors with alternating current (without screening of the motor)

Power Minimum distance THS/M & THS/A Other THS models 0,5 CV 5 x DH 3 x DH 1 CV 6 x DH 4 x DH 2 CV 8 x DH 5 x DH 3 CV 10 x DH 6 x DH > 20 CV 15 x DH ( >10 x DH if screened) 10 x DH ( 6 x DH if screened)

2.1 In the immediate proximity of the metal detector, the motors may be screened by means of cylindrical

enveloping in iron; such cylinders must have a sufficiently large diameter in order to contain the motors and a thickness of not less than 2 mm. The cylinders must be of the unwelded type.

3 fit the electromagnets, remote controls and continuous current motors with RC muffling nets (ask our technical

office for details of the dimensions) and braid the respective power supply cables with as short a pitch as possible.

Fix the cable which connects the probe to the power supply unit so that it can not oscillate or vibrate. If the cable is too long, DO NOT CUT THE CABLE: COIL UP THE EXCESS!

Page 25: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 19

Installation of a CEIA THS-FB integrated system with conveyor belt

Disconnect the system from the various power sources before carrying out any movement.

Mechanical installation of THS-FB integrated system with conveyor belt

Fig II-6

Positioning the conveyor belt Use lift trucks or sling the load-bearing structure, and ensure that the load is balanced during movement. Avoid deforming the structure or its component parts. Keep the packaging materials for possible future transport.

Never attach lifting gear to the Metal Detector probe or the actuators.

Fig II-7a Fig II-7b

Ejector: mounting the safety shield Fix the shield by tightening the knobs provided.

Fig II-7c Fig II-7d

Assembling the buzzer/flasher Fit the buzzer/flasher module into the support and rotate clockwise.

Fig II-8a - Adjusting a foot Fig II-8b - Adjusting a castor

Adjusting the height of the belt Raise or lower the adjustable feet or castors of the load-bearing structure.

Page 26: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 20

Electrical installation - General notes

Observe current regulations regarding electrical and personal safety for both the operator and the installer when installing the device.

Connect the apparatus to the mains power supply only after first carrying out all the other connections needed for complete installation.

These instructions for electrical installation apply to both the CEIA INTEGRATED THS SYSTEM, with conveyor belt, and the CEIA NON-INTEGRATED THS SYSTEM, without conveyor belt.

Connecting to the mains power supply

Only make the connections to the internal terminals of the power supply unit when the unit is disconnected from the mains

Connection to the ground

Connect a grounding conductor to the PE terminal ; the size of the conductor should be in line with the safety standards in force.

Fig. II-9a Terminal PE

Control Power Box

Fig. II-9b Control Power Box

PE

• Connect directly to terminal board J17 on card ALM.

• Conductor section: 1.5 mm2.

Put in a magnetothermic switch upstream: Voltage Current 250Vac 2A 115Vac 4A

Conveyor Control System • Connect to S1 main switch input terminals. • Conductor section: 2.5 mm2.

Put in a magnetothermic switch upstream (curves D) : 10A Fixed-speed Conveyor Control System, with MDT card

Fig. II-9c

• The connection is three-phase, and differs according to the voltage.

Check that the voltage corresponds to the voltage on the identification plate (specify the power-supply voltage when ordering).

IS

Page 27: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 21

Voltage 400V 3~ with neutral conductor

N

PE2200

Fig. II-9d

voltage 230V 3~ without neutral conductor

N

PE

2199

Fig. II-9e

Variable-speed Conveyor Control System with card MDL

Fig. II-9f

• Single-phase connection. • Put in a ground fault interrupter upstream, provided that the trip current is at

least 300 mA.

Connect the safety conductor permanently (without intermediate plugs)

to terminal PE on the casing.

Selection of the power supply voltage for the metal detector only - Control Power Box Power Supply Unit

Fig.II-10

Using the I1 switch, it is possible to set the metal detector power supply voltage to 115Vac or 230Vac. In the illustration, the selector is positioned at 220-240Vac.

N.B.: the conveyor belt motor must be set up for the power supply voltage of the system: the power supply voltage should therefore be specified at the time of ordering.

If the power supply to the device is different from that specified on the plate and/or from that chosen at selector I1, permanent damage may be caused to the device. CEIA will not be held responsible for damage to people, animals or objects caused by failure to obey this instruction. Verification that the power supply conforms to the values specified above and to the regulations in force is the total responsibility of the customer.

Connection of the compressed air supply Connect any components powered by compressed air to a source which complies with the specifications in the “Technical characteristics” section, or otherwise specified in the configuration sheet enclosed with this manual.

IS

I1

Page 28: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 22

Non-integrated THS system supplied without conveyor belt: detailed construction notes and selection of operating parameters

The following notes provide additional instructions necessary for installing the detector on a conveyor belt or other transport system set up by the customer. For the installation checks you need to be able to switch on the system, understand the signals given during use and set the applicable operating parameters. These operations are described in the first part of the “USE” section.

Mechanical Installation

Controls According to regulation EN60204-1, the main switch and the other controls to be used by the operator must be at a height ranging from 600mm to 1,800mm from the flooring. If it proves impossible to comply with this measurement due to the configuration of the system, an additional control unit which complies with the regulations must be set up.

Mechanical installation of the metal detector Mount and fix the probe onto the structure of the conveyor belt (use the four holes located on the base-plates. N.B.: on some models the base-plates can be fixed in two different positions to adapt to the shape of the load-bearing structure). The belt must pass through the tunnel.

The structure must be stable and not subject to vibrations.

Mechanical installation of the power supply unit The power supply unit must be firmly attached to the load-bearing structure by means of four screws; it must be close to the central electronics unit and to the external subsidiary devices connected to the unit (photocell, ejector, etc.).

Mechanical installation of the THS/G probe Mount the probe on the pipe carrying the material to be inspected and fix it with screws and plastic spacers, using the holes provided on underside ( see Fig. "Dimensions of the probe", dimension FHW). Fix the control unit in a convenient position for use, within the limit set by the length of the probe connecting cable.

Fix the cable which connects the probe to the power supply unit so that it can not oscillate or vibrate. If the cable is too long, DO NOT CUT THE CABLE: COIL UP THE EXCESS!

Proximity limits around the THS/G probe The distance between the probe and fixed or moving masses depends on the sensitivity selected and on the size of the masses. The figure below shows: • the minimum distance D between the probe S and the support plate P • the minimum distance H between the probe S and the deflector f, based on a sensitivity setting of 280 and a flap-

type deflector in stainless steel. If the sensitivity or the type of deflector is changed, this minimum distance may decrease: using the procedure for checking environmental interference (see “Maintenance” section), check that activation of the deflector does not influence operation of the metal detector.

Page 29: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 23

D: distance between probe S and support plate P d: rigid plastic spacer; f: steel flap deflector (dim. 290x200x2mm); H: distance between probe S and deflector f p: stainless steel support plate; S: probe. T: diameter of the probe. t: plastic pipe

Fig. II-12 – fixing the THS/G probe

THS/G : mounting the power supply unit The power supply unit must be firmly fixed to the supporting structure with four screws, near the electronics unit and the slave devices connected to the power supply unit (photocell, ejector etc.). For the location of the holes provided for fixing the unit, see Figure I-14a.

Page 30: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 24

Conveyor belt

The distances quoted below are indicative only, and subject to variation according to the sensitivity required and to the type of probe. When installation has been completed, therefore, correct operation should be checked.

Load-bearing structure of the conveyor belt The load-bearing structures of the conveyor belt must be stable and not subject to detectable vibration during movement of the belt. THS/M The structure of the belt must be in non-magnetic steel (e.g. non-magnetic AISI 304).

Fig. II-13 Load-bearing structure Rollers of the conveyor belt

In general, it is advisable that any rollers located near the antenna be of insulating material. In which case, there must be an electrical connection on only one side of the roller, in order to allow the discharge of any electrostatic charges. | Model THS/M THS/A Other models |

| | | D ≥ 3 DH * ≥ 3 DH * ≥ 1,5 DH ** | | |

* use nonmagnetic steel bearings. ** plastic roller with fixed nonmagnetic steel axle and nonmagnetic steel bearings. N.B.: the bearings must be placed at the ends of the rollers, never in the middle.

IC

D

B

DH

Fig. II-14. Rollers in insulating

material with metallic bearings

I: insulated support C: non-insulated support; B: bearing

Metal rollers , pulling or free, must be located at a distance D, to both sides of the antenna. Such rollers must also be insulated on a single supporting piece in order to avoid forming electromagnetic coils and allow the discharge of any electrostatic charges.

| Model THS/M THS/A Other models |

| | | D ≥ 6 DH ≥ 4 DH * ≥ 2 DH | | |

C: non-insulated support I: insulated support S: screening

IC

D

DH

Fig. II-15a. Free metal rollers

I: insulated support C: non-insulated support

I

C

D

S

DH

Fig. II-15b. Pulling metal rollers

Metal rollers must be perfectly concentric.

YES! NO!

Fig. II-16

Page 31: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 25

The motors must be located at a distance D from the antenna, adopting measures identical to those described for the rollers above.

Fit electrical motors with special iron screens and mains filters of sufficient capacity. It is recommended that motors running on alternating current be used rather than those running on continuous current. The table that follows provides some general guidelines for the distances to be placed between the probe and asynchronous motors, depending on their power

Minimum distance advisable between the probe and motors with alternating

current (without motor screening) | Models THS/M THS/A Other models |

| | | D 0,5 CV ≥ 5 DH ≥ 5 DH ≥ 3 DH | | 1 CV ≥ 6 DH ≥ 6 DH ≥ 4 DH | | |

• In the immediate proximity of the metal detector, the motors may be screened

by means of cylindrical enveloping in iron; such cylinders must have a sufficiently large diameter to contain the motors and a thickness of not less than 2 mm. The cylinders must be of the unwelded type

• The table indicates distance measurements corresponding to a high sensitivity level; for lower sensitivity levels, distance D may be reduced.

I

C

D

S

DH

Fig. II-17. motors

C: non-insulated support

I: insulated support S: screening

Attention: Rollers for V-shaped belts, if attached to the frame on one side only, do not require the insulation of the pin. As in the preceding case, their distance from the probe must be at least equal to D, to both sides of the antenna

| Models THS/M THS/A Other models |

| | | D ≥ 9 DH ≥ 6 DH ≥ 3 DH | | |

D

C

DH

Fig. II-18. Metal rollers for V-

shaped belts C: non-insulated support

Examples of roller insulation Insulation of the pin of a roller. I: ferrule in insulating material; P: side bulkhead of the belt frame; R: roller.

I

P

R

Fig. II-19a

Insulation of the pin support of a roller. I: bearing support in insulating material; P: side bulkhead of the belt frame; R: roller.

I

P

R

Fig. II-19b

Insulation of the bearing support of a roller pin. I: ferrule and spacer in insulating material.

I

Fig. II-19c

Page 32: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 26

Position of the conveyor belt inside the probe

• The conveyor belt must pass as close as possible to the lower surface of the tunnel. In order to prevent it from accidentally rubbing against the probe it is advisable that it be supported within the probe by means of a sheet of insulating material , which is thick enough to support the weight of the material being transported (approximately 5-20 mm). It is necessary to take this measure when the belt is of considerable length and must therefore be supported, while at the same time prevented from vibrating. The sheet must not touch the probe (in the illustration an intervening distance of 5-10 mm is shown); if it were to touch the probe it could send vibrations to the antenna. In any event, if there is a supporting metal layer for the belt, when it arrives at the probe, it must be interrupted for a distance D, to both sides of the antenna.

| Models THS/M THS/A Other models |

| | | D ≥ 4 DH ≥ 3 DH ≥ 2 DH | | |

N.B.: THS/M Model: if the product is contained in an aluminium tray, the

optimum distance between the bottom of the tray and the surface of the tunnel is 20-30mm.

N.B.: In the standard structure, the conveyor belt passes through the probe in

both directions to avoid having to cut and rejoin it if the probe is replaced. If necessary, carry out the join as described in the “Maintenance” section.

pm

pi n

D

DH

n

pi

Fig. II-20. Position of the conveyor belt inside the probe

pi: sheet of insulating material; pm:

layer of metal material; n: belt

Side panels to contain the material in transit

• Near the probe, such edges must be made of insulating material (plastic, wood, etc.).

Fig. II-21 Side panels for containing the material in transit

Inserting the conveyor belt on the THS/A model

The THS/A model allows the installation of one side of the conveyor belt through the probe, without cutting the belt itself. The probe has a short section on its side which can be removed to insert the belt. Procedure • Remove screws S. • Remove section A. • Move the belt into the probe, or the probe over

the belt, depending on the requirements of the structure.

• Fix section A in place again using screws S.

B

AS

Fig. II-22

Page 33: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 27

Transit speed

Generally-applied setting Programming parameters Meaning THS/STD THS/SL THS/3F THS/M THS/G THS/PH

BS Transit speed 2 - 250m/’ 2 - 250m /’ 2 - 250m /’ 20 - 70m/’ 2 - 250m /’ 2 - 250m /’

BL Minimum transit speed 2 m/’ 2 m/’ 2 m/’ 20 m/’ 2 m/’ 20 m/’

BM Maximum transit speed 250 m/’ 250 m/’ 250 m/’ 70 m/’ 250 m/’ 250 m/’

KT transmission constant of the motor reducer unit

KT = transit speed . motor driver frequency _ _

DI Diameter of roller DI = ø roller + 2 x (thickness of belt) _ _

KE Encoder constant (impulses per revolution) 0-1000 impulses per revolution _ _

MI Maximum motor operating frequency 60-100 (Hz) - -

CU Maximum motor current consumption 0.000 - 7.000 A - -

The programming parameters must be properly defined depending on the type of installation. Fixed-speed application, without inverter card, without encoder (KT=0.000, KE=0)

V

BS should be assigned the true value of the transit speed.

Fixed-speed application, with MDT card but with encoder (KT=F, KE=0)

V

BS should be assigned the true value of the transit speed.

Variable-speed application, with encoder, without inverter card

V

speed detected by the encoder. The speed limits (BL e BM) must be selected. The KT parameter is 0.000. Assign to the KE parameter the number of pulses per revolution of the encoder. Assign to the DI parameter the value of the diameter of the motor roller (see table above)

Page 34: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 28

Variable-speed application with inverter card, with encoder

V

Variable-speed application with inverter card, without encoder

V

• BS should be assigned the desired value of the transit speed (the current speed is detected by the system based on the working location of the inverter, or via an encoder if fitted).

• Assign to the KE parameter the number of pulses per revolution of the encoder.

• Assign to the DI parameter the value of the diameter of the motor roller (see table)

• Assign the maximum motor operating frequency to parameter MI.• Assign the maximum motor current consumption to parameter

CU. Some structural relationships must be observed:

BL ≤ BS ≤ BM BL ≥ 20 x KT BM ≤ 60 x KT

The parameter KT depends on the system configuration, and can be determined using the following procedure (it is necessary to obtain a transit speed measurement device):

1. set KT=1.000 2. set BS=50 3. activate the motor and measure the speed of transit Vn 4. calculate KT = Vn/50

By changing the value of BS, the speed can vary between 40% and (2 x MI)% of the nominal value of the motor (corresponding to operation at 50Hz). N.B.: by modifying the value of KT, the parameters BL and BM are automatically set to nominal values, respectively 20 x KT and MI x KT. BL and BM can also be modified manually. Example: Motor: operating frequency 50Hz ; maximum frequency 60Hz; maximum current 3A; Encoder 100 impulses/rev.; Roller diameter 60mm, belt thickness 2mm; Desired speed 45m/', minimum 25m/', maximum 50 m/'. • Set: MI=60, CU=3.000, DI=60+(2x2)=64 • Determine KT via the procedure described above:

KT=1.000, BS=50 measured Vn =55 m/' KT=55/50=1.100 • Set BL=25 (correct value to give 20KT=22) • Set BM=50 (correct value to give MI x KT=66) • Set desired speed BS=45

N.B.: The BS parameter is memorised individually for each type of product defined. If required, several speed parameters may be set for the same material by defining an equal number of product types.

Page 35: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 29

Accessory devices

Photocell – General rules

Programming parameters

Meaning Generally applied setting

THS/STD THS/SL THS/3F THS/G THS/M THS/PH PD Distance between metal

detector and photocell At the entrance to the probe: 0-2000 mm At the exit from the probe: see table II-C

50-2000 mm

_

PH Position of the photocell relative to the probe

IN : installed at the entrance to the probe OUT: installed at the exit from the probe

IN _

IP Type of “Photocell” input NC,NO

_

The photocell should naturally be placed at a height whereby it can have a clear view of the objects on the conveyor belt. Photocell installed at the entrance to the probe

F

S

N

PD

When installed at the entrance to the probe, the photocell distance should be within the range 50mm to 2 m

Photocell installed at the exit from the probe

F

S

N

PD

Fig.II-24. N: conveyor belt; S: electronics unit; F: photocell;

d: distance photocell- electronics unit

When installed at the exit from the probe, the photocell distance (PD in the figure) depends on the belt speed, but should not in any case be less than that indicated in the following table:

Table II-C

Belt speed (metres/min) Minimum distance photocell-electronics unit (mm)

< 20 5020 5030 6040 10050 13060 16070 19080 23090 260

>100 290

Photocell self-diagnosis If the photocell is in a continuously active state for a long period, this is interpreted as a malfunction of the sensor by the self-diagnosis system. There are many possible causes (wrong position, short-circuited wiring etc.). The self-diagnosis message may appear:

- in the case of a conveyor belt without encoder or with Power Control Box, with the belt stopped or moving - in the case of a conveyor belt without encoder or with Conveyor Control System, with the belt moving.

The system is not designed to signal a pack which is stuck for some reason in front of the photocell. For this reason, when the system can detect whether or not the conveyor belt is moving (i.e. when it is equipped with an encoder or with the Conveyor Control System power supply unit), the self-diagnosis function gives an alarm only if the photocell is in a state of malfunction when the belt is moving.

On systems without encoder or with the Control Power Box, it is the installer’s and operator’s responsibility to ensure that material does not remain in front of the photocell when the belt is stopped: if it does, the photocell will be continuously active even though it is not malfunctioning. If the foregoing situation can not be avoided, it is advisable to disable photocell self-diagnosis (Parameter PA)

Ejector – General rules

Page 36: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 30

Programming parameters

Meaning Generally applied setting

THS/STD THS/SL THS/3F THS/G THS/M THS/PH PL Length of

product pack _ 5-80cm _

EM Ejection mo Mode B: halting of the production line and manual elimination of the contaminated material

Mode F: automatic set-aside of contaminated material with alarm synchronisation

Mode S: automatic set-aside of contaminated material with photocell synchronisation

Mode SB: halting of the production line with photocell synchronisation and manual elimination of the contaminated material

_

ED Distance of ejector from probe or photocell

0-6000mm

Application with photocell: set Dfe parameter (see the following figures) Application without photocell: set Dse parameter

ET Ejection relay activation time

0-3200 hundredths of a second

The programming parameters which relate to the ejector are CE, CT, EJ, IE, IL and LF (see Programming section). Position the ejector E at the exit point of the central electronics unit. In general, the ejector position is constrained by the following formulas:

Dp

L

PL

F

S

E

N

DfeDse

Dfe ≤ 20 x ( PL + Dp) Dse > 0.5 x (L + PL) Fig.II-25: synchronisation with photocell at the entrance to the probe

Dp

L

PL

F

S

E

N

Dse

Dfe

Dfe ≥ 0.5 x PL Dse ≤ 20 x ( PL + Dp) Fig.II-26: synchronisation with photocell at the exit from the probe

Dp

L

PL

S

E

N

Dse

Dse ≤ 20 x ( PL + Dp) Dse > 0.5 x (L + PL) Fig.II-27 synchronisation with Metal Detector

S probe/electronics unit of the metal detector L length of probe N conveyor belt Dfe distance photocell-ejector F photocell Dse distance probe-ejector

PL length of package Dp distance between packs E ejector

The ejection time ET must be determined by experimentation, as it depends on the type of ejector

To minimise the number of packs rejected at each alarm, it is recommended that Dp is longer than L, so that only one pack is ejected each time the ejector is activated.

THS/M – Specific instructions for ejector Rule Note

Dse ≥ PL + 0,5xL + BS 60 x (ejector response time)

BS: transit speed, in m/min

Dp = 1,2 x (PL + L)

For accurate analysis, the previous product must have left the tunnel before the next one passes through

Page 37: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 31

Applications at high speed (belt speeds greater than 60 m/min) In this case, the response times of the photocell, metal detector and ejector can not be ignored. We would generally advise users to check operation of the ejector experimentally, changing its position and adjusting parameter ED.

Programming used in a few common types of installation

Belt block without ejector

ed

Photocell at entrance, with ejector

E

F

ed

pd

parameter code

description value parameter code

description value

EM BS EJ ED

ejection mode speed ejection ejection distance

B, BS (belt block) belt speed (m/min) ON ed (mm) pack stop position

EM BS PL IP ET LO EJ ED PD PH

ejection mode speed pack length photocell input ejection time input logic ejection ejection distance dist. ph.- metal det. photocell position

S (synchronised) belt speed (m/min) length of pack (cm, only for THS/M) NO: normally open /NC: norm. closed ejection time (hundredths of a second) N: negative / P: positive ON ed (mm) pd (cm) IN

Photocell at exit, with ejector pd

ed

F

E

Retractable belt ed

parameter code

description value parameter code

description value

EM BS IP ET LO EJ ED PD PH

ejection mode speed photocell input ejection time input logic ejection ejection distance dist. ph.- metal det. photocell position

S (synchronised) belt speed (m/min) NO: normally open NC: norm. closed ejection time (hundredths of a sec) N: negative / P: positive ON ed (mm) pd (cm) OUT

EM BS ET EJ ED

ejection mode speed ejection time ejection ejection distance

F (flap) belt speed (m/min) ejection time (cs) ON ed (mm)

Fig.II-28 F: photocell E: ejector

Page 38: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 32

Mechanical installation of a bar code reader

Safety precautions Although the power of the laser beam used in this barcode reader is very low, it can be dangerous to the human eye if stared into for long periods of time. Careful attention must be paid to the warnings on use of the laser. These warnings refer to regulations enforced by local authorities. IEC regulations Warning labels indicating laser radiation and the reader classification are applied to the body of the reader:

Fig.II-29 The device is classified as a Class 2 laser product according to the rules indicated in IEC publication N. 825-1 (1993).

Turn the power off when opening the reader during maintenance or installation to avoid dangerous laser radiation.

Barcode reader kit The barcode reader can also be installed on the THS system at a later date: a special kit is available for this purpose, and includes an enabling code. The reader is available in two versions:

• Picket-Fence, optimised for codes with vertical bars • Step-Ladder, optimised for codes with horizontal bars

1 reader 2 Bar code test chart (PCS 0.9) 3 Mounting kit: - bracket- screws

Fig.II-30a composition of the barcode reader kit

Fig.II-30b dimensions

Page 39: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 33

Distance between the reader and the metal detector probe and distance between packs The reader is mounted upstream of the probe in order to read a code stamped on the pack. If the code is recognised, the reader sends a command to the metal detector to select the relevant product type. The time required by the THS to process the barcode is usually insignificant, but becomes important if the band is changed due to a modification in the type of product.. When the metal detector receives the signal to change product type, an internal adjustment procedure is activated the length of which determines the minimum distance between two packs with different codes, that is to say containing different products.

Model / Event Distance between the packs

Distance between the barcode reader and the THS

probe

L

S

Dp

BR

N

Dsbr

THS/3F with change of band

(BA parameter) between one product

and the other

Dp ≥ L + 3000 mm

Dsbr ≥ 3000 mm

L

S

Dp

BR

N

Dsbr

THS/3F without change of

band (BA parameter) between one product

and the other

Dp ≥ L + 300 mm

Dsbr ≥ 300 mm

L

S

Dp

BR

N

Dsbr

Other THS models

Dp ≥ L + 300 mm

Dsbr ≥ 300 mm

S probe/electronics unit of the metal detector L length of probe N conveyor belt Dsbr Distance THS probe-barcode reader

BR Barcode reader Dp Distance between the packs of different products

Position of the reader and the label in transit

A non-rigid mounting, using anti-vibration supports, should be adopted for the reader.

The two types of reader should be mounted as shown in the figures below. Attention must be paid to the position of the pack in transit, in order to ensure that the barcode can be read (angles P, S and T in the following figures).

P = 0˚˜ P = 0˚˜

D

P = 0˚˜

P = 0˚˜

D

S = 10 - 30˚

S = 10 - 30˚

S = 10 - 30˚

S = 10 - 30˚

S = 10 - 30˚

D

T = 0˚˜ T = 0˚˜

T = 0˚˜ T = 0˚˜

Fig. II-31a Step-Ladder reader: mounting Fig. II-31b Picket-Fence reader: mounting

Page 40: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 34

Reading features The number of scans performed on the code by the reader, and therefore its decoding capability, is influenced by the following parameters:

• number of scans per second • code motion speed • label dimensions • scan direction in respect to code motion

At least 5 scans during the code passage should be allowed to ensure a successful read.

Step-Ladder mode

BCR bar code reader CMD code motion direction at LS speed LB laser beam Fig. II - 32

If scanning is perpendicular to the code motion direction ( “step ladder” mode), the number of effective scans performed by the reader is given by the following formula:

SN = ((LH/LS) * 350) - 2 These symbols signify:

SN = number of effective scans LH = label height (in mm) LS = label movement speed (in mm/s)

For example, the reader for a 25 mm high code moving at 500 mm/s performs:

SN = ((25/500) * 350) - 2 = 15 effective scans

Suitable values for LH and LS should therefore be chosen, so that:

LH/LS > 0.02

Picket-Fence mode

BCR bar code reader CMD code motion direction at LS speed LB laser beam Fig. II -33

If scanning is parallel to the code motion, (“picket fence” mode), the number of effective scans is given by:

SN = (((FW-LW)/LS) * 350) - 2 These symbols signify:

SN = number of effective scans FW = reading field width (in mm) LW = label width (in mm) LS = label movement speed

Page 41: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 35

Reading field width depends on the distance between the label and the reader. The following figure gives the reading diagram for the following conditions::

• code = interleaved 2/5 or code 39 • PCS = 0.90 • P angle = 0° • S angle = 10° • T angle = 0°

Fig. II -34 width of the reading field

For example, for a code 50 mm wide moving through at 1500mm/s at a distance from the reader corresponding to a reading field of 200mm, we get:

SS = (((200-50) /1500) * 350) - 2 = 33 effective scans The position of the reader must therefore be chosen so that FW is at maximum, based on the reading diagram, and LW e LS should be chosen so that

(FW-LW)/LS > 0.02

Kit installation procedure 1. Mechanical mounting, including determination of:

• Distance between reader and metal detector probe • code transit speed • label dimensions

2. Electrical connection to the ALM card 3. Assignment of the CEIA enabling code to parameter BE 4. Selection of parameters from the "barcode reader" menu 5. Selection of the corresponding product type, or creation of a new one if necessary 6. Execution of barcode acquisition procedure (command LC) 7. Repetition of steps 5 and 6 for all products being used

Distance of the label from the reader axis

reader axis

Reader - label distance

Page 42: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 36

Electrical installation: detailed notes

Fig. II -35a : Diagram of model THS connections

Page 43: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 37

Fig. II -35c : Diagram of model THS/G connections

Page 44: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 38

Fig. II -35d : Diagram of model THS-FB connections

Page 45: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 39

Observe current regulations regarding electrical and personal safety for both the operator and the installer when installing the device.

Connect the apparatus to the mains power supply only after first carrying out all the other connections needed for complete installation.

ALM card electrical connections Table II-D ALM card connections

Connector Pin Label Input/ Output

Type Range /Max. value Function

ALM-J1 - - - - - Reserved ALM-J2 - - - - - Reserved ALM-J3 7-8 - Input N.C. contact - Emergency button ALM-J4 1

2 3 4 5 6

NC ISO GND RX- RX+ TX+ TX-

- - Input Input Output Output

NC ground RX- RX+ TX+ TX-

RS 485 serial connection (see next table) N.B.. the ground contact is insulated from the power supply unit ground, and is provided for connection of RS485 cable shielding (if required)

ALM-J5 1 2 3 4 5

-V -V TXD RXD +VB

Output Output Output Input Output

-V -V TXD RXD +VB

0V 0V - - 20-26Vcc, 0.15A

Bar-code reader

ALM-J6 2 3 5 6

- - - -

Input Output - Input

RXD TXD ground DTR

- - - -

RS 232 serial connection (see next table)

ALM-J7 - - - - - reserved ALM-J8 - - - - - reserved ALM-J9 - - - - - reserved ALM-J10 1

2 3

+Vin lid full -V

- Input -

+V N.O. contact* ground

20-26Vcc, ** 0V... +Vin -

+V (high logic level/sensor power supply) container full 0V (low logic level/ power supply ground)

4 5 6

+Vin eject confirm . -V

- Input -

+V N.O. contact* ground

20-26Vcc, ** 0V... +Vin -

+V (high logic level/ sensor power supply) ejection confirmation 0V (low logic level/ power supply ground)

7 8 9

+Vin photocell -V

- Input -

+V N.O. contact* ground

20-26Vcc, ** 0V... +Vin -

+V (high logic level/ sensor power supply) photocell 0V (low logic level/ power supply ground)

10 11 12

+Vin follow.conveyor -V

- Input -

+V N.O. contact ground

20-26Vcc, ** 0V... +Vin -

+V (high logic level/ sensor power supply) downstream belt authorisation 0V (low logic level/ power supply ground)

ALM-J11 - - - - - reserved ALM-J12 1

2 3

+Vin Inhibition -V

- Input -

+V N.O. contact ground

20-26Vcc, ** 0V... +Vin -

+V (high logic level) inhibition 0V (low logic level)

4 5 6

+Vin Reset -V

- Input -

+V N.O. contact ground

20-26Vcc, ** 0V... +Vin -

+V (high logic level) alarm reset 0V (low logic level)

7 8 9 10

+Vin Encoder -V terra

- Input - -

+V N.O. contact ground ground

20-26Vcc, ** 0V... +Vin - -

+V (high logic level/sensor power supply) encoder impulses 0V (low logic level/ power supply ground) ground

ALM-J14 - - - - - reserved ALM-J15 1

2 3

common Cont. NC Cont. NA

Output Output Output

common N.C. contact N.O. contact

250Vca 3A 250Vca 3A 250Vca 3A

auxiliary relay for test due notification

4 5 6

common Cont. NC Cont. NA

Output Output Output

common N.C. contact N.O. contact

250Vca 3A 250Vca 3A 250Vca 3A

authorisation upstream belt relay

ALM-J16 - - - - - reserved ALM-J17 1

3 4

L0 L1 PE

Input Input -

- - ground

230Vac ± 10% 48-62Hz 230Vac ± 10% 48-62Hz -

mains power supply*** safety ground PE ****

Page 46: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 40

Connector Pin Label Input/ Output

Type Range /Max. value Function

ALM-J18 - - - - - reserved ALM-J19 1

2 3 4

terra C1 NC1 NA1

- Output Output Output

ground common N.C. contact N.O. contact

- 250Vca 3A 250Vca 3A 250Vca 3A

ground malfunction relay

5 6 7

C2 NC2 NA2

Output Output Output

common N.C. contact N.O. contact

250Vca 3A 250Vca 3A 250Vca 3A

ejector relay

8 9 10

C3 NC3 NA3

Output Output Output

common N.C. contact N.O. contact

250Vca 3A 250Vca 3A 250Vca 3A

alarm relay

ALM-J20 - - - - - reserved ALM-J21 - - - - - reserved (connection of metal detector) ALM-J22 1

2 3 4 5 6 7 8 9 10 11

+Vo +Vo -V -V +VDD -V +VDD2 -V OUT 1 OUT 2 PE

Output Output Output Output Output Output Output Output Output Output -

+Vo +Vo -V -V +VDD -V +VDD2 -V OUT 1 OUT 2 ground

20-26Vcc, ** 20-26Vcc, ** 0V 0V - 0V - 0V 18-30Vcc,0..2A 18-30Vcc,0..2A -

reserved reserved ground (external contacts) ground (external contacts) reserved ground (external contacts) reserved ground (external contacts) motor stop alarm (EM=B) reserved safety ground

N.C. contact: normally closed contact; N.O. contact: normally open contact

* IE=NO, IL=NO, IP=NO ** The +Vin outputs can provide an overall maximum current of 150mA ; the +Vo outputs can provide an

overall maximum current of 150mA *** On the model with conveyor belt, connect the power supply line to the main switch (see diagram below) **** IMPORTANT! In the case of the Conveyor Control System , connect the safety conductor permanently

(without intermediate plugs) to terminal PE on the casing. N.B.: the J7, J10 and J12 inputs can be connected to switch contacts or to transistors (in this case the saturation voltage must be < 0,4V). Their logic is determined by the LO parameter (Input logic, see Programming section).

0V

+Vin

0V

+Vin

0V

+Vin

0V

+Vin

LO=N: contact LO=P: contact LO=N: transistor LO=P: transistor Fig. II-36

Make all connections relating to input lines using screened cable, connecting the shielding only at the THS

system end to the contacts marked with the symbol which are provided on the various connectors. Lay the cables at a good distance from power lines.

Page 47: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 41

Conveyor Control System: Power-supply and motor connections

MDT card

N

E2199

PE

Fig. II-37a MDT card connections for 230V power supply

N

E2199

PE

Fig. II-37b MDT card connections for 400V power supply

Table II-E: MDT card connections for three-phase 230V power supply

Connector Pin Label Input/ Output

Type Range /Max. value Function

MDT-J23 1 2 3 4 5

1 2 3 4 5

- - Input Input Input

Ground Neutral L3 Phase L2 Phase L1 Phase

- - 230V -18% / +10% , 48-62Hz 230V -18% / +10%, 48-62Hz 230V -18% / +10%, 48-62Hz

safety ground PE Not used Power supply Power supply Power supply

MDT-J24 1 2 3 4 5

1 2 3 4 5

Output Output Output - -

W Phase V Phase U Phase - Ground

Input voltage and frequency, 5A (8A breakaway current) Input voltage and frequency, 5A (8A breakaway current) Input voltage and frequency, 5A (8A breakaway current) - -

Motor power supply Motor power supply Motor power supply Not connected safety ground

MDT-J25 1 2 3 4 5

1 2 3 4 5

Input Input - Input Input

NA Cont. NA Cont. Shield NC Cont. NC Cont.

0 - 26Vcc 0 - 26Vcc 0 - 26Vcc 0 - 26Vcc

Normally open motor thermal protection contact Shield Normally closed motor thermal protection contact

MDT-J26 1 5

1 5

Output Output

L3 Phase L2 Phase

230V -18% / +10% , 48-62Hz 230V -18% / +10% , 48-62Hz

ALM card power supply ALM card power supply

Table II-F: MDT card connections for three-phase +neutral 400V power supply

Connector Pin Label Input/ Output

Type Range /Max. value Function

MDT-J23 1 2 3 4 5

1 2 3 4 5

- - Input Input Input

Ground Neutral L3 Phase L2 Phase L1 Phase

- - 400V -18% / +10% , 48-62Hz 400V -18% / +10%, 48-62Hz 400V -18% / +10%, 48-62Hz

safety ground PE Neutral Power supply Power supply Power supply

MDT-J24 1 2 3 4 5

1 2 3 4 5

Output Output Output - -

W Phase V Phase U Phase - Ground

Input voltage and frequency, 5A (8A breakaway current) Input voltage and frequency, 5A (8A breakaway current) Input voltage and frequency, 5A (8A breakaway current) - -

Motor power supply Motor power supply Motor power supply Not connected safety ground

MDT-J25 1 2 3 4 5

1 2 3 4 5

Input Input - Input Input

NA Cont. NA Cont. Shield NC Cont. NC Cont.

0 - 26Vcc 0 - 26Vcc 0 - 26Vcc 0 - 26Vcc

Normally open motor thermal protection contact Shield Normally closed motor thermal protection contact

MDT-J26 1 2

1 2

Output Output

L3 Phase Neutral

230V -18% / +10% , 48-62Hz 230V -18% / +10% , 48-62Hz

ALM card power supply ALM card power supply

MDT - 400Vac: ALM card power supply: pay attention to the connections at connector J26, illustrated in the figure: power supply to card ALM (230V) uses one input phase and the neutral connection. WARNING! incorrect connection may cause permanent damage to the ALM card.

Page 48: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 42

Dimensioning of the motor: the voltage and frequency values of the motor must correspond to the mains voltage available. The current limit values are shown in the table.

Motor overload protection: to safeguard the motor, it must be fitted with a suitable thermic relay or a magnetothermic switch (see the diagram shown in the figure)

Fig. II-37b: motor protection. connection of a normally closed contact

Fig. II-37c: motor protection. connection of a normally open contact: note the jumper on contacts 4 and 5 of connector J25.

MDL card ( ATTENTION: 230V 1~ only! )

Fig. II-37e MDL card connections. Table II-G: MDL card connections

Connector Pin Label Input/ Output

Type Range /Max. value Function

MDL-J6 1 2 3 4 5

ground ground U V W

- - Output Output Output

ground ground U phase V phase W phase

- - 230V – 2,7A (6 A max breakaway current) 230V – 2,7A (6 A max breakaway current) 230V – 2,7A (6 A max breakaway current)

Shield Protection ground PE motor power supply motor power supply motor power supply

The power supply voltage to the Conveyor Control System with ALM card must be within the range 230Vac ± 10%, 48-62Hz .

Motor overload protection: the motor is protected from overload directly by the card software:: select the motor nominal current value for parameter CU (see Programming section).

WARNING! Do not connect the cable shielding at the motor end.

Page 49: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 43

Operation of the relays (J15 and J19 connectors)

Ejector relay (Eject relay): Programmable relay with delayed action (with respect to the detector alarm); capacity; the programming parameters that relate to the functioning of this relay are ED, EM and ET (see Programming chapter).

Alarm relay programmable relay with immediate action (with respect to the detector alarm); capacity; the programming parameter that relates to the functioning of this relay is AT.

Malfunction relay (Fault relay) Safety operation relay (contacts NA and C connected in correct operation); capacity; the programming parameter that relates to the functioning of this relay is FR. Malfunction conditions are described in the Maintenance section. N.B.: when the device is switched on, the relay is not activated (malfunction condition) for about 6 seconds.

Upstream belt authorisation relay (Preceding conveyor relay) Safety operation relay (contacts NA and C connected in correct operation); capacity 3A.

Auxiliary relay for signalling when periodic test is due (TEST LAMP relay) Programmable relay ; 3A current-carrying capacity ; the programming parameters relating to operation of this relay are LB and the parameters of the QA configuration menu (see Programming section).

Timing

Belt blocking with manual alarm reset (EM=B) Operation with halting of the production line, manual elimination of the contaminated material and manual reset by the operator. N.B.: The metal detector does not check if there are any subsequent fragments in the material immediately following: all material under the probe must therefore be eliminated along with the part that caused the alarm. To minimise waste of material it is advisable to select a low setting for the ED parameter. Product: loose or packaged Models: All models except THS/PH

Conveyor Control System power supply unit Signal Waveform Function

Preceding conveyor relay

Alarm relay

Ejection relay*

Stop/start/reset button

Output OUT1

Upstr. belt authorisation Signalling Belt block Alarm reset/Restart Buzzer/flashing light

Fig. II-38a *:output not activated if MDT or MDL module is fitted

Control Power Box power supply unit Signal Waveform Function

Alarm relay

Ejection relay

Stop/start/reset button

Output OUT1

ED/BS

Signalling Belt block Alarm reset Buzzer/flashing light

Fig. II-38b N.B.: BS = transit speed

Belt blocking with photocell synchronisation and manual alarm reset (EM=SB) Operation with halting of the production line synchronised by photocell, manual elimination of the contaminated material and manual reset by the operator. Allows precise positioning of the material to be rejected.

Page 50: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 44

N.B.: The metal detector does not check if there are any subsequent fragments in the material immediately following: all material under the probe must therefore be eliminated along with the part that caused the alarm. To minimise waste of material it is advisable to select a low setting for the ED parameter. Product: loose or packaged Models: All models except THS/PH

Conveyor Control System power supply unit Signal Waveform Function

Preceding conveyor relay

Alarm relay

Ejection relay*

Stop/start/reset button

Output OUT1

Upstr. belt authorisation Signalling Belt block Alarm reset/Restart Buzzer/flashing light

Fig. II-39a N.B.: *: output not activated if MDT or MDL module is fitted

Control Power Box power supply unit Signal Waveform Function

Alarm relay

Ejection relay

Stop/start/reset button

Output OUT1

ED/BS

Signalling Belt block Alarm reset Buzzer/flashing light

Fig. II-39b N.B.: BS = transit speed

Automatic ejection with alarm synchronisation (EM=F) Operation with automatic set-aside of contaminated material. The set-aside method can vary: an ejector may be used – without halting the production line – or the material can be eliminated by using a retractable belt or by inverting the direction of the belt. This application is typically used for loose material. The mode allows the following settings to be selected:

–- alarm relay activation time (AT parameter); – ejection distance (ED parameter); – selection of activation time of the ejection relay (ET parameter).

Product: loose Models: All models except THS/PH

Signal Waveform Function Preceding conveyor relay

Alarm relay

Ejection relay

Output OUT1

ED/BS ET

t1

t1

None Signalling Ejection Ejection

Fig. II-29c N.B.: NOTE: BS = transit speed

Parameter AT is set to automatic (AT=A); t1= alarm time, generally corresponding to the transit of the metal mass through the probe.

Page 51: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 45

Model THS/PH This model uses a dedicated line (OUT2) instead of the ejection relay. N.B.: standard values for parameters ED and AT are ED=0 and AT=A.

Signal Waveform Function Preceding conveyor relay

Alarm relay

Ejection relay

Output OUT2

ED/BS ET

t1

t1

None Signalling Ejection Ejection

Fig. II-29d N.B.: BS = transit speed. t1= alarm time, generally corresponding to the transit of the metal mass through the probe

Automatic ejection with photocell synchronisation (EM=S) Operation with automatic set-aside of contaminated material, synchronised by photocell. Very similar to the above application, this mode can be used for packaged products. The mode allows the following settings to be selected:

– alarm relay activation time (AT parameter); – ejection distance (ED parameter); – selection of activation time of the ejection relay (ET parameter); – selection of the distance between metal detector and photocell (PD parameter). – selection of the position of the photocell (PH parameter)

Product: packaged Models: All models except THS/PH Photocell at entrance

Signal Waveform Function Photocell

Alarm relay

Ejection relay

Output OUT1

ED/BS ET

AT

Synchronisation Signalling Ejection None

Fig. II-29e N.B.: BS = transit speed Photocell at exit

Signal Waveform Function Photocell

Alarm relay

Ejection relay

Output OUT1

ED/BS ET

AT

Synchronisation Signalling Ejection None

Fig. II-29f N.B.: BS = transit speed

Page 52: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 46

Serial line connection (J3 and J4 connectors) Connect the serial communication cable to the terminal board: contacts for both RS485 and RS232 standards are catered for. The RS 485 connection allows: • long-distance connection of a personal computer to a THS metal detector • connection of a personal computer to several metal detectors linked in a network The RS 232 connection allows: • connection of a personal computer to a single THS metal detector only • connection of a printer fitted with a serial interface

RS 485 connections

personal computer THS

TX-TX+RX+RX-

RX-RX+TX+TX-

6543

J4 Fig. II –40a

personal computer

TX-TX+RX+RX-

RX-RX+TX+TX-

6543

TX-TX+RX+RX-+

6543

THS 2

THS 1J4

J4

to the next THS

Fig. II –40b

RS 232 connections THS personal computer (25p)

RX (SI)TX(SO)

GND

TXRX

GND

235

237

J6

THS personal computer (9p)

RX (SI)TX(SO)

GND

TXRX

GND

235

325

J6

Fig. II –41a

THS printer (25p)

RX (SI)TX(SO)

DTRGND

TXRX

DTRGND

2365

23207

J6

THS printer (9p)

RX (SI)TX(SO)

DTRGND

TXRX

DTRGND

2365

3245

J6

N.B.: Select DTR=H mode on the THS

Fig. II –41b

Page 53: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 47

Inputs

Make all connections relating to input lines using screened cable, connecting the shielding only at the THS system end to the contacts marked with the symbol which are provided on the various connectors.

Bar-code reader The bar-code reader is supplied upon request: for connection, follow the indications in the plan on the previous pages.

Downstream belt authorisation (Following conveyor - Conveyor Control System only) When active, this input indicates that the downstream belt is operating and can accept the product.

Photocell When active, this input indicates the passage of the product in front of the photocell. The input is monitored by the self-diagnosis system.

Ejection confirmation (Eject confirmation) When active, this input indicates the passage of the product into the set-aside container. The input is monitored by the self-diagnosis system.

Container full (Full bin) When active for at least 5 seconds, this input indicates that the set-aside container is full (the malfunction relay is activated).

Impulse encoder (Encoder) This input is used to measure the speed of the conveyor belt if an encoder has been installed. The sensor must provide impulses, the amplitude of which is indicated in the table “Electrical connections”, with a minimum frequency of 2 Hz and a maximum frequency of 1kHz. It may be contact type, open collector (NPN o PNP) or push-pull. For correct operation a coefficient KE must be determined during installation and set-up, as per the procedure described in the para. “ Transit speed “.

Alarm reset (Reset) When active, this input forces the Metal Detector to exit from the alarm state (used in the case of operation with belt block and manual reset).

Inhibition When active, this input disables the detector: it is generally used to avoid false alarms caused by the start-up of the conveyor belt when it is not possible to adjust the mechanical structure of the belt. Alarm inhibition when belt is switched on If the start-up of the belt is accompanied by interference which is serious enough to cause a false alarm, the alarm can be inhibited: • Control Power Box:

• connect a contact which is activated at start-up to the inhibition input; • set the IN parameter to a suitable value determined by experiment (see “Programming” section).

• Conveyor Control System: simply set the IN parameter to a suitable value determined by experiment (see

“Programming” section).

Air pressure sensor When active, this input indicates that the compressed air pressure is sufficient for the ejector.

Container absent (Bin absent) When active for at least 5 seconds, this input indicates that the set-aside container is not in its place (the malfunction relay is activated).

Page 54: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 48

Operating instructions

List of preliminary checks If the equipment is being switched on for the first time, some checks must be carried out and the value of some operating parameters must be set. These operations, which are listed on the first page of the INSTALLATION section, are described in the subsequent paragraphs in this section.

Operations during use and areas of competence The system is designed to be managed by 6 different operators with different areas of competence:

• operator • supervisor • engineer • quality-control operator • head of quality control • remote programmer

Access to programming differs between the various types of user (operator, supervisor, etc.) according to the following table (see Programming section). Operation to be carried out Programming access

level Parameters or menus used

• Adjustment of sensitivity Operator (if enabled) Sensitivity Parameter

Supervisor Engineer

Product Menu

• Choice of product Operator Product Parameter

Supervisor Engineer

Product Menu

• Memorisation of new products • Autolearn • Counter management

Supervisor Engineer

Product Menu Autolearn Menu Counter Menu

• Setting up periodic tests and test reports

Head of quality control

MD Test Menu QA Configuration Menu

• Carrying out periodic tests Quality-control operator Head of quality control

Test MD Menu

• Printing test reports Head of quality control

Print Menu

• Setting detection and ejection parameters

Supervisor Engineer

Rec. parameters Menu (receiver) Ejec. parameters Menu (ejector)

• Setting of installation parameters Engineer Barcode reader Menu THS Configuration Menu ALM Configuration Menu

• Checking of status of sensors and actuators

Engineer I/O Status Menu

* menu available only when a barcode reader is fitted. N.B.: all the parameters shown in the table are accessible in remote mode

Page 55: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 49

Controls and indicators

Power switch On the Conveyor Control System model, the On/Off switch is located on the power supply unit cover; in the case of the Control Power Box, an external switch must be fitted.

Fig. III-1a - Conveyor Control System

Fig. III-1b - Control Power Box Fig. III-1b - Control Power Box in the version for the THS/G

Control panel of the probe/electronics unit The control panel, containing the optical indicators and the metal detector controls, is located on one side of the electronics unit:

Control panel

A POWER a green indicator indicates the presence of power

B ALARM a red indicator indicates the metal detector alarm (detection of a metal fragment or breakdown)

C Alphanumeric display

4 lines, of 20 characters each, display the messages relating to use, programming and self-diagnosis of the device

Acoustical indicators In the Power Control Box is included an acoustical indicator that is activated in case of alarm for the detection of metallic fragments, for the signalization of a fault or for the request of an operator intervention.

Switch

Page 56: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 50

Controls The control of the Metal Detector and the setting of the device parameters are performed through the control panel keyboard, as shown below:

Key Function

Access and exit from the programming phase

Return back from the submenus to the main menu Exit from the Metal Detector Status visualization

Scroll through the sequence of instructions

Choice of the parameters to be changed Modification of the parameter values

Metal Detector Status visualization

Selection of the selected submenu from the main menu

Confirmation of the data entered Reset of some kinds of fault

Conveyor Control System power supply unit control panel On the power supply unit Conveyor Control System, the container cover incorporates a motor control panel. In the case of operation with stopping of the belt and manual resetting, the motor start/stop button also functions as the alarm reset. The motor speed control keys have different functions depending on the version. Fixed-speed Conveyor Control System

Status of motor Key Motor on Motor off

No function Manual advance *

No function Manual reverse *

* if parameter MM = ON Variable-speed Conveyor Control System

Parameter MM = OFF Parameter MM = ON Status of motor Status of motor Key

Motor on Motor off Motor on Motor off

Increase in speed No function No function Manual advance

Decrease in speed No function No function Manual reverse

Fig. III-3: commands and indicators on the power unit with inverter card Conveyor Control System

Scheda MDL Power indicator

Motor malfunction indicator

Metal detector alarm indicator detector

Motor on indicator

Motor off indicator

Speed increase button

Speed decrease button

Motor start/stop and alarm reset button

Page 57: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 51

Visible/audible alarm signalling device The signalling device comprises a flashing light and a buzzer. The sound volume and the type of sound can be selected via minidips.

1 volume & sound selectors

Fig. III-4

Switching on the metal detector

If the device is stored for a long period in temperatures outside the operating range, wait for the temperature of the detector to come back within that range before switching on Power supply unit There are dangerous voltages inside the power supply unit. Close the cover and keep the key safe so that it is onlyavailable for use by trained personnel (Regulation EN 60204) Conveyor belt motor The motor can reach high temperatures during use: do not touch the motor or bring inflammable materials close to itwhile it is operating or immediately afterwards. Ensure that the cooling air intakes are not obstructed, and that there is free air circulation WARNING: do not set the motor in motion without the conveyor belt: this may lead to damage due to excess revolutionsand consequent overheating.

Checking the safety features Before switching on, check that the safety devices with which the system is fitted are in good condition: 1. rollers: protection crankcase for the pin 2. rollers: lower protection panels 3. ejector: protection panels (if fitted) Also check operation of the emergency button with the belt in motion.

Fig. III-5 roller safety protection

1

3

1

3 2

3

2

1 1

Page 58: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 52

It is strictly forbidden to start up the system if all safety features are not properly functional. Tampering with the safety features is also forbidden, and voids all responsibility of the manufacturer for any damage caused.

Keep the power supply unit panel closed. The key must always be in the possession of an authorised person.

Fig. III-6

Signals at power-up The detector is designed to be switched on directly from the electrical panel that controls the production line. The power supply unit does however contain an auxiliary switch I2, which is normally in the ON position.

The presence of mains power supply is signalled by the lighting up of the indicator located on the control panel (Conveyor Control System) ... Fig. III-7a

... or of the green LED L2 located on card ALM, near switch I2 (Control Power Box). Fig. III-7b

When it is first powered up, the Metal Detector’s configuration includes 5 factory-set passwords (shown in the test card at the end of the manual). It is extremely important that the person in charge of the detector modifies the passwords in order to avoidunauthorised access to programming.

When the device is turned on, the display lights up, as do the indicators located on the front of the electronics unit. More specifically, the display shows, in sequence, the serial number and the version of the software program that drives the power supply unit; after that the following is displayed:

THS V3.xxx Product productname |

Fig.III-8

in which: THS identifies the model

V3.xxx identifies the software version of the metal detector

productname indicates the type of programming, specific to one product, which may be chosen from among 250 stored sets, of which 249 can be defined by the user (see Programming chapter); each stored programming set is customised and relates to a specific product to be monitored.

Signals given during use

On models where there is a control panel on both the probe and the power supply unit (because the probe is installed in a position which is inaccessible to the operator), the electronics unit display is disabled (the message “Disabled” appears).

Indication of the received signal On the fourth line of the display the signal being received is displayed by means of a horizontal illuminating bar, subdivided into 20 sections. When the signal increases, the bar extends towards the right. The alarm threshold corresponds to 10 illuminated sections: the sections from 1 to 10 are bars, those from 11 to 20 are asterisks

I2 L2

Page 59: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 53

THS V3.xxx

Product productname | | |

THS V3.xxx Product productname | | | | | | | |

THS V3.xxx Product productname | | | | | | | | | | * * * * *

Fig.III-9a. Example: signal well below the threshold level

Fig.III-9b. Example: signal just below the threshold level

Fig.III-9c Example: signal above the threshold level (alarm).

Checking for environmental electromagnetic interference The THS Metal Detector has very high immunity to electromagnetic interference. However, it may happen that electrical devices, usually power devices, cause interference which is strong enough to lead to false alarms. To identify these sources of interference the indication of the signal received from the probe, which the detectors normally shows on the display, can be used. Under normal conditions, the indication on the display should correspond to that in Fig. III-9a.

Display Messages The Metal Detector display shows messages relating to its current mode of operation:

DISPLAY MEANING

THS V3.xxx Product productname |

Normal functioning The Metal Detector is in normal operating mode: On the fourth line of the display the signal being received is displayed by means of a horizontal illuminating bar, subdivided into 20 sections. When the signal increases, the bar extends towards the right.

THS V3.xxx Product productname | | | | | | | | *

Metallic mass detection The Metal Detector is in normal operating mode: it has just detected a metal object and activates connected slave devices. The alarm threshold corresponds to 10 illuminated sections: the sections from 1 to 10 are bars, those from 11 to 20 are asterisks.

access code

000000

Programming access phase The Metal Detector requests a password to be entered.

Sensitivity 265 <- Products

Programming The Metal Detector has been set to programming mode: accessible parameters can be modified.

**TEST** Product productname |

Test procedure The Metal Detector requires an operational test to be carried out (see “Periodic test management” section in this manual).

**BIN FULL** Product productname |

Self diagnosis The device, when a possible functional problem is detected, shows on the display the problem kind and utters the alarm signal, asking for the intervention of the operator.

Page 60: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 54

Display of the status of the Metal Detector

If the (increase) key is pressed when the display shows normal operation, a list of information relating to the Metal Detector’s status is shown: THS/M

THS/MN V3.xxx

Product productname

|

Sensitivity 265 Cur Alar. 10 Cur. Obj. 156 Time 12:34 Date 24/10/97 Next test 15:00

Fig. III-11a Other THS models:

THS V3.xxx

Product productname

|

Sensitivity 265 TX program 0 Cur Alar. 10 Cur. Obj. * 156 Time 12:34 Date 24/10/97 Next test 15:00

Fig. III-11b * not present on THS/G models

Use of the conveyor belt

Starting/stopping the conveyor belt With the correct power supply and with the motor stopped, check that the LED indicators are on or off as shown in the following table:

Indicator Status mains voltage on motor on off motor off on motor malfunction ! M off metal detector alarm ! off

• Press the start/stop button to switch on the motor: check that it starts up, and that the “motor

on” indicator comes on and the “motor off” indicator goes off.

• To stop the motor press the start/stop button again: check that it stops, and that the “motor

on” indicator goes off and the “motor off” indicator comes on.

• Fixed-speed Conveyor Control System: check the manual movement of the motor using the and keys (if parameter MM=ON).

Adjustment of the belt speed The motor speed control keys have different functions according to the value of parameter MM (see Programming section). The speed of the conveyor belt can be adjusted by: • programming the BS parameter on the metal detector • simply pushing the keys located on the Conveyor Control System, if parameter MM=OFF.

N.B.: during programming of the metal detector, the Conveyor Control System keypad is disabled. Vice-versa, while the Conveyor Control System keys are being used, metal detector programming is disabled.

Page 61: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 55

Display of the metal detector

Keypad of the Conveyor Control System

Comment

Belt lower sp. 20 Belt speed 40 <- Belt maximum sp. 60

The “Speed” reading indicates the speed set, and varies

in real time when the and keys are pressed. Any variation in speed is memorised as a parameter specific to the current product type.

Emergency button An extra emergency button is mounted on the conveyor belt to stop it in case of malfunction or danger.

If necessary, the main system switch can also be used for this purpose. Display

Control Comment

* * EMERGENCY * * Product productname |

emergency button

The alarm indicators are activated

Automatic stop If nothing passes through the metal detector for the length of time set by parameter ST (see Programming section), the conveyor belt stops automatically.

Alarm reset In the case of an alarm, the contaminated product is ejected from the product conveyor according to the type of operation which has been selected: • in operation with automatic ejection, the belt is not stopped and the contaminated product is sent into a set-aside

container which should be emptied periodically by the operator. In this case, the detector resets automatically. • in operation where the conveyor belt is blocked, the belt is stopped and the contaminated product is positioned in the

exit area of the metal detector for manual removal by the operator (N.B. all material between the probe and the stop line must be removed!).

S

N

fig. III-13

In this case, the belt only restarts when the operator pushes the appropriate button. In the case of the Conveyor Control System, this button is incorporated into the control panel:

Action Indicators and results

press once to reset the metal detector alarm the metal detector alarm indicator goes off

press again to restart the motor the motor restarts

Automatic operation using a bar-code reader The THS system can, upon request, incorporate a bar-code reader for automatic selection of the specific parameters of the product in transit. This avoids having to halt the production line frequently. The reader is installed upstream of the probe so as to read a code stencilled on the pack. If the code is recognised, the reader sends a command to the metal detector to select the analysis programme.

If the code is not recognised due to lack of legibility or because it is not on the list of enabled codes (see parameter CD in the Programming section), the reader does not send any signal to the metal detector and the analysis program remains that selected for the last pack). In this case, also, the pack can be expelled automatically from the production line by enabling parameter NE When the metal detector receives the signal to change product type, an internal adjustment procedure is activated the length of which determines the minimum distance between two packs with different codes, that is to say containing different products. This distance is as follows:

Page 62: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 56

THS/3F

with change of band (BA parameter) between one product and the other

D min = (probe length) + 3000 mm

THS/3F without change of band (BA parameter) between one product and the

other

D min = (probe length ) + 300 mm

Other THS models

D min = (probe length ) + 300 mm

Attention must be paid to the position of the pack, or rather of the label, while in transit: this should be parallel to the direction of transit so as to ensure that the barcode is legible.

Photocell self-diagnosis If the photocell is in a continuously active state for a long period, this is interpreted as a malfunction of the sensor by the self-diagnosis system. There are many possible causes (wrong position, short-circuited wiring etc.). For details see the “Self-diagnosis” paragraph in the Maintenance section.

On systems without encoder or with the Control Power Box, it is the installer’s and operator’s responsibility to ensure that material does not remain in front of the photocell when the belt is stopped: if it does, the photocell will be continuously active even though it is not malfunctioning. If the foregoing situation can not be avoided, it is advisable to disable photocell self-diagnosis (Parameter PA)

Programming the metal detector according to the kind of product The operating mode of the metal detector according to the kind of product is determined by the following parameters:

• TX program (TP parameter) except for THS/MN • Sensitivity (SE parameter) • Analysis mode (AM parameter) • Band - only on the THS/3F multi-frequency model (BA parameter)

The factory settings are suitable for dry products (biscuits, pasta, dry frozen food,...). We would remind you that:

• in the case of products with "difficult" characteristics, it is advisable to call CEIA's Technical Department in order to request production of specially-designed equipment.

• it is always advisable to optimise installation in line with the criteria described above in order to obtain maximum sensitivity and maximum rejection of environmental interference.

Procedure for minimising the "product effect" The goal of this procedure is to obtain the following operating mode:

a the detector does not set off an alarm when the conveyor system is active and some of the pure product, without any metallic contamination (with aluminium tray onTHS/MN), passes through the probe.

b the detector sets off an alarm when some of the product containing a metallic sample passes through the probe

It is important to make sure that the product always passes through the probe at the same point and with the same orientation, in order to obtain the best results from this procedure: Procedure for automatic product acquisition (not applicable to the THS/M model) This procedure comprises the automatic acquisition of product characteristics in order to identify the contribution to the received signal due to the metal mass to be detected. The characteristics are acquired progressively by making the product pass through the metal detector several times. The procedure alters the settings of the following parameters:

• SE and TP, if TN>1 (only SE on THS/MN) • Only TP if TN=1 • BA, on model THS/3F if MB=ON

The procedure must be completed once started. Do not change any parameter setting during the procedure. 1 It is advisable to create a new product using the command New P. 2 Set the Analysis Mode parameter to a suitable value (see the “Analysis Mode Selection Criteria” section). In the

case of the THS/3F model, the correct value of the MB parameter must be selected (ON: autolearn with automatic selection of the operating band; OFF: autolearn with operating band pre-set using the BA command). In the case

Page 63: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 57

of multi-band operation(MB=ON), select the desired value for the OS parameter. 3 Set “Autolearn=ON”. Exit from the programming phase and follow the display instructions. 4 Make the product pass several times through the metal detector, according to the value of the Transits

parameter (N.B.: in the case of loose product, the device automatically proceeds to analyse it correctly). N.B.: in the case of model THS/3F, if MB=ON, carry out 3 x TN transits, with TN=2,3.... The message “Pass product” appears on the display, and the buzzer is activated (if enabled).

5 At the end of the transits the detector exits from the autolearn phase and the standard message appears on the display.

6 Final operating check 6.1 Pass some pure product through the detector: the device should not set off any alarm.

6.1.1 Pass some of the product with a metallic sample: the detector should give an alarm. In such a case, the procedure has been successfully concluded.

6.1.2 Otherwise, increase sensitivity and check that the bar-graph indication is not higher than 8 points during the transit of uncontaminated product.

6.2 If the detector gives an alarm whenever some of the pure product passes through the probe, decrease the “Sensitivity” parameter until the detector does not give an alarm (this is probably due to non-uniformity of the product).

7 If a periodic test on the product is required, set the effective diameter of the metal mass used in the relevant parameter in the MD Test menu: parameter FD if the sample is of ferromagnetic metal, parameter SD if stainless steel, or parameter ND if diamagnetic. In this way, the test report will show this value next to the result of the test carried out.

N.B.: if the product can vary significantly in its electromagnetic characteristics, adjust parameter SA (Sensitivity Adjustment)

Page 64: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 58

Analysis mode selection criteria The THS detector offers the possibility of choosing between three different types of detection, using the command Analysis mode AM: Selection criteria

Preferential applications Analysis mode AM THS/M Other THS models

2

always

Distance between products at least 1.5 times the depth of the tunnel (DL ).

3

not applicable

Distance between products can be less than 1.5 times the depth of the tunnel (DL) with product characterised by a

TP setting (from autolearn procedure) in the range 200 to 1000.

4

not applicable Reserved

5

not applicable Reserved

6

not applicable As analysis mode 2, with improved immunity against vibrations

7

not applicable As analysis mode 3, with improved immunity against vibrations

In each case it is advisable to check operation with all types of detection, and to choose the one which provides the highest level of sensitivity.

Page 65: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 59

Sensitivity check with reference sample It is important to check proper operation (sensitivity and ejection of material) of the metal detector periodically by carrying out a sensitivity test with a reference sample.

Test using a sample defined by the customer The reference sample is identified at the end of the installation phase based on the customer’s specifications; the

sensitivity, trajectory and orientation of the sample must be noted if it is not spherical. This sample should be kept under constant conditions, and is used periodically for the test, which should be carried

out under the same conditions as the end-of-installation test.

Test using a CEIA sample The reference sample is one of the CEIA spherical samples available in various sizes and in three types of metal

(ferrous, non-ferrous and stainless steel) Determine by experiment the sensitivity needed to detect the sample, or carry out the procedure for minimising the

product effect Enter the diameter of the sample in the FD parameter (or SD, or ND, depending on the type of metal used) Set the intervals and the waiting period for carrying out the test, and whether or not the malfunction relay is activated

if the test is not performed (see QA Configuration menu)

Periodic test management At the end of the period Test interv. (from when the metal detector is switched on), a message requesting a test is displayed:. ( this can also be signalled via an optional lamp). The check can be carried out either by the Quality-control Operator or the Head of Quality Control. N.B.: to exclude the reminder to carry out the test periodically, set parameter Test int.= 0.

** TEST ** Product productname | |

Test procedure The procedure described below refers to the FE test; the other two tests follow the same procedure.

Display Comment

Test FE < Test SS Test Non-FE

Enter programming phase, select Test FE function and press

key.

Test FE WAIT < Test SS Test Non-FE

Wait

Test FE PASS < Test SS Test Non-FE

Pass a sample through the probe within 20 seconds.

TEST SAMPLE

Test FE OK < Test SS Test Non-FE

The positive outcome is recorded in memory.

TEST SAMPLE

Page 66: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 60

If the test fails, one of the following messages will be seen at point 4:

Display Comment

Test FE NULL < Test SS Test Non-FE

The sample is considered too large to carry out a valid test, with a signal amplitude >400% of the SE alarm threshold. The result of the test is recorded as NO.

Test FE NO < Test SS Test Non-FE

Possible causes: - No transit has been detected for 20 seconds - The signal from the sample is below the SE alarm

threshold - Three consecutives passages were giving negative result - The system of ejection is enabled, but ejection has not

been confirmed via the “ejection confirmation” input The outcome of the test, whether positive or negative, is always stored in memory.

In the case of abnormal operation, carry out a test using the sample indicated on the Configuration Sheet enclosed with each unit after selecting the “default” product.

Page 67: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 61

Programming

General points on programming The control of the Metal Detector and the setting of the device parameters are performed through the control panel keyboard, as shown below:

Key Function

Access and exit from the programming phase

Return back from the submenus to the main menu Exit from the Metal Detector Status visualization

Scroll through the sequence of instructions

Choice of the parameters to be changed Modification of the parameter values

Metal Detector Status visualization

Selection of the selected submenu from the main menu

Confirmation of the data entered Reset of some kinds of fault

A password is requested upon entry to programming mode. When it is first powered up, the Metal Detector’s configuration includes 6 factory-set passwords (shown in the following table). The standard values are:

Access level Password Operator 000001 Supervisor 000002 Engineer 000003 Control Quality Operator 000004 Head of Control Quality 000005 Remote programming 000006

Every level of programming allows access to various groups of operating parameters.

Only the engineer and the remote programmer can alter the passwords to the various levels.

It is extremely important that the person in charge of the detector modifies the passwords in order to avoid unauthorised access to programming.

Programming mode is accessed by pressing

key . The Metal Detector requests a password to be entered:

Access Code

000001

The password is entered by selecting one character at a time via the and keys, confirming each selection with

the key. After the password has been entered, access to programming is given, and the display shows the parameters available for the programming level.

Page 68: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 62

Example of display output during operator-level programming.

Sensitivity 265 <- Products

Parameter name

Parameter value

Cursor

Example of display during programming: supervisor level.

Products -> Autolearn Detection Ejection

Parameter name

Cursor indicating presence of submenu

- The parameters are selected via the (increase) and (decrease) keys, and are activated via the

(Enter) key: when this happens, the current setting begins to flash.

- Submenus are selected via , and accessed via

- The parameter settings are modified via

- The modifications are confirmed by pressing

- Returns to the previous menu and exits from programming mode via .

If the sensitivity value does not begin to flash after has been pressed, it means that the parameter in question is not accessible from the current programming level. The product named “Defalut” cannot be modified.

Every level of programming allows access to various groups of operating parameters, as shown in the following table:

Livello Menu / Comandi disponibili 1 Operator level Sensitivity

Products

2 Supervisor level

Products Autolearn Detection Ejection

Ejection time Counters

3 Engineer level

Products Autolearn Detection Ejection Counters Bar-code reader* THS Configuration

Date setting Change password

ALM Configuration I/O status

4 Quality Control operator level MD Test

5 Head of Quality Control level

MD Test Print

Print report Q-C Config.

Test sensitivity 6 Remote programming level All the commands at Engineer and Head of Quality Control levels.

* menu available only when a bar-code reader is fitted.

The structure of the programming menus is tree-type. The individual parameters are described in the “Programming Instructions” table, along with the menu/submenu sequence via which they can be selected.

Page 69: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 63

Every level of programming allows access to various groups of operating parameters, as shown below:

Operation Programming access level Parameters or Menu used Operator (if authorized) Sensitivity parameter Sensitivity adjustment Supervisor, Engineer Products Menu Operator Product parameter Product choice Supervisor, Engineer Products Menu

Storing of new products Autolearn Counters management

Supervisor, Engineer Products Menu Autolearn Menu Counters Menu

Setting of periodical tests and test reports Head of Quality Control MD Test Menu

QA Settings Menu

Performing of periodical tests Quality Control Operator Head of Quality Control MD Test Menu

Print of Test reports Head of Quality Control Print Menu Settings of detection and ejection parameters Supervisor, Engineer Detection Menu

Ejection Menu

Settings of Installation parameters Engineer THS Configuration Menu ALM Configuration Menu

Control of Sensors and Actuators status Engineer I/O Status Menu

Programming instruction

Products menu Remote Possible settings Standard setting Parameter

Prod. PI 12 alphanumeric characters - Global

Description Models

Type of product selected Selection of a product previously entered and saved. Local programming The various defined products are shown on the display when the arrow keys are pressed. Choose the desired product by pressing the key. Remote programming This command displays the list of products: the current product is shown by the “>” cursor. To change the current product, assign the corresponding value to the PI setting.

Example:

#PI<ENTER> Default Prod_A > Prod_B Prod_C #PI=Prod_A<ENTER> #PI<ENTER> Default > Prod_A Prod_B Prod_C #

All models

Remote Possible settings Standard setting Parameter

P.Name PN 12 alphanumeric characters - Related to the current

product Description Models

Product name Changes the name of a product already in memory.

Note: always enter 12 characters (including spaces). Select each character via the

(increase) e (decrease) keys and confirm by pressing the (ENTER) key.

All models

Remote Possible settings Standard setting Parameter

New P. NW 12 alphanumeric characters - Related to the current

product Description Models

Name of a new product Create a new product. The initial parameters of the new product will be the same of the product selected when the new product is created. Up to 249 products can be created.

Note: always enter 12 characters (including spaces). Select each character via the

(increase) e (decrease) keys and confirm by pressing the (ENTER) key.

All models

Page 70: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 64

Remote Possible settings Standard setting Parameter

Erase EP 12 alphanumeric characters - Related to the current

product Description Models

Elimination of a product Elimination of an existing product: select the desired product in the list displayed using the arrow keys, and confirm with the key.

All models

Autolearn menu Remote Possible settings Standard setting Parameter

Autolearn LE ON / OFF OF-F Global Description Models

Autolearn Select ON and exit from programming to activate the autolearn procedure. The parameter returns to OFF automatically at the end of procedure. See paragraph “Programming the metal detector according to the kind of product” in the Instructions manual.

All models

Remote Possible settings Standard setting Parameter

Optimise SS OS ON / OFF ON Global Description Models

Inclusion of stainless steel in the metals for which the signal/product ratio is optimised ON: frequency optimisation for stainless steel; OFF: frequency optimisation for iron Signal/product ratio: metal signal / product signal. This parameter operates only during autolearn, if MB=ON.

THS/3F

Remote Possible settings Standard setting Parameter

Multi-band MB ON / OFF OFF Global Description Models

Multi-band ON: autolearn with automatic selection of the operating band; OFF: autolearn without modification of the current operating band (BA). See paragraph “Programming the metal detector according to the kind of product”.

THS/3F

Remote Possible settings Standard setting Parameter

Transits TN 1 – 10 2 Global Description Models

Number of product transits for autolearn In the case of non-uniform products, increase TN so as to obtain a more accurate mean. If TN=1 the autolearn will change only the TP value. If TN>1 the autolearn will change both TP and SE. The number of product transits requested for autolearn is 3xTN. Selecting MB=ON. On THS/3F with MB=ON, if TN=1 the value is automatically changed to 2.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

Sensitivity adj. SA 10 – 30 15 Global Description Models

Margin of sensitivity Margin of sensitivity below the limit used to set SE during the autolearn procedure: by lowering the sensitivity, false alarms are avoided in the case of significant variations in the characteristics of the product. If the value of SA is increased, the sensitivity determined by the autolearn procedure decreases. The standard value of 15 corresponds to a ratio of 2 between the effective signal (alarm signal) and the interference due to the product.

All models

Page 71: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 65

Detection menu Remote Possible settings Standard setting Parameter

Sensitivity SE 0 - 299 - Related to the current product

Description Models

Sensitivity Alarm trigger threshold: the smaller the object to be detected, the greater the sensitivity must be. The parameter can be modified at operator level if parameter OA=ON

All models

Remote Possible settings Standard setting Parameter

TX program TP 0 - 1799 0 Related to the current product

Description Models

Analysis parameter of received signal This parameter determines the optimum point of operation to minimise the signal generated by the product, and is set automatically by the detector during the autolearn process. For example, for a dry product the choice of TP=0 is the optimum, for a wet product a value around 900 is the optimum.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

Band BA High / Medium / Low High Related to the current product

Description Models

Operating band High: high band; Medium: medium band; Low: low band. Parameter determined automatically by the system during the autolearn procedure. (if parameter MB =ON). The parameter can also be adjusted manually: in general, the band should get lower as the product increases in humidity or if a metallic film is present.

THS/3F

Remote Possible settings Standard setting Parameter

Analysis mode AM 2 - 7 6 (2 on THS/MN)

Related to the current product

Description Models

Received signal analysis mode AM THS/MN Other THS models 2 Standard recovery time after an alarm 3 Fast recovery time after an alarm 4 Not applicable Reserved 5 Not applicable Reserved

6 Not applicable Standard recovery time after an alarm, with improved immunity against vibrations

7 Not applicable Fast recovery time after an alarm, with improved immunity against vibrations

All models

Page 72: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 66

Ejection menu

Remote Possible settings Standard setting Parameter Ejection mode EM B / F / S / SB - Related to the current

product Description Models

Ejection mode Selection of ejection mode for contaminated material.

Mode B

Used for loose product and belt stop. No photocell required. This includes halting of the production line, manual elimination of the contaminated material and manual reset by the operator.(See also parameters ED and ET). Note: The metal detector does not check if there are any subsequent fragments in the material immediately following: all material under the probe must therefore be eliminated along with the part that caused the alarm. To minimise waste of material it is advisable to select a low setting for the ejection relay activation delay.

Mode F Used for loose product and ejection effected using retracting band or flap. No photocell required Includes automatic set-aside of contaminated material. (See also parameters ED and ET)

Mode S Used for packed product and ejection effected using pusher. Photocell required. Includes automatic set-aside of contaminated material with photocell synchronisation. (See also parameters ED, ET, PD, PH)

Mode SB Used for packed product and ejection effected with belt stop. Photocell required. This includes halting of the production line with photocell synchronisation, manual elimination of the contaminated material and manual reset by the operator.. (See also “Timing” section and parameter ED)

All models

Remote Possible settings Standard setting Parameter

Ej. distance ED 0 – 6000 mm - Related to the current product

Description Models

Distance of ejector from probe or photocell This parameter determines the activation delay of the relay relative : If EM=S or EM=SB : Distance between the photocell and the ejector. If EM=F or EM=B : Distance between the alarm (usually center of the probe) and the ejector. This delay is approximately :

ED (distance between ejector and antenna or photocell) BS (transit speed)

All models

Remote Possible settings Standard setting Parameter

Rev. detection RD ON / OFF OFF Related to the current product

Description Models

Reverse detection Detection of lack of metal parts, with inverted operation of both output relays. This requires a photocell to be mounted before or after the probe. This function is normally used, for example, to detect and reject packages without closing clip. Example with photocell at exit: AT =A

AT≠A

All models

Page 73: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 67

Remote Possible settings Standard setting Parameter

Belt lower sp. BL See below - Global Description Models

Minimum transit speed This parameter appears only if the variable speed inverter module (MDL) is fitted (KT > 0.000) or an encoder is connected (KE>0). In case an encoder without MDL is fitted, the range is 2 < BL < 250 m/min. In case MDL is fitted then 20KT < BL < BM. The parameter is not applicable in case of fixed-speed, MDT card fitted (KT=F) or no conveyor belt. With MDL: select the minimum operating speed If MDL is fitted, BL ≥ 20KT; Alteration of parameter KT results in automatic assignment of BL=20KT.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Belt Speed BS 2 – 250 m/min. - Related to the current product

Description Models

Transit speed In case of conveyor belt with fixed speed or models without conveyor belt, insert the real value of the product transit speed. If KE>0 and KT=0.000 (with encoder, without MDL inverter card), the parameter is not applicable. If the MDL is fitted, sets the real conveyor speed within the range BL - BM..

All models

Remote Possible settings Standard setting Parameter

Belt max. sp. BM See below - Global Description Models

Maximum transit speed This parameter appears only if the variable speed inverter module (MDL) is fitted (KT > 0.000) or an encoder is connected (KE>0). In case an encoder is fitted instead of the MDL, the range is BL – 250 m/min.

BL ≤ BM ≤ (MI x KT) The parameter is not applicable in case of fixed-speed or no conveyor belt. Variable-speed conveyor belt: select the maximum operating speed. If the inverter is fitted, BM ≤ MI x KT ; Alteration of parameter KT or MI results in automatic assignment of BM= MI x KT

All models, except THS/G

Ejection time menu

Remote Possible settings Standard setting Parameter Alarm relay time AT 0 – 20 s / A A Global Description Models

Alarm relay activation time When set to A (automatic) the alarm relay is activated only for the time that the signal exceeds the alarm threshold. If AT>0, the alarm relay is activated for the time that the signal exceeds the alarm threshold plus AT seconds. If AT=0 the relay is not activated.

All models

Remote Possible settings Standard setting Parameter

Ej. relay time ET 1 – 3000 hundredths of a second - Global

Description Models

Ejection relay activation time If EM=S this parameter represents the ejection relay activation time after an alarm. If EM=F: this parameter represents the minimum ejection relay activation time, because the relay is activated for a length of time given by the sum of the alarm time (the transit time of the metal mass through the probe) and time ET.

All models

Remote Possible settings Standard setting Parameter

Confirm time CT 0 – 6000 hundredths of a second - Global

Description Models

Confirm ejection time With the Ejection Confirmation activated (CE=ON), after activation of the ejection relay the status of the “eject confirmation” input is checked; if, after time CT, the input has not been activated (see parameter IE), the “fault ejection” status is activated (fault relay, visible and audible indicators activated, message “Fault: ejection” displayed). This may be caused by the failure to move a contaminated pack into a storage container. The “fault ejection” status is activated if the input remains active for a few seconds – e.g. if a pack is jammed. The alarm is reset by pressing the

key.

All models

Page 74: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 68

Counters menu

Remote Possible settings Standard setting Parameter Cur. alar. CA 0 – 999999999 - Related to the current

product Description Models

Number of alarms caused by the current product (since last reset) To reset this counter select the parameter, press the key and press the (increase) key; in remote programming execute the CR command.

All models

Remote Possible settings Standard setting Parameter

Cur. obj. CO 0 – 999999999 - Related to the current product

Description Models

Number of transits of packs of current product (since last reset) This count is performed through the photocell input. To reset this counter select the parameter, press the key and press the (increase) key; in remote programming execute the CR command.

All models

Remote Possible settings Standard setting Parameter

Alar. cnt. AC 0 – 999999999 - Global Description Models

Number of alarms (since last reset) This counter increases with all products. To reset this counter select the parameter, press the key and press the

(increase) key; in remote programming execute the AR command.

All models

Remote Possible settings Standard setting Parameter

Obj. cnt. OC 0 – 999999999 - Global Description Models

Number of packs (since last reset) This count is performed through the photocell input. This counter increases with all products. To reset this counter select the parameter, press the key and press the

(increase) key; in remote programming execute the OR command.

All models

Barcode reader menu This menu is available only with barcode reader fitted and BE parameter set to the right values.

Remote Possible settings Standard setting Parameter

Code CD See below - Global Description Models

Selection of type of coding type of code recognised by the bar-code reader. Possible settings: CODE 2/5 INTER, CODE 39 STAND, CODE 39 FULL, CODE 32, C.I.P., CODEBAR, CODE 128, EAN 128, CODE 93 STAND, EAN13, EAN8, UPCA, UPCE, EAN13 ADD ON 2, EAN8 ADD ON 2, UPCA ADD ON 2, UPCE ADD ON 2, EAN13 ADD ON 5, EAN8 ADD ON 5, UPCA ADD ON 5, UPCE ADD ON 5, PLESSEY, ALL EAN UPC

All models, except THS/G

Remote Possible settings Standard setting Parameter

Code length CL 1 – 48 / A A Global Description Models

Number of characters in the code A = Automatic

All models, except THS/G

Remote Possible settings Standard setting Parameter

Decodes number DN 1 - 10 - Global Description Models

Number of decodings with same result Number of consecutive identical readings for a code to be considered valid.

All models, except THS/G

Page 75: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 69

Remote Possible settings Standard setting Parameter

Window start WS 1 - 48 - Global Description Models

First of product identification characters First character of series used to identify the product within the code.

Example: If on an EAN13 code (code length 13 digits) we want to ignore the first 2 digits, we must set WS=3 and WE=13. In this case code 7004040090011 is considered the same of code 8004040090011.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Window end WE 1 - 48 - Global Description Models

Last of product identification characters Last character of series used to identify the product within the code.

Example: If on an EAN13 code (code length 13 digits) we want to ignore the last 2 digits, we must set WS=1 and WE=11. In this case code 8004040090011 is considered the same of code 8004040090022.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Learn code LC ON / OFF OFF Related to the current product

Description Models

Activation of code/product association phase Command which allows a code to be associated with a product. When activated (LC=ON), the message “Pass Code” appears on the display. After the barcode is passed in front of the reader, the message “ENTER to confirm” and the code read both appear on the display. Press to associate the code read with the current product, press key to cancel the operation. if one of the arrow keys is pressed, a new request to pass the barcode in front of the reader is made.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Barc-MD dist. BD 300 – 5000 mm - Global Description Models

Distance between reading point and antenna The reader is mounted upstream of the probe in order to read a code printed on the package. If the code is recognised, the reader sends a command to the metal detector to select the relevant product type. The time required by the THS to process the barcode is usually insignificant, but becomes important if the band is changed due to a modification in the type of product. When the metal detector receives the signal to change product type, an internal adjustment procedure is activated the length of which determines the minimum distance between two packages with different codes, that is to say containing different products.

L

S

Dp

BR

N

Dsbr

L

S

Dp

BR

N

Dsbr

Model / Event THS/3F with change of band (BA parameter) between one product and the other

Other THS models and THS/3F without change of band (BA parameter) between one

product and the other Distance

between the packs

Dp ≥ L + 3000 mm Dp ≥ L + 300 mm

Distance between the

barcode reader and the THS

probe

Dsbr ≥ 3000 mm Dsbr ≥ 300 mm

S probe/electronics unit of the metal detector L length of probe N conveyor belt Dsbr Distance THS probe-barcode reader

BR Barcode reader Dp Distance between packs of different products

All models, except THS/G

Page 76: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 70

Remote Possible settings Standard setting Parameter

No code eject NE ON / OFF OFF Global Description Models

Ejection of packs with wrong code When activated, the packages without barcodes or with invalid barcodes are ejected. If deactivated, there is no action. This command is available only if the barcode reader function is enabled.

Note: In order to function, a photocell for synchronisation of the packs must be installed. This photocell can be installed before or after the THS probe; HOWEVER, IT MUST BE INSTALLED AFTER THE BARCODE READER

All models, except THS/G

THS Configuration menu

Remote Possible settings Standard setting Parameter Line ID ID 1000 - 9999 9999 Global Description Models

ID of individual metal detector in network of devices linked via RS485 When connected via RS485, on each metal detector must be set a different value of ID. Maximum of units: 32.

All models

Remote Possible settings Standard setting Parameter

Operator access OA ON / OFF ON Global Description Models

Operator access to sensitivity setting If OA is set to ON the operator can change the sensitivity.

All models

Remote Possible settings Standard setting Parameter

Sound SO ON / OFF ON Global Description Models

Activation of the built-in buzzer All models

Remote Possible settings Standard setting Parameter

TP follower FO ON / OFF OFF Global Description Models

Automatic adjustment of variations in the characteristics of the product If activated, in case of product with chemical-physical characteristics which can vary gradually with time, the detector automatically determines the best point of operation and varies the TP parameter accordingly.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

Language LG See below - Global Description Models

Language for messages THSVxxxa GB / D / F / I THSVxxxb GB / D / NL / S THSVxxxc GB / P / E / JP

The last character of the software versione indicates the group of selectable languages, following the table beside, where the International Codes are used to identify each language.

THSVxxxd GB / D / F / H

All models

Remote Possible settings Standard setting Parameter

Inhib. time IN 0 – 3000 hundredths of a second 0 Global

Description Models

Inhibition time Inibiths the metal detector alarm for a certain time. If KT=0.000 (MDL or MDT not fitted), the time refers to the activation of the “Inhibition input”. If KT≠0.000, the time refers to the conveyor startup.

All models

Page 77: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 71

Remote Possible settings Standard setting Parameter

Barcode enab. BE 6 alphanum. characters - Global Description Models

Enabling code for operation with bar-code reader 6-character code which enables the THS to work with the bar-code reader: this is supplied by CEIA on delivery of an upgrade kit.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Phcell position PH IN / OUT - Global Description Models

Position of the photocell relative to the probe IN: photocell located at the entrance to the probe; OUT: photocell located at exit of the probe.

All models

Remote Possible settings Standard setting Parameter

Phcell-MD dist. PD 0 – 2000 mm - Global Description Models

Distance between metal detector and photocell The distance must be measured from the center of the photocell to the side of the probe.

All models

Remote Possible settings Standard setting Parameter

K trans. KT 0.000 – 9.999 / F - Global Description Models

Transmission constant KT= (transit speed)/(motor frequency) ; KT=0.000: no inverter

Note: when the value of KT is altered, parameters BL and BM are automatically set to nominal values 20 x KT and MI x KT respectively. BL and BM can nevertheless be altered manually as well.

Parameter KT must be set to “F” if the system configuration includes an MDT card.

All models, except THS/G

Remote Possible settings Standard setting Parameter

K encoder KE 0 – 1000 pulses / revol. 0 Global Description Models

Encoder constant Number of pulses per revolution. If set to 0 the encoder is not present.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Diameter DI 10 – 250 mm - Global Description Models

Diameter of encoder roller Diameter of encoder roller. Correlated parameter: K encoder.

All models, except THS/G

Remote Possible settings Standard setting Parameter

TP adjustment TA 0 – 1799 - Global Description Models

Correction of the received signal analysis parameter This parameter is specific to each device. This parameter must be automatically set up using the TL parameter in case the SCD card is replaced.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

TA autolearn TL ON / OFF - Global Description Models

Autolearn of parameter TA Select ON to activate the autolearn procedure (see TA parameter) and exit from programming.

Note: TL=OFF automatically at the end of procedure. See paragraph “Replacement of SCD card ”

All models, except THS/MN

Page 78: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 72

Remote Possible settings Standard setting Parameter

Transmission TX ON / OFF ON Global Description Models

Enabling of the transmitter If set to OFF it is possible to understand if a noise is electrical or mechanical. Refers to the Instructions manual. When TX=OFF the THS does not detect metals. The parameter is automatically set to ON if the THS is switched off and on again.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

TX channel CH 1 / 2 1 Global Description Models

Transmission channel Selection of different channels on adjacent detectors for automatic synchronisation. This parameter is not available on some models.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

Display contrast DC 0 – 50 0 Global Description Models

Display contrast Display contrast can vary with changes in environmental temperature.

All models

Remote Possible settings Standard setting Parameter

Time TM HH:MM - Global Description Models

Current time HH = Hours; MM = Minutes. In remote programming #TM=HH:MM

All models

Date settings menu

Remote Possible settings Standard setting Parameter Year - Last two figures

of the year - Global

Description Models

Year For remote programming, see parameter DA.

All models

Remote Possible settings Standard setting Parameter

Month - 1 - 12 - Global Description Models

Month For remote programming, see parameter DA.

All models

Remote Possible settings Standard setting Parameter

Day - 1 - 31 - Global Description Models

Day For remote programming, see parameter DA.

All models

Page 79: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 73

Change Password menu

Remote Possible settings Standard setting Parameter Operator US 6 alphanum. characters 000001 Global Description Models

Operator’s password Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

All models

Remote Possible settings Standard setting Parameter

Supervisor SU 6 alphanum. characters 000002 Global Description Models

Supervisor’s Password Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

All models

Remote Possible settings Standard setting Parameter

Engineer EG 6 alphanum. characters 000003 Global Description Models

Engineer’s Password Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

All models

Remote Possible settings Standard setting Parameter

Q-C Op. QU 6 alphanum. characters 000004 Global Description Models

Quality control operator’s password Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

All models

Remote Possible settings Standard setting Parameter

Q-C Head QH 6 alphanum. characters 000005 Global Description Models

Head of quality control’s password Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

All models

Remote Possible settings Standard setting Parameter

Remote Prog. RM 6 alphanum. characters 000006 Global Description Models

Password for remote programming Select each character via the (increase) e (decrease) keys and confirm by pressing the key.

All models

ALM Configuration menu

Remote Possible settings Standard setting Parameter Input logic LO P / N P Global Description Models

Input logic Applies to all inputs. If set to P (positive logic) all inputs are read as active when they are pulled to +V (with pull-down incorporated on card ALM). If set to N (negative logic) all inputs are read as active when they are pulled to -V (with pull-up incorporated on card ALM).

All models

Remote Possible settings Standard setting Parameter

BIN_FULL input IL NC / NO NO Global Description Models

Type of device connected to the “BIN_FULL” input NC: Normally Closed; NO: Normally Open If set to NO the Metal Detector gives an alarm when the BIN_FULL input is closed. If set to NC the alarm is given when the input is open.

All models

Page 80: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 74

Remote Possible settings Standard setting Parameter

BIN_ABS input IA NC / NO NO Global Description Models

Type of device connected to the “BIN_ABSENT” input NC: Normally Closed; NO: Normally Open. If set to NO the Metal Detector gives an alarm when the BIN_ABSENT input is closed. If set to NC the alarm is given when the input is open.

All models

Remote Possible settings Standard setting Parameter

EJ_CONF input IE NC / NO NO Global Description Models

Type of device connected to “Ejection confirmation” input NC: Normally Closed; NO: Normally Open If set to NO the Metal Detector read an “Ejection confirmation” when the EJ_CONF input is closed. If set to NC the confirmation is given when the input is open.

All models

Remote Possible settings Standard setting Parameter

PHOTO input IP NC / NO NO Global Description Models

Type of device connected to the “Photocell” input NC: Normally Closed; NO: Normally Open If set to NO the Metal Detector read the passage of a pack when the photocell input is closed. If set to NC the passage is read when the input is open.

All models

Remote Possible settings Standard setting Parameter

FOLL_CONV. input IW NC / NO NO Global Description Models

Type of device connected to the "FOLL_CONV" input NC: Normally Closed; NO: Normally Open If set to NO the Metal Detector stops when the FOLL_CONV input is open. If set to NC the stop is happening when the input is closed.

All models

Remote Possible settings Standard setting Parameter

LOW_PRESS. input I1 NC / NO NO Global Description Models

Type of device connected to the "LOW_PRESSURE" input NC: Normally Closed; NO: Normally Open If set to NO the Metal Detector gives an alarm when the LOW_PRESSURE input is closed. If set to NC the alarm is given when the input is open.

All models

Remote Possible settings Standard setting Parameter

PHOTO Alarm PA ON / OFF ON Global Description Models

Enabling of photocell alarm If set to ON, in case of photocell fault (continuously activated), the system goes into malfunction mode. If set to OFF, the system does not go into malfunction mode. If the photocell is in a continuously active state for a long period, this is interpreted as a malfunction of the sensor by the self-diagnosis system. There are many possible causes (wrong position, short-circuited wiring etc.)

On systems without encoder or with the Control Power Box, it is the installer’s and operator’s responsibility to ensure that material does not remain in front of the photocell when the belt is stopped: if it does, the photocell will be continuously active even though it is not malfunctioning. If the foregoing situation can not be avoided, it is advisable to disable photocell self-diagnosis.

All models

Remote Possible settings Standard setting Parameter

Conf. Ejec. Al. CE ON / OFF OFF Global Description Models

Enabling of “Confirm ejection ” alarm If set to OFF, the confirm ejection is deactivated. If set to ON, after activation of the ejection relay, the status of the “confirm ejection” input is checked; if, after time CT (hundredths of a second), the input has not been activated (see parameter IE), the “fault ejection” is activated. This may be caused by the failure to move a contaminated pack into a storage container. The fault relay is activated if the input remains active for a few seconds – e.g. a package is jammed. The alarm is reset by pressing the key.

All models

Page 81: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 75

Remote Possible settings Standard setting Parameter Bin.Full al. LF ON / OFF OFF Global Description Models

Enabling of “BIN_FULL” alarm If the input remains active for more than 5 seconds, the malfunction signal is activated. The alarm is reset by pressing the key.

All models

Remote Possible settings Standard setting Parameter

Bin Absent alarm LA ON / OFF OFF Global Description Models

Enabling of “BIN_ABS” alarm If the input remains active for more than 5 seconds, the malfunction signal is activated. The alarm is reset by pressing the key.

All models

Remote Possible settings Standard setting Parameter

Air pressure al. AP ON / OFF OFF Global Description Models

Alarm in case of insufficient air pressure OFF: LOW_PRESS input ineffective; ON: if the LOW_PRESS input is active the system goes into “Low Pressure” fault mode.

All models

Remote Possible settings Standard setting Parameter

Motor alarm MA ON / OFF - Global Description Models

Motor overheating alarm OFF: alarm disabled (configuration without motor driving or with MDL card) ON: Version with MDT card: only alarm if the thermic protection sensor, connected to J25 of MDT card, is active

All models, except THS/G

Remote Possible settings Standard setting Parameter

Ejection EJ ON / OFF ON Global Description Models

Ejection Enabling/disabling of ejection, used only for servicing purposes.

All models

Remote Possible settings Standard setting Parameter

Ejec. queue reset QR ON / OFF ON Global Description Models

Reset of the ejection queue OFF: ejection queue is never reset. If the belt stops and a contaminated package is placed between the antenna and the ejector, the package is ejected when the belt is started again; ON: if there is an MDL card or an encoder, the ejection queue is reset when the belt stops, whether by command or as the result of a fault.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Fault relay FR ON / OFF OFF Global Description Models

Enabling of fault relay If FR=ON, and in case of fault the “fault relay” and flashing indicator, connected to J22 pin 8 and 9, are activated.

All models

Remote Possible settings Standard setting Parameter

DTR protocol DT N / H N Global Description Models

DTR protocol Use of DTR line to communicate with printer. N = line not used; H = line used, handshake mode, high active line. The metal detector stop sending data to the serial port, in case the line is not pulled up.

All models

Page 82: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 76

Remote Possible settings Standard setting Parameter

Enable UP/DOWN UD ON / OFF - Global Description Models

Enabling of arrow keys to change the speed Enables the motor speed command from the power unit control panel. If MM=ON the changing of the speed is not activated, whatever is the value of UD.

All models, excepts THS/G

Remote Possible settings Standard setting Parameter

Manual movement MM ON / OFF OFF Global Description Models

Enabling of manual movement of the belt ON: if the motor is off, pressing keys and moves the motor forwards or backwards at speed BS. During movement the alarm and the ejection are disabled.

Only for models with Conveyor Control System

Remote Possible settings Standard setting Parameter

PREC_CONV Enab. PC ON / OFF OFF Global Description Models

Enable “preceding conveyor” relay ON: the relay is activated when the motor is running; OFF: the relay is deactivated

Only for models with Conveyor Control System

Remote Possible settings Standard setting Parameter

FOLL CONV Enab. FC ON / OFF OFF Global Description Models

Enable “following conveyor” input ON: with MDL or MDT, only if the following conveyor belt is running the THS belt is activated; with KT=0.000 (no MDL or MDT fitted) and KE=0 (no encoder fitted) or with THS/G if FC=ON, the metal detector stops incrementing the delay counter in case the “following conveyor” input is not active. This functionality can be used for example on a pipeline to stop the delay counting in case the pump that runs the liquid is stopped. OFF: the motor can be activated whatever is the status of following conveyor input.

All models

Remote Possible settings Standard setting Parameter

Autom. restart RE ON / OFF OFF Global Description Models

Belt restart if there is “following conveyor” input reactivation If FC= OFF, the parameter has no effect; If FC=ON:

- RE=OFF: if the belt is stopped by the “following conveyor” input deactivation, when the FOLL-CONV input reactivated the THS belt must be restarted manually.

- RE=ON: if the belt is stopped by the “following conveyor” input deactivation, when the FOLL-CONV input reactivates the THS belt restarts automatically unless the STOP key has been pressed in the meantime.

When the belt is stopped because of the following conveyor, the light flashes.

All models, excepts THS/G

Remote Possible settings Standard setting Parameter

Stop on fault SF ON / OFF OFF Global Description Models

Belt stop in case of fault SF=ON: if there is a fault in the THS, the belt stops; SF=OFF: if there is a fault the belt continues to run.

All models, excepts THS/G

Remote Possible settings Standard setting Parameter

Stop Time ST 0 – 99 min 0 Global Description Models

Belt auto-stop time This functionality is available only if a photocell is fitted: if no passages are detected for a time ST, the conveyor belt stops automatically (No signal is given).

All models, excepts THS/G

Page 83: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 77

Remote Possible settings Standard setting Parameter

Motor current CU 0.000 – 5.000 A - Global Description Models

Nominal motor current Set the nominal value for the motor connected to the MDL (this parameter is only significant on the version with MDL card). If the current drained to the motor is greater than CU, the belt stops and the “motor alarm” fault is given, both by the display and light. Usually CU must be set to the nominal current of the motor.

All models, except THS/G

Remote Possible settings Standard setting Parameter

Max Inv. freq. MI 60 – 100 - Global Description Models

Maximum inverter operating frequency Sets the maximum nominal value of the motor operating frequency (this parameter is only significant on the version with MDL card)

All models, except THS/G

Remote Possible settings Standard setting Parameter

Lamp blinking LB ON / OFF OFF Global Description Models

Lamp flash option OFF: when activated, the beacon connected to J22 pins 8 and 9, or the “test relay” are constantly activated. ON: when activated, the beacon or the “test relay” are flashing (interval = 1s)

All models

I/O Status menu

Remote Possible settings Standard setting Parameter - - H / L - Global Description Models

Display shows list of input and output lines with indication of their status Example of display: The inputs and outputs are shown on the display in real time.

FAULT relay H EJECT relay L ALARM relay L PREC_CONV relay H

All models

MD Test menu

Remote Possible settings Standard setting Parameter FE test - - - Global Description Models

Activation of the test for the standard iron reference sample Test procedure: see “Periodic test management” section of the Instructions manual.

All models

Remote Possible settings Standard setting Parameter

SS test - - - Global Description Models

Activation of the test for the reference sample in stainless steel Test procedure: see “Periodic test management” section of the Instructions manual.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

Non_FE test - - - Global Description Models

Activation of the test for the reference sample in diamagnetic metal Test procedure: see “Periodic test management” section of the Instructions manual.

All models, except THS/MN

Page 84: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 78

Print menu

Remote Possible settings Standard setting Parameter Print parameters PT - - Global Description Models

Print list of parameters with their current settings All models The data are sent to the RS232 interface, if the command is activated by local programming or via RS232. The data are sent to the RS485 if the command is request via RS485. Example:

#PT<ENTER> PN P2 SE 203 TP 0 BA MEDIUM AM 2 EM B ED 500 RD OFF BS 250 ... JR ON MR ON TR ON RT 0:10 TM 2:58 DA 01/03/00 SN 999999 PV THS/3F V3.390a - ALM V1.060 FIN 013A---a - 001A---- #

Remote Possible settings Standard setting Parameter

Print buffer PB - - Global Description Models

Print list of memorised events The data are sent to the RS232 interface, if the command is activated by local programming or via RS232. The data are sent to the RS485 if the command is request via RS485. The metal detector stores up to 1000 events. An event could be a certain parameter modification (SE, TP ecc.), a test result, an ejection (the result of the ejection is memorized).

Example:

QUALITY REPORT 28/02/00 - 20:14:00 Serial number 999999 Line ID 1013 >Change product 28/02/00 - 20:13:13 P.Name P2 Operator ENGINEER >Test Metal Detector 28/02/00 - 20:13:38 P.Name P2 Fe diameter 1.0 Test OK YES Operator Q-C OPERATOR >Test Metal Detector 28/02/00 - 20:13:49 P.Name P2 SS diameter 1.5 Test OK NO Operator Q-C OPERATOR >Statistics END QUALITY REPORT --------------------------------------------

All models

Page 85: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 79

Print report menu

Remote Possible settings Standard setting Parameter Ejection report JR ON / OFF ON Global Description Models

Include Ejections in the personalized report All models

Remote Possible settings Standard setting Parameter

Param. mod. rep. MR ON / OFF ON Global Description Models

Include Parameters modifications in the personalized report All models

Remote Possible settings Standard setting Parameter

Test report TR ON / OFF ON Global Description Models

Include Quality Control Tests results in the personalized report All models

Remote Possible settings Standard setting Parameter

Recent time RT 00:00 – 23:59 1:00 Global Description Models

Choose the time of the personalized report Events printed on the Quality report (PR) are referred to this parameter. With RT = 2.00, for example, the printed report refers to the last 2 hours of working.

All models

Remote Possible settings Standard setting Parameter

Print Report PR ON / OFF OFF Global Description Models

Print personalized report The data are sent to the RS232 interface, if the command is activated by local programming or via RS232. The data are sent to the RS485 if the command is request via RS485. The printer report is filtered according to JR, MR, TR and RT parameters. Example:

QUALITY REPORT 28/02/00 - 20:14:00 Serial number 999999 Line ID 1013 >Change product 28/02/00 - 20:13:13 P.Name P2 Operator ENGINEER >Test Metal Detector 28/02/00 - 20:13:38 P.Name P2 Fe diameter 1.0 Test OK YES Operator Q-C OPERATOR >Test Metal Detector 28/02/00 - 20:13:49 P.Name P2 SS diameter 1.5 Test OK NO Operator Q-C OPERATOR >Statistics END QUALITY REPORT --------------------------------------------

All models

Page 86: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 80

Quality Control menu (Q.C.Report)

Remote Possible settings Standard setting Parameter Print period PP 00:00 – 23:59 00:00 Global Description Models

Frequency of automatic printing of personalised report If PP=00:00 the automatic printing is disabled. If PP>00:00, an automatic print of the report is automatically sent to the RS232. The printed report includes the events selected with JR, MR, TR, and a final statistic. The interval which the data refers to is related to the last automatic print. For example, setting PP=01.00, each hour are printed the data related to the last hour.

Example of personalized report:

QUALITY REPORT 28/02/00 - 20:13:00 Serial number 999999 Line ID 1013 >Change parameter 28/02/00 - 20:12:18 Sensitivity 202 -> 203 P.Name P2 Operator ENGINEER >Ejection 28/02/00 - 20:12:31 P.Name P2 Ejection OK >Ejection 28/02/00 - 20:12:44 P.Name P1 Ejection OK >Change product 28/02/00 - 20:12:45 P.Name P1 Operator ENGINEER >Ejection 28/02/00 - 20:12:49 P.Name P1 Ejection OK >Statistics P.Name P2 n. allarms 1 n. objects 8 Alarm rate 12.50 % END QUALITY REPORT -------------------------------------------

All models

Remote Possible settings Standard setting Parameter

Test period TE 00:00 – 23:59 00:00 Global Description Models

Pre-defined interval between Quality Control tests If TE=00:00 the tests are disabled. If TE>00:00 a test is requested every TE interval.

All models

Remote Possible settings Standard setting Parameter

Test delay TD 00:00 – TE 00:00 Global Description Models

Waiting time for test to be carried out Time within the operator should carry out test every TE interval.

Note: the need to carry out a test is signalled on the display.

All models

Remote Possible settings Standard setting Parameter

Fault time out FT ON / OFF ON Global Description Models

Activation of fault status if maximum time for test expires without performing the test All models

Test Sensitivity menu (Test sensitiv.)

Remote Possible settings Standard setting Parameter

FE diameter FD 0.0 – 25.0 - Global Description Models

Diameter of iron sample sphere used to perform the test Datum that must be set for inclusion in the test report.

Note: The value is printed in the Q.C. report and does not effect the sensitivity.

All models

Page 87: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 81

Remote Possible settings Standard setting Parameter

SS diameter SD 0.0 – 25.0 - Global Description Models

Minimum detectable diameter for stainless steel sample sphere Datum that must be set for inclusion in the test report.

Note: The value is printed in the Q.C. report and does not effect the sensitivity.

All models, except THS/MN

Remote Possible settings Standard setting Parameter

Non_FE diameter ND 0.0 – 25.0 - Global Description Models

Minimum detectable diameter for diamagnetic metal sample sphere Datum that must be set for inclusion in the test report.

Note: The value is printed in the Q.C. report and does not effect the sensitivity.

All models, except THS/MN

Commands accessible only in Remote Programming

Remote Possible settings Standard setting Parameter

- PE - - Global Description Models

Exit from remote programming In case the remote programming is not used for 3 minutes, the PE command is sent automatically by the THS

All models

Remote Possible settings Standard setting Parameter

- PV - - Global Description Models

Software version Provides the software version loaded on the THS. #PV <ENTER>

THS/STD V3.390a – ALM V1.060

All models

Remote Possible settings Standard setting Parameter

- HE - - Global Description Models

Help Provides the list of commands available, their meanings and their current settings

All models

Remote Possible settings Standard setting Parameter

- DP - - Global Description Models

Cancellation of all products

The command delete ALL products defined by the user, leaving only the “Default” product. All models

Remote Possible settings Standard setting Parameter

- DA DD/MM/YY - Global Description Models

Current date insertion DD = Day, MM = Month YY = last two figures of the year

#DA=18/02/04 <ENTER> #

All models

Page 88: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 82

Remote Possible settings Standard setting Parameter

- CR - - Related to the current product

Description Models

Reset of the current product counters Resets the alarm and object counters for the current product.

All models

Remote Possible settings Standard setting Parameter

- AR - - Global Description Models

Reset total alarm counter All models

Remote Possible settings Standard setting Parameter

- OR - - Global Description Models

Reset total pack transit counter All models

Remote programming via serial link

Programming is carried out through a remote computer fitted with an RS232 or RS485 interface, using a standard communications program (e.g. Windows™ Terminal) or the CEIA MDScope program, available on request.

Communication parameter settings: • Baud rate = 9600 bit/s (to be set on the computer) • 8 data bits • NO parity • 1 stop bit • no communication protocol • CR -> CR+LF • Local echo = OFF • Terminal: VT 100 (ANSI)

Entering remote programming

Connecting to a metal detector (via RS 232) - Run the communications program

- Enter the password and key ENTER. The command prompt will appear

(password) <ENTER> #

Note: each password accesses programming at the appropriate level (operator, supervisor, …)

Long-distance connection to a single metal detector (via RS 485) Identical to the above.

Network connection (via RS 485) Using RS 485 transmission, several metal detectors can be connected in a network. In this case, the PC acts as master and the metal detectors as slaves. So as to allow each individual metal detector to be identified, the following steps must be taken: Set a password on each metal detector (N.B.: the password can be the same if so desired). Set a different Line ID identification code for each metal detector (line ID parameter ID=1001, 1002, 1003, .).

Page 89: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 83

Connecting to a metal detector in a network - Run the communications program

- Execute the PE command

- On the same line, enter the ID code and password (Head of Quality Control) and key ENTER. The command prompt will appear

#PE <ENTER>* (LineID)(password)<ENTER> #

* ENTER = ASCII code 013 Note: LineID always > 1000

3.13.3 - Displaying a parameter setting Type the code of the parameter and press ENTER: the parameter setting will appear next to it.

#SE<ENTER> #SE 30

3.13.4 - Changing a parameter setting #SE=35<ENTER> #

Type the code of the parameter followed by the “=” character or a space, the new value and ENTER.

#SE 35<ENTER> #

3.13.5 - Executing a function Key in the parameter code and press ENTER. #PR<ENTER>

#

Page 90: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 84

Maintenance

Any maintenance or repair of the device while open and energised should be avoided, and in any case should only be carried out by trained personnel who are fully aware of the risks which the operation entails, following the instructions given in the “Maintenance” section.

When the mains is disconnected using the main switch S1 of the Conveyor Control System, the power supply section is deactivated, but the contacts which are connected permanently to the mains, e.g. the relay outputs, remain energised. N.B. When the I2 service switch is turned off, most components remain energised.

fig. V -1a fig. V -1b

Removal of the safety protections fitted to the device is strictly prohibited.

Periodic maintenance Table V-1

Operation Period Operator detection check • beginning of each shift

• on changing product type • periodically

• Quality-control operator • Head of quality control

cleaning of conveyor belt beginning of each shift Operator

belt tension adjustment 6 months or when necessary maintenance personnel

locking of terminals used to connect control panels

6 months maintenance personnel

Cleaning of barcode reader (if fitted) with a non-abrasive cloth dampened with alcohol

6 months or when necessary Operator N.B.: clean when the device is switched off

The operator must monitor the condition of the system and its suitability for use, and consult the maintenance personnel if necessary.

S1

I2

Page 91: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 85

Self-diagnosis The internal diagnostic system monitors the operational status of the metal detector. If a fault is detected, the following are activated in addition to a message on the display:

• the illuminating alarm indicators • the buzzer (if activated) • the fault relay (if Fault relays parameter is ON) • flashing light (if Fault relays parameter is ON)

Fault status can only be reset by eliminating the cause of the fault.

Table V-2 Message Probable cause Action Test time out Time-out for pre-programmed

test. Carry out the test

Fault: power Power-supply section faulty

Contact service technician

Fault: probe Antenna connection broken

Contact service technician

Fault: ejection ** Ejection of material not carried out

• Check that the ejection times are correct. • Check that the ejector is not blocked • Check photocell operation (positioning, connections

etc.) • Check the Confirm Ejection input connections When the cause of the fault has been eliminated, press the E key to reset the alarm status.

Bin full Storage container full Empty it Press E key to reset the alarm status

Fault: communication Fault in communication between SCD and ALM cards

Check that the power-supply voltage is stable and corresponds to the values on the identification plate. Check the wiring If the wiring is correct, replace the cards

Fault: motor alarm ("motor alarm" indicator activated)

Overloading of the belt motor Wrong setting of CU parameter

Remove the cause of overloading and press E key. Set a proper value of CU parameter and press E key.

Fault: air pressure Compressed air pressure too low

Check the compressed air connection. When the cause of the fault has been eliminated, press the E key

Photocell fault *** Photocell malfunction or pack stuck in front of photocell

• check there is no pack stuck in front of the photocell • check the photocell connections • Check the positions of the photocell and the

retroreflector • replace the photocell When the cause of the fault has been eliminated, press the E key to reset the alarm status ****

Memory card not installed (THS system not operative)

Memory faulty or absent Check presence and connections of the SPM external memory card (see para. "Replacement of SCD card"

Compatibility error SCD card incompatible with the data stored in the SPM memory card

Use compatible SCD card (ask service personnel)

*Enabled by the Fault relays parameter **Enabled by the Ejection confirmation parameter *** Enable via the PHOTO Alarm parameter **** The self-diagnosis message may appear: - in the case of a conveyor belt without encoder or with Power Control Box, with the belt stopped or moving - in the case of a conveyor belt without encoder or with Conveyor Control System, with the belt moving The system is not designed to signal a pack which is stuck for some reason in front of the photocell. For this

reason, when the system can detect whether or not the conveyor belt is moving (i.e. when it is equipped with an encoder or with the Conveyor Control System power supply unit), the self-diagnosis function gives an alarm only if the photocell is in a state of malfunction when the belt is moving.

On systems without encoder or with the Control Power Box, it is the installer’s and operator’s responsibility to ensure that material does not remain in front of the photocell when the belt is stopped: if it does, the photocell will be continuously active even though it is not malfunctioning. If the foregoing situation can not be avoided, it is advisable to disable photocell self-diagnosis (Parameter PA)

Page 92: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 86

Storage Store the system in its original packaging, or in a way that protects it adequately from atmospheric agents or other possible causes of damage (moving objects, weights, solvents etc.). Storage temperature (Regulation EN 60204): -25°C - +55°C long-term, +70°C for 24 hours maximum.

Transport and movement of the conveyor belt

Disconnect the system from the various power sources before carrying out any movement. Use lift trucks or sling the load-bearing structure, and ensure that the load is balanced during movement. Avoid deforming the structure or its component parts.

Never attach lifting gear to the Metal Detector probe or the actuators. Keep the packaging materials for possible future transport.

Fig. V-2

Adjustment of conveyor belt tension This is carried out on the roller on the side opposite the motor roller. To adjust the belt tension, loosen screws A on both sides by the same number of turns, so that the slack in the belt at the entrance to the probe appears as in the figure (about 0.02 x length of the belt, s=0.02 D).

D

s

Fig. V-3a Fig. V-3b

A

Page 93: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 87

Replacing the belt If the belt has to be joined, this should be done along a diagonal or, even better, in a zigzag, in order to minimise the increase in thickness due to the joint.

Fig. V-5a : diagonal join Fig. V-5b: zigzag join

Disposal of the device and of consumables with environmental impact For disposal follow the regulations in force in the country where the device is being used. The following components should be taken into consideration:

Table V-3 Component Specifications battery incorporated on card SCD Lithium 3.6V type CR1/2 AA lubricant for motor drum EP SAE 90 oil for gears, or equivalent

Fuses The figure shows the position and rating of the fuses fitted to the device.

Table V-4 Ref. Type Description F1-F2 250V 10A, fast 5x20mm card power supply protection P1 250V 3,15A fast 5x20mm upstream belt relay common contact protection P2 250V 3,15A fast 5x20mm auxiliary relay common contact protection P3 250V 3,15A fast 5x20mm metal detector alarm relay common contact protection P4 250V 3,15A fast 5x20mm ejector relay common contact protection P5 250V 3,15A fast 5x20mm malfunction relay common contact protection F3-F4-F5 500V 10A, fast 6.3x32mm card MDT power supply protection

Fig V-6a - ALM and MDL card fuses Fig V-6b - MDT card fuses

Troubleshooting

Self-resetting protections • The ALM card power supply inputs are protected by self-resetting components PTC. • The MDL inverter card outputs are electronically protected against short circuit between two phases. • The ALM card inputs are protected against wrong connection up to the voltages present on the card itself, with the

exception of the mains voltage.

Table V-5

F1 F2

P1

P2

P3

P4

P5

F3 F4 F5

Page 94: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 88

Symptom Probable cause Action Power supply unit-metal detector system off

Malfunction of the power supply section No line voltage Unstable or partial connections

Switch off, wait a few minutes to let any self-resetting components inside cool down, then switch on the system again. If the problem persists, replace card ALM Check the power supply connections Check insertion of the ALM card connectors

Power supply unit-metal detector system alternates between on and off

Malfunction of the power supply section

As above

Metal detector does not give an alarm in the presence of metal masses of the same type as the reference sample and of equal or greater mass

Metal detector inhibition Wrong detection parameters for the current product Product effect SCD card malfunction

Carry out the following operations in sequence: Set IN=0 Disconnect the ALM card connectors which do not link up to the power supply or probe. Select the “Default” product and check, with the sample provided with the device, that the detector gives an alarm. Carry out the autolearn procedure. Check the settings of the detection parameters (SE, TP, etc.) Carry out the autolearn procedure. If the procedure is not successful, replace the SCD card.

Metal detector gives false alarms with no product in transit

Environmental interference SCD card malfunction Line voltage insufficient or unstable

Carry out the “ Checking for environmental electromagnetic interference” procedure. Deactivate all electrical and mechanical devices surrounding the detector, or move it into a place which is guaranteed free of interference. Disconnect the ALM card connectors which do not link up to the power supply or probe. If the interference signal remains the same, replace the SCD card. Check.

MDT card

motor 4

L1 L2 L3

Switch I2

F5 F4F3

ALM card

Voltage regulators

Voltage regulators

Controller Metal Detector SCD card

Emergency switch

Sensors/Actuators

L2

Switch I1 115/230V

STC card Keyboard and signals

Forward / backward switching module

MDT card

motor 4 L1L2L3N

Switch I2

F5 F4 F3

ALM card

Voltage regulators

Voltage regulators

Controller Metal Detector SCD card

Emergency switch

Sensors/Actuators

L2

Switch I1115/230V

STC card Keyboard and signals

Forward / backward switching module

Fig. V-8a block diagram of the THS system with MDT card, 230V~ power supply

Fig. V-8b block diagram of the THS system with MDT card, 400V~ power supply

Page 95: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 89

MDL card

Variable frequency 3-phases generator

motor 4 L0 L1

Switch I2

F1 F2

ALM card

Voltage regulators

Voltage regulators

Controller Metal Detector SCD card

Emergency switch

Sensors/Actuators

L2

Switch I1 115/230V

STC card Keyboard and signals

Fig. V-8c block diagram of the THS system with MDL card

Replacing Card SCD If the control card has to be replaced, the serial number of the device must be quoted in the order; the card will only be able to be used with that same detector.

Procedure • Switch off the device • The card is attached to the detector control panel. Remove the control panel by unscrewing the fixing screws, taking

care not to pull on the internal connecting wires. • Disconnect the card and connect the internal wires to the replacement card. • Plug the SPM memory card from the old control card into the new one. N.B.: the memory card contains all the

device’s stored programming, product and event data. • Reassemble the control panel. • Switch on the detector and reset the programming. • Carry out the TL Autolearn procedure:

• The procedure must be carried out in an interference-free environment: deactivate the THS conveyor belt and any other power devices in the area.

• Set the parameter TL Autolearn = ON and exit from programming. • The message “Pass” will appear on the display: press forcibly for at least a second on the probe (see figs. below –

press in the middle of the belt width at either the entrance or the exit, but NOT in the centre). In the case of models THS/PH and THS/G, make the probe vibrate. Repeat TL autolearn for each band (BA) and for each channel (CH).

• N.B.: in the case that the procedure is not carried out, or is carried out improperly, compensation for the products

may not be correct. As a check, select the “default” product and make some tests with the sample indicated in the test card enclosed with this manual.

• Check that the system operates properly with all the products stored in memory. The SCD card stores the values of all the operating parameters, including those of the power-supply and control

unit. If the power supply unit is replaced, therefore, it is not necessary to reprogram the system..

Page 96: Detector Industrial de Metales

THS – FI022GB2K8v3 --- V - MAINTENANCE 90

Checking environmental electromagnetic interference The existence of interference is indicated by false alarms or by the display of several segments on the bar-graph when the conveyor belt is stopped and there is no product in transit:

THS/STD V3.290 Product productname I I I

THS/STD V3.290 Product productname I I I I I I I I

THS/STD V3.290 Product productname I I I I I I I I I I * * * * *

Fig.V-9a. Example: signal well below the threshold level

Fig.V-9b. Example: signal just below the threshold level

Fig.V-9c Example: signal above the threshold level (alarm).

For correct operation, the bar-graph indicator should not have more than THREE bars lit. To eliminate the interference, the first thing to do is to identify whether it is electrical or magnetic: 1 Set parameter TX=OFF. . (NB: on model THS/MN, set the switch on the internal card of the probe power-supply unit to OFF) 2 If the interference remains the

same, it is electrical Examples of sources of electrical interference: electric motors, inverters, power cables, lighting

3 If the interference decreases, it is of a mechanical nature

Examples of sources of mechanical interference: unstable anchoring of the metal detector (vibrations), metal masses moving in the vicinity of the probe, intermittent loops, metal fragments in the conveyor belt.

To increase immunity to mechanical interference, adjust the AM parameter (see paragraph “Analysis mode selection criteria” ). To eliminate sources of interference, refer to the illustrated notes in the Installation section.

Page 97: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 91

APPENDICES

DECLARATION OF CONFORMITY CE

DECLARATION OF CONFORMITY CE DECLARATION DE CONFORMITE CE KONFORMITÄTSERKLÄRUNG CE

DECLARACION DE CONFORMIDAD CE DICHIARAZIONE DI CONFORMITÁ CE

Manufacturer Fabricant / Hersteller / Fabricante / Costruttore:

CEIA S.p.A. Zona industriale Viciomaggio 54/G 52040 Viciomaggio - Arezzo - ITALY

Declares that the product déclare que ce produit / erklärt, daß das Produkt / declara que el producto / dichiara che il prodotto:

Product name:

Nom du produit: / Produktname: Nombre del producto: / Nome:

Electronic Metal Detector Détecteur de métaux / Elektronischer Metalldetektor Electronic Metal Detector / Metal Detector Elettronico

Model Série / Serie / Serie / Modello:

THS all model tous modèles/ alle Modelle todos los modelos/ tutti i modelli

conforms to the following Product Specifications est conforme aux spécifications suivantes / folgenden Produktspezifikationen entspricht

es conforme a las siguientes especificaciones / è conforme alle seguenti specifiche di prodotto:

Safety / Sécurité / Sicherheit / Seguridad / Sicurezza: EN 60204 - 1 This product complies with the requirements of the Low Voltage Directive 73/23/EEC and following modifications indicated in the 93/68/EEC Directive. Le produit ci-dessus répond aux exigences de la Directive 73/23/CEE et aux modifications suivantes mentionnées dans la Directive 93/68/CEE concernant la basse tensions. Dieses Produkt entspricht den Anforderungen an Niederspannungsgeräte gemäß der Norm 73/23/EEC und nachfolgender, in der Norm 93/68/EEC angegebener Änderungen. El producto indicado cumple los requisitos de la Low Voltage Directive 73/23/CEE y siguientes modificaciones indicadas en la Directiva 93/68/EEC. Il prodotto è conforme alle norme della direttiva 73/23/EEC e successive modifiche indicate nella direttiva 93/68/EEC sulla bassa tensione.

EMC EN 55011: Group 1 - Class A EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 ENV50204 Dieses Produkt entspricht den Anforderungen der EMC-Norm 89/336/EEC und nachfolgender in den Normen 92/31/EEC und 93/68/EEC angegebener Änderungen. El producto indicado cumple los requisitos de la Directiva EMC 89/336/CEE y siguientes modificaciones indicadas en las Directivas 92/31/EEC y 93/68/EEC. Il prodotto è conforme alle norme della direttiva EMC 89/336/EEC e successive modifiche indicate nelle direttive 92/31/EEC e 93/68/EEC.

Arezzo, 2003-12-15

SpA

Person in charge Lab. EMC Resp. Laboratoire EMC / Laborattaché EMC

Resp. Laboratorio EMC / Resp. Lab. EMC Ing. E. Sorini

Page 98: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 92

Spare parts, Options and Accessories

Ordering spare parts When ordering spare parts please specify the following: •company details with exact address where the parts are to go •serial number of the device •description of the part •quantity ordered •shipping method CEIA is not responsible for any error in shipping due to incomplete and/or inaccurate orders.

When ordering any component, please indicate the serial number of the device!

THS standard model / THS/3F Validity: revision 3.30, 09/06/2003 Spare parts Description Quantity Code Control panel 1 30270 SPM module 1 21853 Cable connecting the probe to the power supply unit: length 3 metres (family A) 1 18940 Cable connecting the probe to the power supply unit: length 3.5 metres (family B) 1 18941 Cable connecting the probe to the power supply unit: length 4 metres (family C, D) 1 18942 Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992 Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999 Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000 Power supply unit without motor control - Control Power Box 1 21001 Power supply card 00208ALM 1 18939 Motor control panel - card 00208STC 1 18944 Motor control card 00208MDL 1 18943 Motor control card 00208MDT 1 19946 Remote control card 00208RCU 1 18945 Compact power supply unit without motor control 1 22626 Power supply card 00208AL_ 1 22569 Connector kit for Power supply card 00208AL_ 1 22616 Picket-Fence bar code reader (code with vertical bars) 1 17823 Step-Ladder bar code reader (code with horizontal bars) 1 18700 Options Description Quantity Code RS 485 interface 1 17828 Remote control module for Conveyor Control System 1 21559 Remote control module for Control Power Box 1 21560 115/230Vca Transformer Box 1 23181 400/230Vca Transformer Box 1 23182 Protection against high-pressure water cleaning 1 24775 Ethernet Module 1 29756 Accessories Description Quantity Code MDScope 1 26894 MDCAD 1 27185 THS REPORT 1 27184 RS232/RS485 converter 1 21540

THS /A Validity: revision 3.300, 09/06/2003 Spare parts Description Quantity Code Control panel 1 16804 SPM module 1 21853 Cable connecting the probe to the power supply unit: length 3 metres 1 18940 Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992 Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999 Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000 Power supply unit without motor control - Control Power Box 1 21001

Page 99: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 93

Power supply card 00208ALM 1 18939 Motor control panel - card 00208STC 1 18944 Motor control card 00208MDL 1 18943 Motor control card 00208MDT 1 19946 Remote control card 00208RCU 1 18945 Picket-Fence bar code reader (code with vertical bars) 1 17823 Step-Ladder bar code reader (code with horizontal bars) 1 18700 Options Description Quantity Code RS 485 interface 1 17828 Remote control module for Conveyor Control System 1 21559 Remote control module for Control Power Box 1 21560 115/230Vca Transformer Box 1 23181 400/230Vca Transformer Box 1 23182 Protection against high-pressure water cleaning 1 24775 Ethernet Module 1 29756 Accessories Description Quantity Code MDScope 1 19795 MDCAD 1 27185 THS REPORT 1 27184 RS232/RS485 converter 1 21540

THS/SL Validity: revision 3.300, 09/06/2003 Spare parts Description Quantity Code Control panel 1 16804 SPM module 1 21853 Cable connecting the probe to the power supply unit: length 3 metres 1 18940 Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992 Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999 Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000 Power supply unit without motor control - Control Power Box 1 21001 Power supply card 00208ALM 1 18939 Motor control panel - card 00208STC 1 18944 Motor control card 00208MDL 1 18943 Motor control card 00208MDT 1 19946 Remote control card 00208RCU 1 18945 Compact power supply unit without motor control 1 22626 Power supply card 00208AL_ 1 22569 Connector kit for Power supply card 00208AL_ 1 22616 Picket-Fence bar code reader (code with vertical bars) 1 17823 Step-Ladder bar code reader (code with horizontal bars) 1 18700 Options Description Quantity Code RS 485 interface 1 17828 Remote control module for Conveyor Control System 1 21559 Remote control module for Control Power Box 1 21560 115/230Vca Transformer Box 1 23181 400/230Vca Transformer Box 1 23182 Protection against high-pressure water cleaning 1 24775 Ethernet Module 1 29756 Accessories Description Quantity Code MDScope 1 19795 MDCAD 1 27185 THS REPORT 1 27184 RS232/RS485 converter 1 21540

THS/MN Validity: revision 3.30, 09/06/2003 Spare parts Description Quantity Code Control panel 1 30270 SPM module 1 21853 Cable connecting the probe to the power supply unit: length 3 metres 1 23395 Power supply unit with motor control - Conveyor Control System - variable speed version 1 20999 Power supply unit with motor control - Conveyor Control System - fixed-speed version 1 21000 Power supply unit without motor control - Control Power Box 1 21001 Power supply card 00208ALM 1 18939 Motor control panel - card 00208STC 1 18944

Page 100: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 94

Motor control card 00208MDL 1 18943 Motor control card 00208MDT 1 19946 Remote control card 00208RCU 1 18945 Auxiliary power supply unit 1 23400 Power supply card 00208MAG 1 23240 Picket-Fence bar code reader (code with vertical bars) 1 17823 Step-Ladder bar code reader (code with horizontal bars) 1 18700 Options Description Quantity Code RS 485 interface 1 17828 Remote control module for Conveyor Control System 1 21559 Remote control module for Control Power Box 1 21560 115/230Vca Transformer Box 1 23181 400/230Vca Transformer Box 1 23182 Protection against high-pressure water cleaning 1 24775 Ethernet Module 1 29756 Accessories Description Quantity Code Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) High sensitivity

1 18711

Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) - Low sensitivity

1 22605

Sample with a ø 0.8 mm in AISI 420 steel sphere (ferromagnetic) 1 18124 Sample with a ø 1.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18125 Sample with a ø 1.2 mm in AISI 420 steel sphere (ferromagnetic) 1 18126 Sample with a ø 1.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18127 Sample with a ø 2.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18128 Sample with a ø 2.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18129 Sample with a ø 3.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18130 Sample with a ø 3.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18131 Sample with a ø 4.0 mm in AISI 420 steel sphere (ferromagnetic) 1 20251 Sample with a ø 4.5 mm in AISI 420 steel sphere (ferromagnetic) 1 20252 Sample with a ø 5.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22056 Sample with a ø 5.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22057 Sample with a ø 6.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22058 Sample with a ø 6.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22059 MDScope 1 19795 MDCAD 1 27185 THS REPORT 1 27184 RS232/RS485 converter 1 21540

THS/PH Validity: revision 1.102, 12/04/2001 Spare parts Description Quantity Code Control panel 1 18657 SPM module 1 21853 Deflector 1 18743 Infeed conveyor 1 16332 Support assembly 1 16043 Cable connecting the probe to the power supply unit 1 18938 Power supply unit 1 18744 Power supply card 00208ALM20 1 18939 Included sample - Stainless steel (ø0.3mm sphere) 1 17052 Included sample - Iron (ø0.3mm sphere) 1 17051 Included sample - Blank 1 16793 Short discharge conveyor 1 16335 Long discharge conveyor 1 19803 Deflector cover 1 16344 Deflector white basis in PETG 1 16333 Deflector flap position sensor 1 15286 Flap actuator 1 23541 Steel deflector flap 1 23542 Options Description Quantity Code RS 485 interface 1 17828 Accessories Description Quantity Code MDScope 1 19795

Page 101: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 95

THS/G Validity: revision 3.300, 30/06/2003 Spare parts Description Quantity Code Control panel 1 18736 SPM module 1 21853 Cable connecting the probe to the power supply unit: length 3 metres 1 18940 Cable connecting the probe to the power supply unit: custom length (max. 40m) 1 19992 Power supply unit 1 21141 Power supply card 00208ALM 1 18939 Remote control card 00208RCU 1 18945 Options Description Quantity Code RS 485 interface 1 17828 400/230Vca Transformer Box 1 23182 Protection against high-pressure water cleaning 1 24775 Ethernet Module 1 29756 Key for flange mounting 1 23376 Accessories Description Quantity Code MDScope 1 19795 MDCAD 1 27185 THS REPORT 1 27184 RS232/RS485 converter 1 21540 Infeed conveyor øin 330mm - øout 126.5mm PM2034A 1 23435 Infeed conveyor, part 1 code 2-37, øin 330mm, øout 161mm 1 23353 Infeed conveyor, part 2 code 2-39, øin 172mm, øout 126.5mm 1 23223 Infeed conveyor øin 330mm - øout 102.5mm PM2035A 1 23434 Infeed conveyor, part 1 code 2-37, øin 330mm, øout 165mm 1 23353 Infeed conveyor, part 2 code 2-41, øin 161mm, øout 152mm 1 23221 Infeed conveyor, part 3 code 2-42, øin 147mm, øout 142mm 1 23356 Infeed conveyor, part 4 code 2-43, øin 142mm, øout 126mm 1 23355 Infeed conveyor, part 5 code 2-44, øin 134mm, øout 102.5mm 1 23354 Infeed conveyor øin 330mm - øout 82mm PM2036A 1 23433 Infeed conveyor, part 1 code 2-37, øin 330mm, øout 165mm 1 23353 Infeed conveyor, part 2 code 2-38, øin 161mm, øout 110mm 1 23222 Infeed conveyor, part 3 code 2-40, øin 111mm, øout 82mm 1 23357

THS-FB Validity: revision 1.06, 10/05/2002 Spare parts Description Quantity Code Belt 1 2 Tab. A Trespa support plate - long part 1 7 Tab. A Trespa support plate - short part 1 8 Tab. A Plate spacer/support 1 9 Tab. A Plate and reflektor spacer/support 1 10 Tab. A Power supply unit and blinking light support kit 1 11 Tab. A Reflektor support 1 12 Tab. A Drum motor with wiring 1 15 Tab. A 250mm Drum motor 1 24922 300mm Drum motor 1 24715 350mm Drum motor 1 24923 400mm Drum motor 1 24716 450mm Drum motor 1 24918 500mm Drum motor 1 24717 600mm Drum motor 1 24718 Photocells 1 18486 Orange blinking light module 1 21280 Buzzer module 1 21281 Support for buzzer/blinking light 1 21282 Support for blinking light 1 20359 Supports for Free roller 1 21428 Bearing for Free roller and Bend roller 1 24605 Supports for Drum motor 1 21429 00208SCN connection card 1 21917 Casing for connectio card - drum motor side 1 21623 Casing for connectio card - supply box side 1 21622 Roller tilting support - right side 1 20803 Roller tilting support - left side 1 20804 Drum motor support - right side 1 20805 Drum motor support - left side 1 20806 General purpose support 1 21243 6mm diameter blue air rubber pipe 1 20958 8mm diameter blue air rubber pipe 1 21601 PG9 plug 1 22315

Page 102: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 96

Accessories and Options

Description Quantity Code Feet for 1000mm - 1500mm belt 4 21525 Castors for 1000mm - 1500mm belt 4 21548 Feet for 2000mm & THS/MN belt 4 24802 Castors for 2000mm & THS/MN belt 4 24803 Bar-code reader mounting kit 1 21613 Insufficient air-pressure sensor kit 1 21614 Piston ejector - 200mm 1 21610 Air group protection casing 1 21121 Air adiustment group 1 21604 Connection and solenoid valve kit 1 21602 Piston ejector - 350mm 1 21611 Air group protection 1 22397 Air adiustment group 1 21604 Connection and solenoid valve kit 1 21602 Air-jet ejector 1 22477 Protection casing 1 26282 Valve kit 1 26270 Set-aside container with support 1 21423 Plastic container 1 19139 Ejection confirmation sensor and full set-aside container sensor kit 1 21612 Protective panel set at the exit of the antenna - belt width 1500 x 200 mm for Family A 1 24739 Cover - belt width 200mm for Family A 1 24862 "U" protection for cover - belt width 3200mm for Family A 1 24861 Protective panel set at the exit of the antenna - belt width 2000 x 200 mm for Family A 1 24741 Cover - belt width 200mm for Family A 1 24862 "U" protection for cover - belt width 3200mm for Family A 1 24864 Protective panel set at the exit of the antenna - belt width 1500 x 300 mm for Family A 1 21412 Thermoformed cover - belt width 300mm for Family A 1 23262 "U" protection for Thermoformed cover - belt width 300mm for Family A 1 23140 Protective panel set at the exit of the antenna - belt width 2000 x 300 mm for Family A 1 24743 Thermoformed cover - belt width 300mm for Family A 1 23262 "U" protection for Thermoformed cover - belt width 300mm for Family A 1 24866 Protective panel set at the exit of the antenna - belt width 1500 x 400 mm for Family A 1 24745 Cover - belt width 400mm for Family A 1 24842 "U" protection for cover - belt width 400mm for Family A 1 24868 Protective panel set at the exit of the antenna - belt width 2000 x 400 mm for Family A 1 24747 Cover - belt width 400mm for Family A 1 24842 "U" protection for cover - belt width 400mm for Family A 1 24869 Protective panel set at the exit of the antenna - belt width 1500 x 500 mm for Family A 1 21413 Cover - belt width 500mm for Family A 1 21371 "U" protection for cover - belt width 500mm for Family A 1 21362 Protective panel set at the exit of the antenna - belt width 2000 x 500 mm for Family A 1 24749 Cover - belt width 500mm for Family A 1 21371 "U" protection for cover - belt width 500mm for Family A 1 24871 Protective panel set at the exit of the antenna - belt width 1500 x 200 mm for Family B 1 24740 Cover - belt width 200mm for Family B 1 24863 Protective panel set at the exit of the antenna - belt width 2000 x 200 mm for Family B 1 24742 Cover - belt width 200mm for Family B 1 24863 "U" protection for cover - belt width 200mm for Family B 1 24865 Protective panel set at the exit of the antenna - belt width 1500 x 300 mm for Family B 1 23527 Cover - belt width 300mm for Family B 1 21242 Protective panel set at the exit of the antenna - belt width 2000 x 300 mm for Family B 1 24744 Cover - belt width 300mm for Family B 1 21242 "U" protection for cover - belt width 300mm for Family B 1 24867 Protective panel set at the exit of the antenna - belt width 1500 x 400 mm for Family B 1 24746 Cover - belt width 3400mm for Family B 1 24843 Protective panel set at the exit of the antenna - belt width 2000 x 400 mm for Family B 1 24748 Cover - belt width 400mm for Family B 1 24843 "U" protection for cover - belt width 400mm for Family B 1 24870 Protective panel set at the exit of the antenna - belt width 1500 x 500 mm for Family B 1 23526 Cover - belt width 500mm for Family B 1 21372 Protective panel set at the exit of the antenna - belt width 2000 x 500 mm for Family B 1 24750 Cover - belt width 500mm for Family B 1 21372 "U" protection for cover - belt width 500mm for Family B 1 24872 Protective panel set at the exit of the antenna - belt width 2000 x 300 mm per THS/MN DH 150mm 1 24909 Cover - belt width 300mm per THS/MN DH 150mm 1 23262 "U" protection for cover - belt width 300mm per THS/MN DH 150mm 1 23533 Protective panel set at the exit of the antenna - belt width 2000 x 300 mm per THS/MN DH 200mm 1 24910 Cover - belt width 300mm per THS/MN DH 200mm 1 21242 "U" protection for cover - belt width 300mm per THS/MN DH 200mm 1 24857 Protective panel set at the exit of the antenna - belt width 2000 x 500 mm per THS/MN DH 150mm 1 24911 Cover - belt width 500mm per THS/MN DH 150mm 1 21371 Protective panel set at the exit of the antenna - belt width 2000 x 500 mm per THS/MN DH 200mm 1 24912 Cover - belt width 500mm per THS/MN DH 200mm 1 21372 Protective panel set at the exit of the antenna - belt width 2000 x 500 mm for Family C 1 22855 Cover - belt width 500mm for Family C 1 21364 "U" protection for cover - belt width 500mm for Family C 1 20398

Page 103: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 97

Table A • Components Item 3 7 8 9 10 11 12 15

Bel

t

Tres

pa

supp

ort p

late

- lo

ng p

art

Tres

pa

supp

ort p

late

- sh

ort p

art

Pla

te

spac

er/s

uppo

rt P

late

an

d re

flekt

or

spac

er/s

uppo

rt P

ower

su

pply

un

it an

d bl

inki

ng

light

su

ppor

t kit

Ref

lekt

or

supp

ort

0.5m

/sec

. D

rum

m

otor

w

ith w

iring

Quantity 1 1 1 1 1 1 1 1

1000 X 200 X 875 ± 50 24690 24721 24729 22956 22956 24661 21244 24715 1500 X 200 X 875 ± 50 24691 24722 24730 20354 21240 21351 21244 24715 2000 X 200 X 875 ± 50 24692 24723 24731 20354 21240 24987 21244 24715

1000 X 300 X 875 ± 75 21801 24217 24218 22956 22956 24661 21244 24716 1500 X 300 X 875 ± 75 21316 17841 17842 20354 21240 21351 21244 24716 2000 X 300 X 875 ± 75 23532 24724 24732 20354 21240 24987 21244 24716

800 X 400 X 875 ± 75 25776 25771 25772 no no 25361 25505 24717 1000 X 400 X 875 ± 75 24694 24725 24733 22956 22956 24661 21244 24717 1500 X 400 X 875 ± 75 24695 24726 24734 20354 21240 21351 21244 24717 2000 X 400 X 875 ± 75 24696 24727 24735 20354 21240 24987 21244 24717

1000 X 500 X 875 ± 75 24697 24728 24736 22956 22956 24661 21244 24718 1500 X 500 X 875 ± 75 21359 21370 21369 20354 21240 21351 21244 24718 2000 X 500 X 875 ± 75 24650 24620 24621 20354 21240 24987 21244 24718 2000 X 500 X 875 ± 75 Fam. C 24650 24915 24916 20354 21240 25361 21244 24718

2000 X 300 X 875 ± 75 per THS/MN 23532 23382 23383 20354 21240 25361 21244 24716 2000 X 500 X 875 ± 75 per THS/MN 24650 24938 24939 20354 21240 25361 21244 24718 Table B - Compatibility, Options and Spare parts Part A

Options

THS

Fam

ily

com

patib

ility

Com

plet

e co

nvey

or b

elt

Bel

t sup

ports

(fe

et)

Cas

tors

Ant

enna

fixi

ng k

it

Blu

e bl

inki

ng la

mp

for t

est r

eque

st

Bar

-cod

e re

ader

m

ount

ing

kit

Insu

ffici

ent a

ir-pr

essu

re s

enso

r ki

t

Sid

e pa

nels

kit

Pis

ton

ejec

tor

Air-

jet e

ject

or

Fam

. A p

rote

ctio

n pa

nel s

et

Quantity 1 1 1 1 1 1 1 1 1 1

Page 104: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 98

1000 X 200 x 875 ± 50 SL A 24658 21525 21548 Tab. D 21279 21613 no 21553 no no no 1500 X 200 x 875 ± 50 A B 24659 21525 21548 Tab. C 21279 21613 21614 21553 21610 22477 24739 2000 X 200 x 875 ± 50 A B 24660 24802 24803 Tab. C 21279 21613 21614 21553 21610 22477 24741

1000 X 300 x 875 ± 75 SL A 24130 21525 21548 Tab. D 21279 21613 no 21553 no no no 1500 X 300 x 875 ± 75 A B 21761 21525 21548 Tab. C 21279 21613 21614 21553 21610 22477 21412 2000 X 300 x 875 ± 75 A B 25341 24802 24803 Tab. C 21279 21613 21614 21553 21610 22477 24743

1000 X 400 x 875 ± 75 SL A 24662 21525 21548 Tab. D 21279 21613 no 21553 no no no 1500 X 400 x 875 ± 75 A B 24663 21525 21548 Tab. C 21279 21613 21614 21553 21611 22477 24745 2000 X 400 x 875 ± 75 A B 24664 24802 24803 Tab. C 21279 21613 21614 21553 21611 22477 24747

1000 X 500 x 875 ± 75 SL A 24665 21525 21548 Tab. D 21279 21613 no 21553 no no no 1500 x 500 x 875 ± 75 A B 21762 21525 21548 Tab. C 21279 21613 21614 21553 21611 22477 21413 2000 X 500 x 875 ± 75 A B 24666 24802 24803 Tab. C 21279 21613 21614 21553 21611 22477 24749 2000 X 500 x 875 ± 75 Fam.C C 25773 24802 24803 Tab. E 21279 21613 21614 21553 21611 22477 24749

2000 X 300 x 875 ± 75 per THS/MN 23540 24802 24803 Tab. E 21279 21613 21614 21553 21610 22477 Tab. E 2000 X 500 x 875 ± 75 per THS/MN 24956 24802 24803 Tab. E 21279 21613 21614 21553 21611 22477 Tab. E

Table B - Compatibility, Options and Spare parts Part B

Options Spare parts

THS

Fa

mily

co

mpa

tibilit

y

Fam

. A

LA

RG

E

prot

ectio

n pa

nel s

et

Fam

. B

pr

otec

tion

pane

l set

Fam

. B

LA

RG

E

prot

ectio

n pa

nel s

et

Set

-asi

de

cont

aine

r w

ith s

uppo

rt

LAR

GE

S

et-a

side

co

ntai

ner

with

su

ppor

t

Eje

ctio

n co

nfirm

atio

n se

nsor

and

ful

l se

t-as

ide

cont

aine

r se

nsor

kit

Ben

d ro

ller

Free

rolle

r

Pis

ton

ejec

tor

Quantity 1 1 1 1 1 1 1 1

1000 X 200 x 875 ± 50 SL A no no no no no no no 24884 24808 no 1500 X 200 x 875 ± 50 A B no 24740 no 21423 no no 21612 24884 24808 21598 2000 X 200 x 875 ± 50 A B on req. 24742 on req. 21423 on req. on req 21612 24884 24808 21598

1000 X 300 x 875 ± 75 SL A no no no no no no no 24876 20371 no 1500 X 300 x 875 ± 75 A B no 23527 no 21423 no no 21612 24876 20371 21598 2000 X 300 x 875 ± 75 A B on req. 24744 on req. 21423 on req. on req 21612 24876 20371 21598

1000 X 400 x 875 ± 75 SL A no no no no no no no 24885 24809 no 1500 X 400 x 875 ± 75 A B no 24746 no 21423 no no 21612 24885 24809 21599 2000 X 400 x 875 ± 75 A B on req. 24748 on req. 21423 on req. on req 21612 24885 24809 21599

1000 X 500 x 875 ± 75 SL A no no no no no no no 24886 21360 no 1500 x 500 x 875 ± 75 A B no 23526 no 21423 no no 21612 24886 21360 21599 2000 X 500 x 875 ± 75 A B on req. 24750 on req. 21423 on req. on req 21612 24886 21360 21599 2000 X 500 x 875 ± 75 Fam.C C no 24750 no 21423 no no 21612 24886 21360 21599

2000 X 300 x 875 ± 75 per THS/MN no Tab. E no 21423 no no 21612 22962 20371 21598 2000 X 500 x 875 ± 75 per THS/MN no Tab. E no 21423 no no 21612 24897 21361 21599

Table C - Fam. A & B antenna fixing kit for belt length of 1500 mm and 2000 mm Metal Detector aperture height Code 100 mm 21414 125 mm 21415 150 mm 21416 175 mm 21417 200 mm 21427 225 mm 21418 250 mm 21419 275 mm 21420 Table D - THS/SL and Fam. A antenna fixing kit for belt length of 1000 mm Metal Detector aperture height THS/SL Fam. A

Page 105: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 99

100 mm 24899 24900 125 mm 24899 24901 150 mm 24899 24902 175 mm 24899 24903 200 mm 24899 - - Table E - THS/MN and Fam C fixing kit Metal Detector aperture height Code THS/MN DH 150 24904 THS/MN DH 200 24905 Fam. C with aperture heigth 300 mm 24906 Fam. C with aperture heigth 325 mm 24907 Fam. C with aperture heigth 350 mm 24908 Table F - Exit Protective panel set for Fam C and THS/MN Metal Detector aperture height Code THS/MN H 150 on belt with width 300mm 24909 THS/MN H 200 on belt with width 300mm 24910 THS/MN H 150 on belt with width 500mm 24911 THS/MN H 200 on belt with width 500mm 24912 Fam. C with aperture heigth 300 mm 24913

THS Accessories - Test pieces Validity: revision 1.01, 30/10/2002 Description Quantity Code Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) - High sensitivity 1 18711 Set of quality control test samples (AISI 420 steel (ferromagnetic) and non ferrous metal) - High sensitivity 1 22607 Set of quality control test samples (AISI 420 steel (ferromagnetic) and AISI 316 Stainless steel) - Low sensitivity 1 22605 Set of quality control test samples (AISI 420 steel (ferromagnetic) and non ferrous metal) - Low sensitivity 1 22606 Sample with a ø 0.8 mm in AISI 420 steel sphere (ferromagnetic) 1 18124 Sample with a ø 1.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18125 Sample with a ø 1.2 mm in AISI 420 steel sphere (ferromagnetic) 1 18126 Sample with a ø 1.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18127 Sample with a ø 2.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18128 Sample with a ø 2.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18129 Sample with a ø 3.0 mm in AISI 420 steel sphere (ferromagnetic) 1 18130 Sample with a ø 3.5 mm in AISI 420 steel sphere (ferromagnetic) 1 18131 Sample with a ø 4.0 mm in AISI 420 steel sphere (ferromagnetic) 1 20251 Sample with a ø 4.5 mm in AISI 420 steel sphere (ferromagnetic) 1 20252 Sample with a ø 5.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22056 Sample with a ø 5.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22057 Sample with a ø 6.0 mm in AISI 420 steel sphere (ferromagnetic) 1 22058 Sample with a ø 6.5 mm in AISI 420 steel sphere (ferromagnetic) 1 22059 Sample with a ø 1.0 mm in AISI 316 Stainless steel sphere 1 18118 Sample with a ø 1.5 mm in AISI 316 Stainless steel sphere 1 18119 Sample with a ø 2.0 mm in AISI 316 Stainless steel sphere 1 18120 Sample with a ø 2.5 mm in AISI 316 Stainless steel sphere 1 18121 Sample with a ø 3.0 mm in AISI 316 Stainless steel sphere 1 18122 Sample with a ø 3.5 mm in AISI 316 Stainless steel sphere 1 18123 Sample with a ø 4.0 mm in AISI 316 Stainless steel sphere 1 20254 Sample with a ø 4.5 mm in AISI 316 Stainless steel sphere 1 20253 Sample with a ø 5.0 mm in AISI 316 Stainless steel sphere 1 22052 Sample with a ø 5.5 mm in AISI 316 Stainless steel sphere 1 22053 Sample with a ø 6.0 mm in AISI 316 Stainless steel sphere 1 22054 Sample with a ø 6.5 mm in AISI 316 Stainless steel sphere 1 22055 Sample with a ø 1.0 mm in non ferrous material sphere 1 21485 Sample with a ø 1.5 mm in non ferrous material sphere 1 21486 Sample with a ø 2.0 mm in non ferrous material sphere 1 21487 Sample with a ø 2.5 mm in non ferrous material sphere 1 21488 Sample with a ø 3.0 mm in non ferrous material sphere 1 21489 Sample with a ø 3.5 mm in non ferrous material sphere 1 21490 Sample with a ø 4.0 mm in non ferrous material sphere 1 21491

Page 106: Detector Industrial de Metales

THS – FI022GB2K8v3 --- VI - APPENDICES 100

Sample with a ø 4.5 mm in non ferrous material sphere 1 21492 Sample with a ø 5.0 mm in non ferrous material sphere 1 21493 Sample with a ø 5.5 mm in non ferrous material sphere 1 21494 Sample with a ø 6.0 mm in non ferrous material sphere 1 21495 Sample with a ø 6.5 mm in non ferrous material sphere 1 21496

THS Accessories - MD CAD - 27185 Validity: revision 1.0, 17/09/2002 Spare parts Description Quantity Code Cable 60387 1 26895